MENU 12 - LEVEL 3 SUPPLY AIR
Setting range: 0 - 100%
Factory setting: 75%
Here you set the speed for the supply air fan’s highest
level.
This mode is ideal when there are a lot of people in the
home.
MENU 13 - LEVEL 1 EXHAUST AIR
Setting range: 0 - 100%
Factory setting: 30%
Here you set the speed for the exhaust air fan’s lowest
level.
This mode is ideal when there is nobody at home.
MENU 14 - LEVEL 2 EXHAUST AIR
Setting range: 0 - 100%
Factory setting: 50%
Here you set the speed for the exhaust air fan’s normal
level.
MENU 15 - LEVEL 3 EXHAUST AIR
Setting range: 0 - 100%
Factory setting: 75%
Here you set the speed for the exhaust air fan’s highest
level.
This mode is ideal when there are a lot of people in the
home.
MENU 16 - T2 ADJUSTMENT
Setting range: -5 - 0 °C
Default value: -3 °C
You adjust the display’s built-in room sensor (BT50) here
so that it displays the correct temperature
MENU 17 - LEVEL 3-4 T
Setting range: 1 - 9 h
Factory setting: 3 h
Select the return time for temporary speed change
(speed 3) of the ventilation in User menu, menu 4 -
"Level 3-4 hours".
Return time is the time taken before the ventilation
speed returns to level 2.
MENU 18 - FILTER/STOP
Setting range: "On" and "off"
Factory setting: "On"
If you select "on", the filters must be replaced within 14
days after a filter alarm, otherwise GV-HR 130 will stop.
If you select "off", GV-HR 130 will continue to work, even
though the filters are soiled.
MENU 19 - ROOM/ON/OFF
Setting range: 0 - 2
Default value: 1
Here you select control of GV-HR 130:
Room control/room sensor (BT50)
0
Supply air control/supply air sensor (BT22)
1
Exhaust air control/exhaust air sensor (BT20)
2
A re-heater is required in order to heat the home with
GV-HR 130 and control the installation with supply air
or exhaust air control. In installations that do not have
reheating, GV-HR 130 is only used to ventilate the home
and to utilise the energy in the extract air. In this type
of installation, supply air control is recommended.
MENU 20 - PREHEATING
Setting range: -15 - 10 °C
Default value: -3 °C
Here you set the outdoor air temperature at which the
electrical air heater (EAH) will start.
TIP
Select -3°C if you want to prevent ice forming.
NIBE GV-HR 130
Chapter 8 | Control - Menus
26