NI-9853 in a potentially explosive environment. Not following these guidelines may
result in serious injury or death.
Caution
Do not disconnect I/O-side wires or connectors unless power has
been switched off or the area is known to be nonhazardous.
Caution
Do not remove modules unless power has been switched off or
the area is known to be nonhazardous.
Caution
Substitution of components may impair suitability for Class I,
Division 2.
Caution
For Division 2 and Zone 2 applications, install the system in an
enclosure rated to at least IP54 as defined by IEC/EN 60079-15.
Caution
For Zone 2 applications, install a protection device between the
CAN signals and the NI-9853 CAN pins. The device must prevent the CAN
Port-to-COM voltage from exceeding 55 V if there is a transient overvoltage
condition.
Special Conditions for Hazardous Locations Use in Europe and
Internationally
The NI-9853 has been evaluated as Ex nA IIC T4 Gc equipment under DEMKO
Certificate No. 03 ATEX 0324020X and is IECEx 14.0089X certified. Each NI-9853 is
marked II 3G and is suitable for use in Zone 2 hazardous locations, in ambient
temperatures of -40 °C ≤ Ta ≤ -70 °C . If you are using the NI-9853 in Gas Group IIC
hazardous locations, you must use the device in an NI chassis that has been
evaluated as Ex nC IIC T4, Ex IIC T4, Ex nA IIC T4, or Ex nL IIC T4 equipment.
Caution
You must make sure that transient disturbances do not exceed
140% of the rated voltage.
ni.com
4
NI-9853