Control

23

For the Installer

FIGHTER 1220

Changing a parameter (value):

■ 

Access the required menu.

■ 

Press the Enter button, the numerical value starts to
flash

■ 

Increase or decrease the value with the Plus/Minus
buttons.

■ 

Confirm by pressing the Enter button.

■ 

Menu 1.0 is automatically displayed again 30 min-
utes after pressing the last button.

Changing parameters

To quickly return to the main menu from sub-menus
press the following:

Operating mode button

Enter button

Quick movement

NOTE! 

Ensure the operating mode is not

changed during quick movement

A key lock can be activated in the main menus by
simultaneously pressing the Plus and the Minus but-
tons. The key symbol will then be shown on the dis-
play. The same procedure is used to deactivate the
key lock.

Key lock

1.1
Periodtime HW/Total

Time Heating/Set.
Time HW/Set.

1.2
Time period

1.3
MAX-time HW-period

1.4
HW-temp/Starttemp.HW

1.5
HW-temp/Stoptemp.HW

1.6
Stop Temp. XHW

1.7
Stop compressor XHW

1.8
Interval XHW

1.9
Next XHW action 

1.10
HW running time

1.11.0
Pool settings
1.12
Return to 1.0

Hotwatertemperature
1.0

2.1
Curve coefficient

2.2
Offset heating curve

2.3
Flow Temp./MIN

2.4
Flow Temp./MAX

2.5
External adjustment

2.6.0
Own curve definition

2.7
Return temp./MAX

2.8
Degree minutes

2.9.0
HPAC settings

2.10
Return to 2.0

Flow temperature
2.0

A B

I II III

I II

5 0 . 0     C

H o t w a t e r t e m p e r a t u r e  

13.43

1.0

Example

Changing the curve slope, menu 2.1. 

■ 

The starting point is menu 1.0.

■ 

Press the plus button to move to menu 2.0.

■ 

Press the enter button to move to menu 2.1.

■ 

Press the enter button to allow the value to be
changed.

■ 

Change the value by pressing the plus or minus
buttons.

■ 

Confirm the chosen value by pressing the enter 
button.

■ 

Press the minus button to move to menu 2.10

■ 

Press the enter button to move to menu 2.0.

■ 

Press the minus button to move to menu 1.0.

Содержание FIGHTER 1220

Страница 1: ...INSTALLATION AND MAINTENANCE INSTRUCTIONS FIGHTER 1220 MOS GB 0429 1 011676 FIGHTER 1220 LEK Fighter 1220 R...

Страница 2: ......

Страница 3: ...fset 2 21 Heating curve offset 0 21 Heating curve offset 2 21 Control General 22 Changing parameters 23 Key lock 23 Quick movement 23 Menu tree 24 Main menus 27 Hot water temperature 28 Supply tempera...

Страница 4: ...d with all correspondence with NIBE 689_ _ _ _ _ _ _ _ _ _ FIGHTER 1220 _ _ kW Installation engineers Anti corrosion Enamel Stainless steel Copper The type of brine Mixing proportion freezing point Ac...

Страница 5: ...sor The refrigerant the temperature of which has now been raised is passed to the condenser where it gives off its energy to the heating medium cir cuit and if necessary to the water heater After the...

Страница 6: ...Indicates when immersion heater is con nected The line indicates which power step steps are currently connected I 2 kW additional power is connected II 4 kW additional power is connected I II 6 kW add...

Страница 7: ...g this button The change does not need to be confirmed with the enter button A Means that the hot water temperature is increased to 60 C adjustable The temperature then returns to the normal value Whe...

Страница 8: ...r first see the sec tion Room temperature Basic setting The basic heating is set using menu 2 1 and with the Offset heating curve knob If you do not know the correct settings use the basic data from t...

Страница 9: ...concrete floor structure Markaryd Area 10 5 Select curve 5 on the dis play and 1 on the Increase reduce heat knob 3 House with floor heating installed in a timber floor structure Markaryd Area 10 5 Se...

Страница 10: ...the tempera ture to about 70 C for 3 24 hours press the Extra hot water button once When the electrical module is connected for extra hot water the compressor stops The value is adjustable between 50...

Страница 11: ...lly follows the operation of the heat pump There is a special operating mode for continuous operation for 10 days followed by return to normal mode this may be used before stable circu lation has been...

Страница 12: ...mediate frost protected circuit must be provided because of the risk of dirt and freezing in the evaporator This requires an additional heat exchanger Pipe installation must be carried out in accordan...

Страница 13: ...the connection of ambient cold possible To avoid condensation all pipes and other cold sur faces must be insulated with diffusion proof material Where the cooling demand is high fan convectors with dr...

Страница 14: ...kPa 250 500 750 0 l h 1000 2 4 8 20 80 40 Tryckfall Fl de 1250 1500 1750 60 6 2500 2250 2000 FIGHTER 1215 7 FIGHTER 1215 10 0 0 mvp kPa 250 500 750 0 l h 1000 2 4 8 20 80 40 Tryckfall Fl de 1250 1500...

Страница 15: ...perature limiter thermostat compressor or the immersion heater can be damaged The automatic heating control system circulation pumps and their wiring are internally fuse protected with a miniature cir...

Страница 16: ...e contactor Remove the 2 orange straps on terminal block 9 and connect the control voltage to the outermost terminals marked L and N on the wiring diagram LEK PE L2 L3 N L1 PE L1 L2 L3 PE L2 L3 N L L1...

Страница 17: ...mmersion heater out kW Knob position Max phase A 5 kW Max phase A 7 kW Max phase A 8 5 kW Max phase A 10 kW 6 4 C 14 3 16 2 17 4 18 6 9 3 B 9 9 11 8 13 0 14 2 9 9 D 18 6 20 5 21 7 22 9 Max hot water t...

Страница 18: ...one of the phases the immersion heater will step down the output until it can be connected again The control system must be set for the installation s main fuse so that the load monitor can work corr...

Страница 19: ...onitor is required for the collector installation this can be connected to positions 16 17 on terminal block 14 In order for this to be active you must change menu 9 2 11 brine pressostat to On The co...

Страница 20: ...ure limiter TB has tripped Indicated as a TB alarm The motor cut out MS has tripped indicated by an MS alarm Pressure level monitor brine accessory indicated as pressure level brine Brine temp low ind...

Страница 21: ...menu 9 2 12 The heat pump cannot start because EP electric boil er mode only is selected The brine pump is now operational together with the filling pump The fluid can circulate via the mixing vessel...

Страница 22: ...ine pump 10 days from menu 9 2 12 to run the brine pump continuously for 10 days After 10 days the brine pump automatically returns to normal operation Ensure the brine and heating medium pumps are ve...

Страница 23: ...b is then set A suitable value for floor heating is 1 and for radiator systems 2 Offset heating curve 2 Setting using diagrams 30 40 50 60 70 C FRAMLEDNINGSTEMPERATUR 40 C UTETEMPERATUR 10 0 10 20 30...

Страница 24: ...ting mode button followed by enter quick movement to return to menu 1 0 Information is presented on the display about the status of the heat pump and the electric boiler Menu 1 0 is nor mally shown on...

Страница 25: ...1 2 Time period 1 3 MAX time HW period 1 4 HW temp Starttemp HW 1 5 HW temp Stoptemp HW 1 6 Stop Temp XHW 1 7 Stop compressor XHW 1 8 Interval XHW 1 9 Next XHW action 1 10 HW running time 1 11 0 Pool...

Страница 26: ...1 11 1 Pooltemperatur inst 1 11 2 Diff pool min temp 1 11 3 Poolperiod 1 11 4 Poolpause 1 11 5 Sensor typ 1 11 6 Return to 1 11 0 Hotwatertemperature 1 0 4 1 Outdoor avg temp 4 2 Return to 4 0 Outdoor...

Страница 27: ...3 3 7 3 9 Set time Monday Sunday 7 3 10 Return to 7 3 0 8 1 1 Operation mode types 8 1 2 Language 8 1 3 Contrast 8 1 4 Light intensity 8 1 5 Return to 8 1 0 8 2 1 Summer mode temp 8 2 2 Winter mode t...

Страница 28: ...tep 9 1 3 Add heat run time 9 1 4 Return to 9 1 0 Service menues 9 0 9 2 1 Max HW temp 9 2 2 Flow diff HP 9 2 3 Diff HP Add 9 2 4 Electric boiler 9 2 5 System 2 Present 9 2 6 Room disp Present 9 2 7 C...

Страница 29: ...bmenus to this menu Menu 9 0 Service menues This menu and its submenus are only shown on the display screen when access has been selected in menu 8 1 1 Values can be read and various settings can be m...

Страница 30: ...u 1 10 HW running time How long hot water heating has been in progress is shown here accumulated 2 0 6 0 m i n P e r i o d t i m e H W T o t a l 1 1 1 4 d ay s I n t e r v a l X H W 1 8 9 0 h 1 0 m i...

Страница 31: ...emperature to the heating system is shown here The value is adjustable between 10 and 65 C The calculated flow temperature never exceeds the set level irrespective of the outdoor temperature curve slo...

Страница 32: ...of 20 is chosen here The value is adjustable between 0 and 60 Menu 2 6 3 Set temperature Here you select at what outside temperature the break point shall occur The value is adjustable between 0 and...

Страница 33: ...ts is set here The val ue is adjustable between 10 and 60 2 0 m i n T i m e b e t w e e n s t a r t s 5 3 N N Menu 5 4 Compr starts at How low the degree minutes may drop before the a compressor start...

Страница 34: ...C o m p r e s s o r t y p e 5 1 4 U Menu 5 21 Return Pressing the enter button returns you to menu 5 0 R e t u r n 5 2 1 Menu 7 1 Date The current date is set Menu 7 3 0 Day change period 1 Settings e...

Страница 35: ...e time for the day change e g night reduction is chosen here S e t T i m e M o n d a y 7 4 3 U U Menu 7 5 0 Timer XHW Settings are made in the submenus of this menu when extra hot water is required on...

Страница 36: ...nd menu type are set on the submenus to this menu D i s p l a y s e t t i n g s 8 1 0 Menu 8 1 1 Operation mode types The menu type is chosen here Normal extended or service Normal covers the normal u...

Страница 37: ...ting selected on the load monitor card 2 is shown here knob 100 1 6 A F u s e s i z e 8 3 4 Menu 8 3 1 Current phase 1 Shows the measured current from phase 1 3 5 A C u r r e n t p h a s e 1 8 3 1 Men...

Страница 38: ...actory settings can be made on the sub menus in this menu O p e r a t i n g m o d e s e t 9 2 0 Menu 9 2 1 Max HW temp Here the maximum boiler temperature is shown The value is selected on the load mo...

Страница 39: ...y i n g s e t 9 2 9 0 S Menu 9 2 9 1 Floor drying The floor drying program is chosen from this sub menu The options are Prog 1 On Prog 2 On or Off The heat pump must be in Winter mode selected with t...

Страница 40: ...f B r i n e p r e s s o s t a t 9 2 1 1 S Menu 9 2 12 Brinepump 10 days The brine pump can be active for 10 days when the installation is started The basic setting is Off O f f B r i n e p u m p 1 0...

Страница 41: ...Q u i c k s t a r t 9 3 S TEST Forced driven operation Menu 9 4 0 TEST Forced operat Test of outputs automatic return after 8 hours Only for service personnel T E S T F o r c e d o p e r a t 9 4 0 S M...

Страница 42: ...he compressor is blocked and FIGHTER 1220 switches to electric boiler mode No hot water is produced This may be due to No or low flow on the brine pump 16 Closed thermostat valves A L A R M H P 1 1 0...

Страница 43: ...T W A T E R S E N S O R 1 0 A L A R M F L O W 1 0 Alarm Flow High flow temperature 1 High flow temperature 2 extra shunt group accessory High return temperature The following alarm stops the compress...

Страница 44: ...trips repeatedly call an electrician Cause Compressor and electric module do not heat Action Check and replace blown circuit and main fuses Cause The compressor does not run because of a too low set...

Страница 45: ...e bent down and emptied in a small bowl Now loosen the connection on Brine in a little to allow air to enter so the heat pump s collector side is emptied completely When the circuit is empty the requi...

Страница 46: ...for servic ing An area of 800 mm is required in front of FIGHTER 1215d for service work When FLM 30 is fitted on FIGHTER 1215 the distance to the wall should be 50 mm 598 179 525 525 30 399 454 144 32...

Страница 47: ...e 65 Drying filter 67 Contactor electric module step 2 69 Contactor compressor operation 70 Connection heating flow 22 mm o d 71 Connection heating return 22 mm o d 72 Hot water circulation VVC Enamel...

Страница 48: ...I I II I II 5 0 0 C Va r m v a t t e n t e m p 1 0 8 88 75 116 115 1 Component placement 46 FIGHTER 1220 For the Installer LEK 41 18 65 17 112 111 110 27 7 42 48 28 33 LEK 16 76 87 24 35 96 19 4 86 94...

Страница 49: ...Component placement 47 For the Installer FIGHTER 1220 LEK 9 3 39 26 25 6 69 67 10 LEK 1 32 29 LEK 73 70 99 71 58 75 95 72 74 LEK 2 34 97 100 101 102 14...

Страница 50: ...Wiring diagram 3 x 400 V N FIGHTER 1220 For the Installer 48 Sheet 1 4 Compressor Immersion heater Supplied connectied 6 kW Relay board...

Страница 51: ...Wiring diagram 3 x 400 V N 49 For the Installer FIGHTER 1220 Sheet 2 4 Compressor Soft starter Heating medium pump 3 way valve Relay card...

Страница 52: ...Wiring diagram 3 x 400 V N FIGHTER 1220 For the Installer 50 Sheet 3 4 Brine pump Relay board...

Страница 53: ...temp Current phase 3 Current phase 2 Current phase 1 Not function Tariff B Tariff A EBV card Temp set back 1 Outdoor sensor Extra hot water Hot water Heating water return 1 Heating water flow 1 Hot ga...

Страница 54: ...edium flow l s 0 13 0 18 0 22 0 26 Max temp supply return C 60 50 IP 21 Volume water heater litres 160 Starting current A 24 24 24 26 Fuse incl imm heater 6 kW A 16 16 20 20 Output brine pump W 130 17...

Страница 55: ...40 Two 4 5 LEK LEK LEK NIBE AB Utete mp era tur giv are Ou tdo or tem perature sensor Aussentem peratur f h ler Artikel 018764 Level vessel with safety valve Part no 85 024413 52 424091 15 85 Particle...

Страница 56: ...PAC Part no 089 265 Level monitor NV 10 Part no 089 315 L E K L E K 1 0 15 20 25 30 C Room thermostat RT 10 Part no 418 366 Extra shunt group Used when there is a need of two different supply tem pera...

Страница 57: ...55 For the Installer FIGHTER 1220...

Страница 58: ...FIGHTER 1220 For the Installer 56...

Страница 59: ......

Страница 60: ...aajat NIBE AB n sivuliike Pohjant hdentie 17 01451 Vantaa Puh 09 274 697 0 Fax 09 274 697 40 E mail info haato com www haato fi NIBE Systemtechnik GmbH Am Reiherpfahl 3 29223 Celle Tel 05141 7546 0 Fa...

Отзывы: