User Manual

Version 5.3

6.

Press the 

Delay Mode

 key to move to the next step. A double beep will sound in case of success, or an error beep in case of failure returning

to step 5;

7.

The  

Earth  

LED will start blinking, indicating that the zone should be activated using a manual callpoint (if more than one zone is being

configured, then all of them should be activated before proceeding). If the value of a zone is not acceptable by the FIREWALL, then the
zone’s alarm LED will remain on until a correct value is read. If the zones in configuration do not have a callpoint, then this step can be
ignored by pressing the 

Buzzer

 key and jumping to the last step;

8.

Press the 

Delay Mode

 key to move to the next step. A double beep will sound in case of success, or an error beep in case of failure returning

to step 7;

9.

A double beep will be emitted in case of a successful operation returning to the group selection.

Note

: This feature is available since version 

FW 3.30

.

7.8  Maintenance setup:

The maintenance warning can be configured with the values disabled, 6 months, 1 year and 2 years.

1.

Press 

Buzzer 

and 

Sounder 

keys to increase and decrease the maintenance period.

2.

The delay is associated to LEDs  

Earth

,  

Battery

  and  

Battery

 

state

. All LEDs OFF corresponds to maintenance

disabled and the maximum maintenance period corresponds to all LEDs ON.

3.

Press 

Delay Mode

 

key to accept and 

Reset

 key to cancel.

4.

A double beep will be emitted in case of a successful operation, and a single beep otherwise, backing to the previous
state.

When the period is reached the FIREWALL will enable its sounder and the 

Buzzer

 LED will blink fast. The timer can be

reset by entering test mode (see 7.6) or by setting factory defaults (see 7.1.2).

Note

: This feature is available since version 

FW 3.30

.

8 - Specifications:

Main power

100 – 240 VAC
50/60Hz
45VA

Battery

12VDC
7Ah

,or 2x

6VDC 

1

12Ah

Standby current

60mA

Maximum current

1A

Peak current

1,3A

24 VDC auxiliary output

24VDC
500mA

Fuses

Main power

4A

24V

1,6A

Sounder

500mA 

2

Sounder(s) output

24VDC
500mA

Relay contacts

250VAC
10A

Zones

24V
< 60mA
up   to   32  conventional  detectors,   with   termination   resistance   of   3300Ω,
1/4W in parallel (Callpoints with zener diodes of 5V1, 1/4W in series)

Auxiliary   outputs   by
zones (open-collector)

80VDC
500mA

Dimensions

Length:

255 mm

Height:

360 mm

Depth:

93 mm

Cable entries:

8 x Ø20mm

Table 4: Technical specifications

1

 – Recommended for 16 zones models.

2

 – Depending on version, sounder circuit may be protected by a PTC instead of a fuse.

8 / 8

Figure 19:

Maintenance setup

group selected.

Содержание EN 54-2

Страница 1: ...o 16 ZONES EC Certificate of Conformity ref NGQ05020008 NIBBLE Engenharia Lda Rua Júlio Dinis 265 1D 4785 330 Trofa Portugal EN 54 2 EN 54 4 FIRE DETECTION AND FIRE ALARM SYSTEMS CONTROL AND INDICATING EQUIPMENT POWER SUPPLY EQUIPMENT FIRE ALARM CONTROL PANEL 1 8 ...

Страница 2: ... is available an auxiliary output that can be configured to signal a failure or an alarm detection in the corresponding zone Each of these open collector outputs can sink up to 500mA 2 4 Automatic test The FIREWALL has a test mode which resets the system automatically after an alarm see 7 6 allowing the system to be tested by a single person 2 5 Smart setup The FIREWALL can be configured to adapt ...

Страница 3: ...ion of fails due to short circuit or open circuit It should be used a termination resistor of 3300Ω 1 4W at the end of line and in parallel with the sounder s 4 5 Auxiliary power It is available an auxiliary output to power external equipments up to 500mA 24VDC 4 6 Battery It is mandatory to use a battery lead acid not included with the equipment of 12VDC 7Ah or two batteries of 6VDC 12Ah connecte...

Страница 4: ...le to detect short circuits or open circuits If a short circuit is detected this LED blinks fast in case of open circuit it will blink slowly This LED also indicates if a zone is active or not When permanently ON it indicates inactive zone 6 1 3 Zone alarm indication LED This LED indicates an alarm in the corresponding zone If it blinks fast it means that the alarm was signaled at a callpoint If i...

Страница 5: ...t circuit occurs the LED blinks fast and when an open circuit is detected the LED blinks slowly 6 1 16 Sounder fuse fail indication LED When the maximum specifications for sounders output is not respected 500mA the fuse opens the circuit to prevent damages When this happens the yellow LED indicates it 6 1 17 Disabled indication LED When any functionality of the FIREWALL is deactivated a zone for e...

Страница 6: ...a successful operation and a single beep otherwise 7 1 General These general configurations allow to change the access code and to reset all parameters to the default ones Note Resetting the parameters to the default values will also set the access code to the default one Buzzer Sounder Sounder Buzzer 7 1 1 Change access code 1 Press Z1 key 2 A double beep is emitted 3 Enter new code using any com...

Страница 7: ...f an alarm To enter the test mode follow the next procedure 1 Press the Buzzer and Siren keys to increase or decrease the alarm time before perform the automatic reset It can be configured with the values of 1s 5s 10s 15s 30s and 1min 2 The selected delay is represented by the LEDs Main power 24VDC Fuse Earth Battery and Battery state A delay of 1s is represented by all LEDs off and the maximum de...

Страница 8: ...elay is associated to LEDs Earth Battery and Battery state All LEDs OFF corresponds to maintenance disabled and the maximum maintenance period corresponds to all LEDs ON 3 Press Delay Mode key to accept and Reset key to cancel 4 A double beep will be emitted in case of a successful operation and a single beep otherwise backing to the previous state When the period is reached the FIREWALL will enab...

Отзывы: