User Manual
Version 5.3
6.
Press the
Delay Mode
key to move to the next step. A double beep will sound in case of success, or an error beep in case of failure returning
to step 5;
7.
The
Earth
LED will start blinking, indicating that the zone should be activated using a manual callpoint (if more than one zone is being
configured, then all of them should be activated before proceeding). If the value of a zone is not acceptable by the FIREWALL, then the
zone’s alarm LED will remain on until a correct value is read. If the zones in configuration do not have a callpoint, then this step can be
ignored by pressing the
Buzzer
key and jumping to the last step;
8.
Press the
Delay Mode
key to move to the next step. A double beep will sound in case of success, or an error beep in case of failure returning
to step 7;
9.
A double beep will be emitted in case of a successful operation returning to the group selection.
Note
: This feature is available since version
FW 3.30
.
7.8 Maintenance setup:
The maintenance warning can be configured with the values disabled, 6 months, 1 year and 2 years.
1.
Press
Buzzer
and
Sounder
keys to increase and decrease the maintenance period.
2.
The delay is associated to LEDs
Earth
,
Battery
and
Battery
state
. All LEDs OFF corresponds to maintenance
disabled and the maximum maintenance period corresponds to all LEDs ON.
3.
Press
Delay Mode
key to accept and
Reset
key to cancel.
4.
A double beep will be emitted in case of a successful operation, and a single beep otherwise, backing to the previous
state.
When the period is reached the FIREWALL will enable its sounder and the
Buzzer
LED will blink fast. The timer can be
reset by entering test mode (see 7.6) or by setting factory defaults (see 7.1.2).
Note
: This feature is available since version
FW 3.30
.
8 - Specifications:
Main power
100 – 240 VAC
50/60Hz
45VA
Battery
12VDC
7Ah
,or 2x
6VDC
1
12Ah
Standby current
60mA
Maximum current
1A
Peak current
1,3A
24 VDC auxiliary output
24VDC
500mA
Fuses
Main power
4A
24V
1,6A
Sounder
500mA
2
Sounder(s) output
24VDC
500mA
Relay contacts
250VAC
10A
Zones
24V
< 60mA
up to 32 conventional detectors, with termination resistance of 3300Ω,
1/4W in parallel (Callpoints with zener diodes of 5V1, 1/4W in series)
Auxiliary outputs by
zones (open-collector)
80VDC
500mA
Dimensions
Length:
255 mm
Height:
360 mm
Depth:
93 mm
Cable entries:
8 x Ø20mm
Table 4: Technical specifications
1
– Recommended for 16 zones models.
2
– Depending on version, sounder circuit may be protected by a PTC instead of a fuse.
8 / 8
Figure 19:
Maintenance setup
group selected.