General
All electrical equipment is connected at the factory.
• Disconnect FLM S45 before insulation testing the
house wiring.
• For the exhaust air module wiring diagram, see
• Signal cables to external connections must not be laid
close to high current cables.
• If the supply cable is damaged, only NIBE, its service
representative or similar authorised person may re-
place it to prevent any danger and damage.
NOTE
Electrical installation and service must be car-
ried out under the supervision of a qualified
electrician. Electrical installation and wiring
must be carried out in accordance with the
stipulations in force.
Connections
CONNECTING TO COMPATIBLE HEAT PUMP
Connection of supply to FLM S45
The exhaust air module is connected to an earthed single
phase wall socket or a permanent installation. For per-
manent installations, FLM S45 must be preceded by a
circuit breaker with at least a 3 mm breaking gap.
Connecting the communication to FLM S45
no. 1
S1155/S1255: The communication control cable (W6)
with connector connects to contact X6 on the PCB (AA2)
in the main product.
AA2-X6
AA2-X21-X6
W6
FLM S45 Main product
The DIP switch (AA5-S2) has to be set as follows.
ON
1
2
3
4
5
6
7
8
AA5-S2
LEK
LEK
S3
AA5-S2
AA5
AA5-S2
NIBE FLM S45
Chapter 5 | Electrical connections
18
5 Electrical connections