10

NIBE FLM 40

For the Installer

Ziehl -EBM G1G 146-AE37-07, Matningsspänning fläkt ca 225 VAC

8

9

10*

0

50

100

150

200

250

300

0

100

200

300

400

500

600

700

Tillgängligt tryck, Pa

800

Luftflöde, m

3

/h

1

2*

3

4

5

6* 7

Available static pressure

Pa

Air flow

m

3

/h

Ventilation connection

Ventilation flow

FLM 40 is connected so that all ventilation air, except for 
the kitchen fan, passes the heat exchanger (62) in the 
exhaust air module. Minimum flow should conform to the 
demands as set out in applicable norms. The ventilation 
flow should conform to applicable norms. 
Switching the ventilation capacity is described in the sec-
tion “Electrical installation” “Setting the fan capacity”.

Exhaust air duct

The kitchen flue must not be connected to FLM 40

A duct in a masonry chimney stack 

must not be used for extract air.

NOTE!

Duct installation

To prevent fan noise being transferred to the exhaust air 
devices, it may be a good idea to install a silencer in the 
duct.  This is especially important if there are exhaust air 
devices in bedrooms.
Connections can be made using flexible hoses, which 
should be stretched well and routed to allow easy replace-
ment. The extract air duct must be provided with diffusion-
tight insulation over its entire length.  Provision must be 
made for inspection of the duct. Make sure that there are 
no reductions of cross-sectional area in the form of creases, 
tight bends etc, since this will reduce the ventilation capa-
city. All joins in the ducting must be sealed and pop-riveted 
to prevent leakage. The duct system must be carried out in 
accordance with current norms. 

Adjustment

To obtain the necessary air exchange in every room of the 
house, the exhaust air devices must be correctly positioned 
and adjusted. A defective ventilation installation may lead 
to reduced exhaust air module efficiency and thus poo-
rer operating economy, and may result in damage to the 
house.

Fan diagram

Содержание FLM 40

Страница 1: ...LEK MOS GB 0802 1 NIBE FLM 40 031190 INSTALLATION AND MAINTENANCE INSTRUCTIONS NIBE FLM 40...

Страница 2: ......

Страница 3: ...___________ 9 External control of fan and brine pump ________________ 9 Ventilation connection Ventilation flow _________________________________ 10 Exhaust air duct _ ________________________________...

Страница 4: ...experience and knowledge un less they have been given supervision or instruction concerning use of the appli ance by a person responsible for their safety Children should be supervised to ensure that...

Страница 5: ...has then dropped as FLM 40 has utilised the energy in the room air The warm room air is led to FLM 40 FLM 40 increases the tem perature of the brine to the heat pump Outdoor air is drawn into the hous...

Страница 6: ...DRAG 1 Dr cken 1 Dr cken 2 Ziehen 1 Dr cken 1 Dr cken 2 Ziehen FLM 40 and its ventilation ducting require some regular maintenance where the following points should be checked The numbers in brackets...

Страница 7: ...e water seal 92 to the drip pan 93 If the water seal is empty or has a very low water level so that it gurgles water can be filled for example using a watering can through the condensation water hose...

Страница 8: ...set at the factory and should not need adjus ting Changes to the parameters can result in the heat ex changer becoming blocked by frost The buttons are locked with a code In the event of a fault indic...

Страница 9: ...ine circuit should be fitted with a pressure expansion vessel If there is a level vessel this should be replaced The brine side should be pressurised to at least 0 5 bar The pressure expansion vessel...

Страница 10: ...es for the heat medium and water heater and if necessary hot water circulation are routed backwards Install the check valve horizontally The distance from the wall must be 50 mm for both FIGHTER 1240...

Страница 11: ...ced directly above the heat pump the power supply can be connected to the heat pump s termi nal block The connection plug must however be cut off If FLM 40 is installed independently it can be connect...

Страница 12: ...e being transferred to the exhaust air devices it may be a good idea to install a silencer in the duct This is especially important if there are exhaust air devices in bedrooms Connections can be made...

Страница 13: ...ition C on the knob Setting the DIP switches Fan mode A DIP switch 5 DIP switch 6 Fan mode A fan curve off off not used off on not used on off 1 on on 2 Fan mode B DIP switch 3 DIP switch 3 Fan mode B...

Страница 14: ...nning The temperature difference applies at a room temperature of 20 degrees and 0 degrees on the brine The brine flow through FLM 40 will be from 0 1 l s 360 l h to 0 15 l s 540 l h at the above temp...

Страница 15: ...13 NIBE FLM 40 For the Installer Electrical circuit diagram Electrical circuit diagram Fr nluftsfl kt Exhaust air fan Frostvakt Frost protection K ldb rarpump Brine pump...

Страница 16: ...4 NIBE FLM 40 For the Installer Fl desriktning LEK 90 16 36 74 73 19 37 62 5 91 66 93 63 22 20 21 LEK 38 8 65 9 14 10 Gammalt Gammalt Component locations Component locations Direction of flow for brin...

Страница 17: ...onnector fan speed switch female 22 Connector fan speed switch male 36 Fan 37 Fan speed switch mode A B C 38 Switch positions 0 1 circulation pump 62 Heat exchanger 63 Air filter 65 Frost protection 6...

Страница 18: ...ur Frontabdeckungsdemontage Ansicht von unten Installationsh he im FLM 40 Ansicht von oben Vy sedd ovanifr n 445 115 305 Avluft 160 Fr nluft 160 625 600 1 440 400 95 90 300 90 510 250 350 Fritt instal...

Страница 19: ...V 50 Hz Rated output fan 113 W Rated output circulation pump 95 W Max air flow ca 250 m3 h Max cooling effect 1 6 kW Enclosure class IP 21 Sound power level 38 48 dB A Sound level in the boiler house...

Страница 20: ...in amount of fluid may run out Insert a screwdriver and turn the pump rotor Screw in the venting screw Start FLM 40 and check whether the circulation pump runs It is usually easier to start the circul...

Страница 21: ...19 NIBE FLM 40...

Страница 22: ...20 NIBE FLM 40...

Страница 23: ......

Страница 24: ...STAD NB Tel 0168 477722 Fax 0168 476998 E mail info nibenl nl www nibenl nl V lund Varmeteknik Filial af NIBE AB Brog rdsvej 7 6920 Videb k Tel 97 17 20 33 Fax 97 17 29 33 E mail info volundvt dk www...

Отзывы: