Technical specifications
GV-HR 130-250
GV-HR 130-150
Type
Electrical data
230 V ~ 50Hz
V
Supply voltage
10
A
Fuse
2 x 100
2 x 27
W
Driving power fan
IP 21
Enclosure class
Ventilation
G4
Filter type, exhaust air filter
F7
Filter type, supply air filter
Sound pressure levels
47.4
dB(A)
Sound pressure level (L
P(A)
) at 1 m
1
50.0
dB(A)
Sound pressure level (L
P(A)
) at 1 m
2
Pipe connections
125
mm
Ventilation Ø
15
mm
Condensation water drain
Dimensions and weight
A
Efficiency class
3
2.4
m
Length, supply cable
2.0
m
Length, control cable
1,202
mm
Width
673
mm
Depth
241
mm
Height
25
kg
Weight
066 120
066 122
Part no.
1
105 m
3
/h at 50 Pa
2
250 m
3
/h at 140 Pa
3
Scale for efficiency class: A+ to G.
GV-HR 130-250
Dry temperature efficiency according to EN 308
78
(l/s)
(m
3
/h)
80
82
84
86
88
90
92
94
Temperatur
(°C)
Luftflöde
0
0
35
50
75
100
150
200
250
300
50
Efficiency
Airflow
Outdoor air: 5 °C Exhaust air 25 °C RH exhaust air: <27.7
%
GV-HR 130-150
Dry temperature efficiency according to EN 308
78
(l/s)
(m
3
/h)
80
82
84
86
88
90
92
94
Temperatur
(°C)
Luftflöde
0
0
35
50
75
100
150
200
250
300
50
Efficiency
Airflow
Outdoor air: 5 °C Exhaust air 25 °C RH exhaust air: <27.7
%
35
Chapter 12 | Technical data
NIBE GV-HR 130
Содержание GV-HR 130
Страница 1: ...IHB EN 1820 1 431877 INSTALLER MANUAL Ventilation heat exchanger NIBE GV HR 130 LEK...