background image

prevent unacceptable performance degradation, install and use this product in strict

accordance with the instructions in the product documentation.
Furthermore, any changes or modifications to the product not expressly approved

by National Instruments could void your authority to operate it under your local

regulatory rules.

Notice

 To ensure the specified EMC performance, operate this product

only with shielded cables and accessories. Do not use unshielded cables or

accessories unless they are installed in a shielded enclosure with properly

designed and shielded input/output ports and connected to the product

using a shielded cable. If unshielded cables or accessories are not properly

installed and shielded, the EMC specifications for the product are no

longer guaranteed.

Mounting the TRC-8546

Caution

 The TRC-8546 is a thermally active device that dissipates heat.

Refer to the user manual of the host this device directly connects to for

specific information regarding thermal management. Not following

mounting requirements may affect the system ambient temperature

and/or the measurement accuracy of modules in the system.

Caution

 To meet thermal management requirements, do not zip tie more

than six cables in a bundle, and allow for air flow around the bundle. If

used with a cRIO or cDAQ chassis, mount all cables at least 152 mm

(6.0 in.) from the chassis and do not mount more than six cables directly

beneath the chassis.

You can route and strain relieve the TRC-8546 similarly to ordinary cables. You also

can panel mount it using its removable jackscrews, zip tie, or screw mount it. The

screw mounting holes support #6 and M3 screws spaced 35.56 mm (1.400 in.)

center-to-center, with minimum length of 23 mm (7/8 in.). The TRC-8546 supports

zip ties up to 5.33 mm (0.210 in.) wide.

ni.com

6

TRC-8546 Getting Started

Содержание TRC-8546

Страница 1: ...TRC 8546 Getting Started 2022 06 30...

Страница 2: ...elines 5 Mounting the TRC 8546 6 Panel Mounting the TRC 8546 7 Wiring to the TRC 8546 7 Cable Specifications 8 Cable Lengths 9 Number of LIN Nodes 9 Termination Resistors 9 TRC 8546 Hardware Overview...

Страница 3: ...fer to the documentation for each component in the system to determine the safety and EMC ratings for the entire system Safety Guidelines Caution Observe all instructions and cautions in the user docu...

Страница 4: ...side connector unless power has been switched off or the area is known to be nonhazardous Caution Do not unplug the TRC 8546 unless power has been switched off or the area is known to be nonhazardous...

Страница 5: ...mum ingress protection rating of at least IP54 as defined in IEC EN 60079 15 Caution The enclosure must have a door or cover accessible only by the use of a tool Electromagnetic Compatibility Guidelin...

Страница 6: ...on The TRC 8546 is a thermally active device that dissipates heat Refer to the user manual of the host this device directly connects to for specific information regarding thermal management Not follow...

Страница 7: ...ed with the TRC 8546 work with panel thicknesses up to 2 21 mm 0 087 in Caution Tighten the jackscrews to a maximum torque of 0 56 N m 5 0 lb in If your panel is thicker than 2 21 mm 0 087 in you can...

Страница 8: ...to the connector on the host port end The shielding does not electrically connect to the COM signals Caution When connecting the D Sub connector shell do not exceed the maximum jackscrew torque of 0...

Страница 9: ...odes are terminated at the transceiver Slave nodes typically are pulled up from the LIN bus to VSUP with a 30 k resistance and a serial diode This termination usually is integrated into the transceive...

Страница 10: ...d bus status LED 1 primarily indicates whether the hardware is currently in use LED 2 primarily indicates the activity information of the connected bus Each LED can display two colors red or green whi...

Страница 11: ...voltage 40 VDC to 40 VDC Supply voltage range VSUP 8 VDC to 18 VDC normal operating 0 3 VDC to 40 VDC absolute limits MTBF Contact NI for Bellcore MTBF specifications at other temperatures or MIL HDB...

Страница 12: ...ectrical supply system that powers equipment This category is for measurements of voltages from specially protected secondary circuits Such voltage measurements include signal levels special equipment...

Страница 13: ...9 15 2012 Note For safety certifications refer to the product label or the Product Certifications and Declarations section Hazardous Locations U S UL Class I Division 2 Groups A B C D T4 Class I Zone...

Страница 14: ...6 5 g 10 Hz to 500 Hz Operating shock IEC 60068 2 27 30 g 11 ms half sine 50 g 3 ms half sine 18 shocks at 6 orientations Electromagnetic Compatibility This product meets the requirements of the follo...

Страница 15: ...follows 2014 35 EU Low Voltage Directive safety 2014 30 EU Electromagnetic Compatibility Directive EMC 2014 34 EU Potentially Explosive Atmospheres ATEX Product Certifications and Declarations Refer t...

Страница 16: ...lations For more information about how to recycle NI products in your region visit ni com environment weee RoHS 5 40 e RoHS NI RoHS NI RoHS ni com environment rohs_china For information about China Ro...

Отзывы: