Start-up and inspection
Preparations
Connect AMS 10 to ACVM 270 (refrigerant pipe and wir-
ing) and connect ACVM 270 to the climate system.
Filling the climate system
1. Ensure that the pressure gauge (BP5) is visible.
2. Connect a hose to the filling valve (QM1) and open
the valve to fill the boiler and the radiator system.
3. After a while note that the pressure on the pressure
gauge (BP5) can be seen to rise.
4. When the pressure has reached about 0.25 MPa (2.5
bar) the safety valve (FL2) starts to release air mixed
with water. Close the filling valve (QM1).
LEK
FL2
BP5
LEK
LEK
LEK
QM1
QM20
QM60
QM24
Venting the climate system
Vent ACVM 270 through the safety valve (FL2), bleed
screws (QM20, QM24 and QM60), and the rest of the cli-
mate system through the relevant vent valves.
Keep topping up and venting until all air has been removed
and the correct pressure has been obtained.
Filling the hot water coil
The hot water coil is filled by opening a hot water tap.
Commissioning
AMS 10
NOTE
Do not start AMS 10 at outdoor air temperatures of
-20 C or less.
1. Check that the miniature circuit breaker (FA2) in
ACVM 270 is on.
ACVM 270
1. Check that the temperature limiter (FD1) has not
tripped.
2. Switch on the circuit breaker and check that the mini-
ature circuit breaker (FA1) in ACVM 270 is on.
3. Set switch (SF1) to " 1" (the switch should be switched
on 6 hours before the compressor can be started).
When switch (SF1) is set to "0" - wait at least 1 minute
before setting it back to "1".
4. Select operating mode "Add. heat only" by holding in
the operating mode button for 7 seconds).
5. Set the date and time in menu 7.1 and 7.2.
6. Select “Service" in menu 8.1.1.
7. Select additional heat type in menu 9.2.8.
8. Set the fuse size on knob (R24). Check the value in
menu 8.3.1.
9. Set the max immersion heater output on knob (R25).
Check the value in menu 8.3.2.
10. Select the desired curve slope in menu 2.1.2 and set
the parallel offset using the knob. Also see section
Default setting on page 11.
11. Check that the hot water temperature in menu 1.0
exceeds 25 C.
12. When point 11 has been carried out, select operating
mode "Auto".
The heat pump starts 30 minutes after the outdoor unit is
powered up if there is a demand.
Setting system flow heating
1. Ensure that the heat pump produces heating for the
climate system.
2. Select “On” in menu 9.6.2.
3. Select ”40
4. Check the supply and return temperatures in menu
2.5. Adjust the circulation pump speed in menu 2.1.5
so that the difference between these temperatures is
according to the diagram below.
5. Select ”Off” in menu 9.6.2.
0
2
4
6
8
10
12
-15
-10
-5
0
5
10
15
20
25
Δ
T (°C)
Utomhustemperatur (°C)
Outdoor temperature
Radiator system
Under floor heating systems
Setting system flow cooling
A temperature difference of dt=7 K is recommended in
most cases. To achieve this, the following setting can be
selected:
9
7
5
3
kW
Dimensioned cooling output
Qc
90
70
60
60
%
Menu 2.2.5
The table shows the recommended output position, de-
pending on the dimensioned cooling output. Go to menu
2.2.5 for further adjustment of pump speed.
NIBE™ SPLIT ACVM 270
36
For the Installer
Start-up and inspection
Содержание ACVM 270
Страница 2: ...LEK LEK 1 2 LEK LEK 7 LEK 5 6 LEK 3 4 LEK LEK LEK LEK AMS 10 8 LEK LEK AMS 10 12 ...
Страница 66: ...Electrical circuit diagram ACVM 270 NIBE SPLIT ACVM 270 66 Miscellaneous Electrical circuit diagram ...
Страница 67: ...67 NIBE SPLIT ACVM 270 Miscellaneous Electrical circuit diagram ...
Страница 68: ...NIBE SPLIT ACVM 270 68 Miscellaneous Electrical circuit diagram ...
Страница 69: ...69 NIBE SPLIT ACVM 270 Miscellaneous Electrical circuit diagram ...
Страница 70: ...NIBE SPLIT ACVM 270 70 Miscellaneous Electrical circuit diagram ...
Страница 94: ......
Страница 95: ......