Docking
FIGHTER 2010
For the Installer
12
Abbreviations
AV
Shutoff valve
CP
Circulation pump
FG
Temperature sensor, supply line
Included with FIGHTER 2010
HR
Auxiliary relay
LP
Charge pump
RG
Return temperature sensor
Included with FIGHTER 2010
RV
Control valve
RT 10
Room thermostat
SF
Particle filter
Included with FIGHTER 2010
SV
Shunt valve
SÄV
Safety valve
TV
Drain valve
UG
Outside sensor
VVG
Hot water sensor
FIGHTER 2010 docked to an electric/oil boiler
(floating condensing)
FIGHTER 2010 is controlled by a room thermostat and
works with floating condensing on the return from the heat-
ing system. FIGHTER 2010 works in stage 1 or stage 2
depending on the outdoor air temperature.
If FIGHTER 2010 cannot meet the heating requirement the
additional heating is shunted in using the existing control
equipment.
Additional heat can be blocked above the set balance tem-
perature by means of the automatic control system in
FIGHTER 2010. Hot water production only takes place using
the existing electric/oil boiler.
The accessory RT 10 is required for this option.
P
FIGHTER 2010
AV
RV
SF
SÄV
TV
FG
RG
RT 10
RC
Extern alt
befintlig regler-
utrustning.
Accessory or
existing control
equipment