AMS 10-12
Cable holder
TB
Connect phase (brown), neutral (blue), communication
(black and grey) as well as earth (yellow/green) as illus-
trated:
L
N
1
2
3
L
N
2
3
PE
(AMS 10-12:-X1)
(ACVM 10-270:-X2)
N
L
1
2
3
L
N
2
3
PE
(AMS 10-8:-X1)
(ACVM 10-270:-X2)
brown
blue
black
grey
yellow/green
5x2.5 mm2
TB
X2
AMS 10-12
ACVM 270
Setting max power, electrical addition
Setting the different maximum immersion heater outputs
is performed using the knob (R25) on the load monitor
board (AA22). Set value displayed in menu 8.3.2. The fol-
lowing table only applies when menu 9.2.8 Add. heat type
is set to "Internal power 1" (factory setting).
L3 (A)
Compressor
L2 (A)
L1 (A)
Max.
electric
power
Knob
posi-
tion
Immer-
sion
heater,
output
(kW)
off
on
0
15
0
0
0
-
0.0
0
15
4.3
5.3
1
-
2.0
0
15
8.7
9.7
2
A
4.0
0
15
13
14
3
B
6.0
13
-
13
14
4
C
9.0
Setting max boiler temperature
The setting of the different maximum boiler temperatures
is made on the knob (R26) on the load monitor board
(AA22). Set value is displayed in menu 9.3.1.
Knob position
Boiler temperature
A
55
B
60
C
65
D
65
E
65
F
65
EBV board, terminal and wiring diagram
The following connections are made on the EBV board
(AA22).
See page 66 for complete wiring diagram of board.
AA22-X1
AA22-X4
AA22-X2
AA22-R24
AA22-R25
AA22-R26
Connecting the outside sensor
Install the outdoor temperature sensor in the shade on a
wall facing north or north-west, so it is unaffected by the
morning sun. Connect the sensor to terminal block X1:1
and X1:2 on the load monitor board (AA22) via cable
grommet UB4. Use a 2-core cable of at least 0.5 mm
2
.
If the outside sensor cable runs close to power cables,
shielded cable must be used.
If a conduit is used it must be sealed to prevent condensa-
tion in the sensor capsule.
Connecting the current limiter
NOTE
Only applies to 3X400V.
When many power consumers are connected in the
property at the same time as the electric addition is oper-
ating, there is a risk of the property's main fuse tripping.
ACVM 270 is equipped with an integrated current limiter
that controls the electrical steps and the compressor. If
necessary, the electrical steps are disengaged and/or the
compressor frequency is reduced.
33
NIBE™ SPLIT ACVM 270
For the Installer
Electrical installation
Содержание ACVM 270
Страница 2: ...LEK LEK 1 2 LEK LEK 7 LEK 5 6 LEK 3 4 LEK LEK LEK LEK AMS 10 8 LEK LEK AMS 10 12 ...
Страница 66: ...Electrical circuit diagram ACVM 270 NIBE SPLIT ACVM 270 66 Miscellaneous Electrical circuit diagram ...
Страница 67: ...67 NIBE SPLIT ACVM 270 Miscellaneous Electrical circuit diagram ...
Страница 68: ...NIBE SPLIT ACVM 270 68 Miscellaneous Electrical circuit diagram ...
Страница 69: ...69 NIBE SPLIT ACVM 270 Miscellaneous Electrical circuit diagram ...
Страница 70: ...NIBE SPLIT ACVM 270 70 Miscellaneous Electrical circuit diagram ...
Страница 94: ......
Страница 95: ......