Always be aware when configuring events to prevent the programming of conflicting ones that
can lead to undesirable behaviour of the outputs.
5.5
Loop configuration
Menu
→
Field
→
Loops
This menu is used to configure the loops. Loop 1 is enable by default, if more loops are installed, they
must first be enable through this menu. Use the right arrows to navigate through the loops The menu
contains the following items:
Loop configuration description:
•
Type
- type of loop installed (limited to Apollo loop for now);
•
Devices
- number of devices in the current loop;
•
Name
- the name and id of the loop;
•
Status
- the current status of the loop, it can have the following:
– Online
- loop is working correctly;
– Offline
- loop is not present or unable to communicate;
– Comm failure
- There is a problem with the loop and communications are failing;
– Disabled
- loop is disabled and communications are disabled.
•
Firmware version
- version of the loop firmware.
Use the
Configure
to update the firmware, the
Scan
to force the loop to perform a scan for new
devices and the button
Enable
/
Disable
to enable or disable the loop. Disabled loops will not trigger
alarms or faults and will not communicate with the devices installed in its interface.
There is no need to force a scan in a loop because the loop is always querying the devices and scanning
for new ones. When a new device appears on the loop, it will automatically be placed in zone 1.
5.6
Field configuration
Menu
→
Field
→
Field configuration
Several global configurations of the panel can be set in this area:
•
Common delay
- This field sets a global delay for all the sounders in the system, when in day mode.
This delay only applies to detectors.
•
Permanent delay
- This field sets a permanent delay for all the sounders in the system independently
day/night mode configuration. This delay only applies to detectors.
•
Evacuate transition delay
- Sets a delay to make sounders change its sound to evacuation after an
alarm from a detector. Alarms from manual callpoints will instantly trigger the evacuation sound while
detectors will trigger the alarm sound.
•
Sounders
- sets up the behaviour of the loop sounders in the system:
– Common
- when an alarm is triggered, all the sounders is the system will be activated;
– Zonal
- sounders connected to SND1 and SND2 and the ones that are in the same zone as the
device in alarm will be activated, sounders in other zones will not suffer any change.
•
Polling LED
- enter this menu to select the devices that will blink its led when they are working;
•
Re-sound on new alarm
- activate this, if you want sounders to be activated again when a new alarm
triggers, after they had already been silenced.