HBS 05 + AMS 10
Fuse location, HBS 05
L
EK
F3
Fuse
NIBE Part no.
Fuse (F3)
P
tot
(W)
Length
(m)
718 085
T100mA/250V
15
1
518 900*
T250mA/250V
45
3
718 086
T500mA/250V
90
6
*Fitted at the factory.
Electrical connection
HBS 05 is equipped with a terminal block for a heating
cable (EB14). The connection is fused with 250 mA (F3
on the communication board AA23). If another cable is
to be used, the fuse must be replaced with a suitable
one (see table).
Connect external heating cable (EB14) to terminal block
AA23-X1:4–6 according to following image:
5
6
4
2
3
1
KVR 10
HBS 05
X1
EB14
External heat cable
AA23
F3
Connecting automatic protection
Connection of earth leakage circuit breaker (FB1)
between terminal block (X1) and communication board
(AA23-X1:1-3). Cut off the brown and blue cores. Con-
nect the brown core connected to X1:L1 to the automatic
protection FB1:1/2 and the blue core connected to X1:N
to FB1:N. The brown core that is connected to AA23-
X1:1 must be connected to the automatic protection
FB1:2/1 and the blue core connected to AA23-X1:2 must
be connected to FB1:N.
Strip 11 mm from cores that are to be connected to the
automatic protection.
L
EK
Condensation water pipe KVR 10
Chapter 3 |
Electrical connection
22