NOTE
All electrical connections must be carried out
by an authorised electrician.
Electrical installation and wiring must be carried
out in accordance with the stipulations in force.
GV-HR 130 must not be powered during install-
ation.
NOTE
If the supply cable is damaged, only NIBE, its
service representative or similar authorised
person may replace it to prevent any danger
and damage.
NOTE
Communication and/or sensor cables to extern-
al connections must not be laid closer than 20
cm from high voltage cables, to prevent inter-
ference at any splices.
• Communication and sensor cables to external connec-
tions must not be laid close to high current cables.
• The minimum area of communication and sensor
cables to external connections must be 0.25 mm² up
to 50 m, for example EKKX or LiYY or equivalent.
For electrical wiring diagram, see
Display
GV-HR 130 is supplied with an enclosed display (AA4)
which is also a room sensor.
Install the display in a neutral position where the set
temperature is required. A suitable location might be on
a free inner wall in a hall approx. 1.5 m above the floor.
It is important that the display is not obstructed from
measuring the correct room temperature, for example
by being located in a recess, between shelves, behind
a curtain, above or close to a heat source, in a draught
from an external door or in direct sunlight. Closed radi-
ator thermostats can also cause problems. The display
contains a light sensor that regulates the brightness; for
this reason, it should not be placed close to a lamp.
1.
Fit the display mount on the wall.
Z1
Z2
Z3
Z4
C1
C2
C3
C4
UN
2.
Install the display on the mount by connecting the
connector and then carefully pressing the lower part
of the display against the wall.
Z1
Z2
Z3
Z4
C1
C2
C3
C4
UN
15
Chapter 5 | Electrical connection
NIBE GV-HR 130
5 Electrical connection