background image

User Manual

Version 5.3

6 - Control and Indication:

6.1  Front panel user interface:

1

Zone activation key

10

24VDC fuse fault indication LED

2

Zone fault indication LED

11

Earth circuit fault indication LED

3

Zone alarm indication LED

12

Battery presence indication LED

4

Internal buzzer silence key

13

Battery charging indication LED

5

External sounder silence key

14

General fault indication LED

6

Reset key

15

Sounder fault indication LED

7

Delay Mode key

16

Sounder fuse fault indication LED

8

General Alarm indication LED

17

Disabled indication LED

9

Main-power indication LED

18

System fault indication LED

19

Access level indication LED

Table 1: Legend of Front panel user interface

6.1.1  Zone activation key:

With this key is possible to activate or deactivate the corresponding zone.

Note

: Action only available with level 2 access (after the introduction of the access code or key).

6.1.2  Zone fail indication LED:

The detection circuits of each zone are monitored to make possible to detect short-circuits or open-circuits. If a short-circuit is detected this LED

blinks fast, in case of open-circuit it will blink slowly.

This LED also indicates if a zone is active or not. When permanently ON it indicates inactive zone.

6.1.3  Zone alarm indication LED:

This LED indicates an alarm in the corresponding zone. If it blinks fast, it means that the alarm was signaled at a callpoint. If it is permanently ON,

it means that the alarm was signaled by a detector.

6.1.4  Internal buzzer silence key:

With this key, it is possible to silence the internal buzzer which is activated every time that an alarm or a fail occurs.

Note

: Once silenced, the buzzer will only be activated when a new alarm or fail occurs.

6.1.5  External sounder silence key:

Once detected a fire alarm, the sounder will be activated. It is possible to silence the sounder pressing this key, or reactivate it by pressing again

the key. Even when there is not any alarm, it is possible to activate the sounder manually.

Note:

 Action only available with level 2 access (after the input of the access code or key).

4 / 8

Figura 10: Front panel user interface for 16 zones model.

1

7

6

5

4

14

12

8

9

10
11

19

18

16

15

17

13

3

2

Содержание EN 54-2

Страница 1: ...o 16 ZONES EC Certificate of Conformity ref NGQ05020008 NIBBLE Engenharia Lda Rua Júlio Dinis 265 1D 4785 330 Trofa Portugal EN 54 2 EN 54 4 FIRE DETECTION AND FIRE ALARM SYSTEMS CONTROL AND INDICATING EQUIPMENT POWER SUPPLY EQUIPMENT FIRE ALARM CONTROL PANEL 1 8 ...

Страница 2: ... is available an auxiliary output that can be configured to signal a failure or an alarm detection in the corresponding zone Each of these open collector outputs can sink up to 500mA 2 4 Automatic test The FIREWALL has a test mode which resets the system automatically after an alarm see 7 6 allowing the system to be tested by a single person 2 5 Smart setup The FIREWALL can be configured to adapt ...

Страница 3: ...ion of fails due to short circuit or open circuit It should be used a termination resistor of 3300Ω 1 4W at the end of line and in parallel with the sounder s 4 5 Auxiliary power It is available an auxiliary output to power external equipments up to 500mA 24VDC 4 6 Battery It is mandatory to use a battery lead acid not included with the equipment of 12VDC 7Ah or two batteries of 6VDC 12Ah connecte...

Страница 4: ...le to detect short circuits or open circuits If a short circuit is detected this LED blinks fast in case of open circuit it will blink slowly This LED also indicates if a zone is active or not When permanently ON it indicates inactive zone 6 1 3 Zone alarm indication LED This LED indicates an alarm in the corresponding zone If it blinks fast it means that the alarm was signaled at a callpoint If i...

Страница 5: ...t circuit occurs the LED blinks fast and when an open circuit is detected the LED blinks slowly 6 1 16 Sounder fuse fail indication LED When the maximum specifications for sounders output is not respected 500mA the fuse opens the circuit to prevent damages When this happens the yellow LED indicates it 6 1 17 Disabled indication LED When any functionality of the FIREWALL is deactivated a zone for e...

Страница 6: ...a successful operation and a single beep otherwise 7 1 General These general configurations allow to change the access code and to reset all parameters to the default ones Note Resetting the parameters to the default values will also set the access code to the default one Buzzer Sounder Sounder Buzzer 7 1 1 Change access code 1 Press Z1 key 2 A double beep is emitted 3 Enter new code using any com...

Страница 7: ...f an alarm To enter the test mode follow the next procedure 1 Press the Buzzer and Siren keys to increase or decrease the alarm time before perform the automatic reset It can be configured with the values of 1s 5s 10s 15s 30s and 1min 2 The selected delay is represented by the LEDs Main power 24VDC Fuse Earth Battery and Battery state A delay of 1s is represented by all LEDs off and the maximum de...

Страница 8: ...elay is associated to LEDs Earth Battery and Battery state All LEDs OFF corresponds to maintenance disabled and the maximum maintenance period corresponds to all LEDs ON 3 Press Delay Mode key to accept and Reset key to cancel 4 A double beep will be emitted in case of a successful operation and a single beep otherwise backing to the previous state When the period is reached the FIREWALL will enab...