NI FieldPoint cFP-RLY-423 Скачать руководство пользователя страница 9

© 

National Instruments Corp.

9

cFP-RLY-423

250 V

rms

1

. Safety standards (such as those published by UL 

and IEC) require the use of double insulation between hazardous 
voltages and any human-accessible parts or circuits.

Never

 try to use any isolation product between human-accessible 

parts (such as DIN rails or monitoring stations) and circuits that 
can be at hazardous potentials under normal conditions, unless the 
product is specifically designed for such an application, as is the 
cFP-RLY-423. 

Even though the cFP-RLY-423 is designed to handle applications 
with hazardous potentials, follow these guidelines to ensure a safe 
total system:

The cFP-RLY-423 has a safety isolation barrier between the 
I/O channels and the inter-module communication bus. There 
is no isolation between channels unless otherwise noted. If any 
of the channels on a module are wired at a hazardous potential, 
make sure that all other devices or circuits connected to that 
module are properly insulated from human contact.

Do 

not

 share the external supply voltages (the V and C 

terminals) with other devices (including other FieldPoint 
devices), unless those devices are isolated from human contact.

You 

must

 connect the protective earth (PE) ground terminal 

on the cFP-BP-

x

 backplane to the system safety ground. The 

backplane PE ground terminal has the following symbol 
stamped beside it: 

. Connect the backplane PE ground 

terminal to the system safety ground using 14 AWG (1.6 mm) 
wire with a ring lug. Use the 5/16 in. panhead screw shipped 
with the backplane to secure the ring lug to the backplane 
PE ground terminal.

As with any hazardous voltage wiring, make sure that all 
wiring and connections meet applicable electrical codes 
and commonsense practices. Mount backplanes in an area, 
position, or cabinet that prevents accidental or unauthorized 
access to wiring that carries hazardous voltages.

The isolation of the cFP-RLY-423 is certified as 
double-insulated for working voltages of 250 V

rms

. Do 

not

 use 

the cFP-RLY-423 as the only isolating barrier between human 
contact and working voltages of more than 250 V

rms

.

1  

Working voltage

 is defined as the signal voltage plus the common-mode voltage. 

Common-mode voltage

 is the voltage of the module with respect to ground.

Содержание FieldPoint cFP-RLY-423

Страница 1: ...RLY 423 is a Compact FieldPoint relay output module with the following features Four single pole double throw SPDT relay channels Switches up to 1 5 A at 35 VDC or 250 VAC LED relay status indicators...

Страница 2: ...ent backward insertion 2 Press firmly to seat the cFP RLY 423 on the backplane 3 Using a number 2 Phillips screwdriver with a shank of at least 64 mm 2 5 in length tighten the captive screws to 1 1 N...

Страница 3: ...peak or 60 VDC Caution Ensure that hazardous voltage wiring is performed only by qualified personnel adhering to local electrical standards Each relay channel of the cFP RLY 423 has four terminals one...

Страница 4: ...loads and an external power supply to one channel of the cFP RLY 423 as shown in Figure 2 Install a 1 5 A 250 V maximum fast acting fuse suitable for the load at the connected IC terminal to protect...

Страница 5: ...are connected to the relays a large counter electromotive force can occur at relay switching time because of the energy stored in the inductive load These flyback voltages can severely damage the rel...

Страница 6: ...e the circuit you are planning to use Diode and Zener Diode Circuit Diode Circuit 1 This section has been reprinted with permission from American Zettler Inc Diagram Notes Use in DC applications only...

Страница 7: ...hould be smaller than that of the CR circuit Do not utilize for timer loads as leakage current can cause faulty operations Circuit B is suitable for AC or DC If the load is a relay or solenoid release...

Страница 8: ...Isolation and Safety Guidelines Caution Read the following information before attempting to connect the cFP RLY 423 to any circuits that may contain hazardous voltages This section describes the isola...

Страница 9: ...al supply voltages the V and C terminals with other devices including other FieldPoint devices unless those devices are isolated from human contact You must connect the protective earth PE ground term...

Страница 10: ...llation Category II is for measurements performed on circuits directly connected to the electrical distribution system This category refers to local level distribution such as that provided by a stand...

Страница 11: ...operations min Electrical 1 105 operations at rated resistive load Maximum switching frequency Mechanical 20 operations per second Electrical 1 operation per second at maximum load Relay operate time...

Страница 12: ...r altitudes the isolation voltage ratings must be lowered Pollution Degree 2 Safety This product is designed to meet the requirements of the following standards of safety for electrical equipment for...

Страница 13: ...for the most current manuals examples and troubleshooting information For telephone support in the United States create your service request at ni com support and follow the calling instructions or d...

Страница 14: ...0 311 210 Russia 7 095 783 68 51 Singapore 65 6226 5886 Slovenia 386 3 425 4200 South Africa 27 0 11 805 8197 Spain 34 91 640 0085 Sweden 46 0 8 587 895 00 Switzerland 41 56 200 51 51 Taiwan 886 2 252...

Страница 15: ...com are trademarks of National Instruments Corporation Product and company names mentioned herein are trademarks or trade names of their respective companies For patents covering National Instruments...

Отзывы: