Gutter drainage
NOTE
Bend the hose to create a water seal, see illustra-
tion.
LEK
Frostfritt
djup
Water seal
Frost free
depth
Water seal
LEK
Exhaust air/air heat
pump
■
The outlet of the condensation water pipe must be at
frost free depth.
■
Route the pipe downward from the air/air heat pump.
■
The condensation water pipe must have a water seal
to prevent air circulation in the pipe.
■
The installation length can be adjusted by the size of
the water seal.
Electrical connection
NOTE
The electrical installation and wiring must be
carried out under the supervision of an author-
ised electrician.
General
Connection between AG-CH10 and AG-AA10 / AG-AC10
is made via the enclosed electrical distribution box as il-
lustrated.
Electrical cabinet
Condensation water pipe
Heating cable/
Electrical cable
AG-CH10 is equipped with terminal board for connection
of heating cable and outdoor unit. The connection is
fitted with a 250 mA fuse at the factory.
If a cable length other than 3 m is used, the fuse (F3)
must be replaced with the one enclosed.