User Manual

Version 5.3

6.2.2  Activating/deactivating zones:

1.

Enter the access code.

2.

Press the zone key to activate/deactivate it.

3.

Fail indication LED of each zone will be ON when the zone is not active and OFF when the zone is active or in steady-state.

6.2.3  

Sounder silencing:

1.

Enter the access code.

2.

Press the 

Sounder

 key to silence the sounder and press it again to reactivate it.

3.

Sounder

 key has a LED that blinks fast when the sounder is muted and remains ON when the sounder is active.

6.2.4  

Reset:

1.

Enter the access code.

2.

Press 

Reset 

key to reset the fire alarm panel.

        

Note

: Zone circuits are supplied and monitored only 30 seconds after fire alarm panel reset.

6.2.5  

Activating/deactivating 'Delay Mode':

1.

Enter the access code.

2.

Press Delay Mode key to activate/deactivate 'Delay Mode'.

7 - Configuration:

To enter configuration mode it is necessary to remove the frontal and switch the position of the jumper 

JP1

 to ON position.

Note

: This actions should only be performed by specialized technicians.

The control unit will reset and enter configuration mode. Main alarm LED and main fail LED will blink slowly.
The available configurations are grouped and the selected group in each moment is indicated through LEDs associated to keys 

Buzzer,

 

Sounder

,

Reset

 and 

Delay Mode

.

It is possible change the selected group using 

Buzzer 

(forward) and 

Sounder 

(backward) keys.

To select a group press 

Delay Mode

 key (enter) and to leave a group press 

Reset

 key (cancel).

Whenever a group is selected, LEDs of keys 

Buzzer

Sounder

Reset

 and 

Delay Mode 

blink fast, and stay ON when the group is not selected.

A double beep is emitted to signal a successful operation, and a single beep otherwise

7.1  General:

These general configurations allow to change the access code and to reset all parameters to the default ones.

Note

: Resetting the parameters to the default values will also set the access code to the default one (

Buzzer

,

Sounder

Sounder

Buzzer

).

7.1.1  Change access code:

1.

Press 

Z1 

key.

2.

A double beep is emitted.

3.

Enter new code using any combination of keys 

Buzzer

Sounder

Reset

 

and

 Delay Mode

. Code maximum length: 9

keys; if exceeded the extra keys will be rejected and an error beep will be emitted.

4.

Press 

Z1

 key to confirm and 

Z2

 key to cancel.

5.

A double beep will be emitted in case of a successful operation and a single beep otherwise, backing to the previous
state.

7.1.2  Replace original parameters:

1.

Press 

Z2

 

key.

2.

The parameters will be replaced to the default ones (Table 2) and a double beep will be emitted, backing to the previous state.

Relay 1

Signals general alarm.

Relay 2

Signals all faults.

Delay Mode

Active, 30 seconds

Intelligent zones

All

Automatic zones

None

Auxiliary outputs

All signal fire alarm at corresponding zone

Access code

Buzzer, Sounder, Sounder, Buzzer

Maintenance

Disabled

Table 2: Original parameters

7.2  Delay mode:

The delay of a fire alarm, used in Delay Mode, is configurable and can be set to: 0s, 15s, 30s, 1min, 2min, 3min.

1.

Press 

Buzzer 

and 

Sounder 

keys to increase and decrease the delay time.

2.

The   delay   is   associated   to   LEDs:  

Main   power

,  

24VDC   Fuse

,  

Earth

,  

Battery

  and  

Battery   state

.   A   delay   of   0s

corresponds to all LEDs OFF and the maximum delay time corresponds to all LEDs ON.

3.

Press 

Delay Mode

 

key to accept and 

Reset

 key to cancel.

4.

A double beep  will be emitted   in case  of a successful  operation,  and  a single  beep  otherwise,  backing  to  the
previous state.

6 / 8

Figure 12: Delay

mode group

selected.

Figure 11:

General group

selected.

Содержание EN 54-2

Страница 1: ...o 16 ZONES EC Certificate of Conformity ref NGQ05020008 NIBBLE Engenharia Lda Rua Júlio Dinis 265 1D 4785 330 Trofa Portugal EN 54 2 EN 54 4 FIRE DETECTION AND FIRE ALARM SYSTEMS CONTROL AND INDICATING EQUIPMENT POWER SUPPLY EQUIPMENT FIRE ALARM CONTROL PANEL 1 8 ...

Страница 2: ... is available an auxiliary output that can be configured to signal a failure or an alarm detection in the corresponding zone Each of these open collector outputs can sink up to 500mA 2 4 Automatic test The FIREWALL has a test mode which resets the system automatically after an alarm see 7 6 allowing the system to be tested by a single person 2 5 Smart setup The FIREWALL can be configured to adapt ...

Страница 3: ...ion of fails due to short circuit or open circuit It should be used a termination resistor of 3300Ω 1 4W at the end of line and in parallel with the sounder s 4 5 Auxiliary power It is available an auxiliary output to power external equipments up to 500mA 24VDC 4 6 Battery It is mandatory to use a battery lead acid not included with the equipment of 12VDC 7Ah or two batteries of 6VDC 12Ah connecte...

Страница 4: ...le to detect short circuits or open circuits If a short circuit is detected this LED blinks fast in case of open circuit it will blink slowly This LED also indicates if a zone is active or not When permanently ON it indicates inactive zone 6 1 3 Zone alarm indication LED This LED indicates an alarm in the corresponding zone If it blinks fast it means that the alarm was signaled at a callpoint If i...

Страница 5: ...t circuit occurs the LED blinks fast and when an open circuit is detected the LED blinks slowly 6 1 16 Sounder fuse fail indication LED When the maximum specifications for sounders output is not respected 500mA the fuse opens the circuit to prevent damages When this happens the yellow LED indicates it 6 1 17 Disabled indication LED When any functionality of the FIREWALL is deactivated a zone for e...

Страница 6: ...a successful operation and a single beep otherwise 7 1 General These general configurations allow to change the access code and to reset all parameters to the default ones Note Resetting the parameters to the default values will also set the access code to the default one Buzzer Sounder Sounder Buzzer 7 1 1 Change access code 1 Press Z1 key 2 A double beep is emitted 3 Enter new code using any com...

Страница 7: ...f an alarm To enter the test mode follow the next procedure 1 Press the Buzzer and Siren keys to increase or decrease the alarm time before perform the automatic reset It can be configured with the values of 1s 5s 10s 15s 30s and 1min 2 The selected delay is represented by the LEDs Main power 24VDC Fuse Earth Battery and Battery state A delay of 1s is represented by all LEDs off and the maximum de...

Страница 8: ...elay is associated to LEDs Earth Battery and Battery state All LEDs OFF corresponds to maintenance disabled and the maximum maintenance period corresponds to all LEDs ON 3 Press Delay Mode key to accept and Reset key to cancel 4 A double beep will be emitted in case of a successful operation and a single beep otherwise backing to the previous state When the period is reached the FIREWALL will enab...

Отзывы: