User Manual
Version 0.10
8
Specifications
Dimensions
436x443x110 mm
Main power
110 - 240 VAC
50/60Hz
150W
Batteries
Min: 2 x 12V 12Ah in series
Max: 8 x 12V 12Ah in 24V pairs
Working environment
Indoor use
Temperature: -5 a 45ºC
Relative humidity: <95% (no condensation)
Maximum number of zones zones
120
Maximum number of loops
4
Maximum number of devices
126 per loop (Apollo XP95/Discovery)
254 per loop (Apollo CoreProtocol)
Fire outputs
2x supervised: 28V
1
100mA
Sounder outputs
2x supervised: 28V
1
500mA
Fault outputs
28V
1
100mA (in Off state)
Auxiliary outputs
2x 28V
1
500mA shared
Relay outputs
3x 250VAC 5A
Terminating resistor (supervised outputs)
10 k
Ω
Max battery impedance
800 m
Ω
Network
CAN + Ethernet
External memory devices
Micro SD Card + USB flash drive
Other features
Sounders delay
Scheduled day/night mode
Alarm counter (more than 1 million alarms)
Test mode
Polling led
Zones type A and B
Logic event programming
Event logging
Custom logo
Table 13:
Technical details
1
When mains is not present, the voltage may vary from 28V to 21.6V, according to the battery voltage.
25
25 / 26