Figure 3.

 cRIO-9066 Power Connections

Power Connector

C

V

Power Supply

+

Note

 

The C terminals are internally connected to each other.

4.

Tighten the terminal screws on the power connector to 0.20 N · m to 0.25 N · m
(1.8 lb · in. to 2.2 lb · in.) of torque.

5.

Install the power connector on the front panel of the cRIO-9066.

6.

Tighten the power connector screw flanges to 0.20 N · m to 0.25 N · m (1.8 lb · in. to
2.2 lb · in.) of torque.

7.

Power on the power supply.

Powering On the cRIO-9066

When you power on the cRIO-9066 for the first time, the device boots into safe mode. The
POWER LED illuminates, the STATUS LED illuminates briefly, and then the STATUS LED
blinks twice every few seconds.

Connecting the cRIO-9066 to the Host Computer

Complete the following steps to connect the cRIO-9066 to the host computer using the USB
device port.
1.

Power on the host computer.

2.

Connect the cRIO-9066 to the host computer using the USB A-to-B cable.

Caution

 

NI requires the use of a locking USB cable (157788-01) to meet the 

shock and vibration specifications. Refer to the specifications on 

ni.com/

manuals

 for shock and vibration specifications.

The device driver software automatically detects the cRIO-9066. If the device driver
software does not detect the cRIO-9066, verify that you installed the appropriate NI
software in the correct order on the host computer.

Tip

 

You can also use the Ethernet port to connect directly to the host computer or

network. Refer to the user manual on 

ni.com/manuals

 for more information about

Ethernet connections.

Configuring the System in Measurement &
Automation Explorer (MAX)

Complete the following steps to find the system in MAX.

8

  | 

ni.com

  | 

NI cRIO-9066 Getting Started Guide

Содержание cRIO-9066

Страница 1: ...safety protection built into the product if the product is damaged in any way If the product is damaged return it to NI for repair Safety Guidelines for Hazardous Locations The cRIO 9066 is suitable for use in Class I Division 2 Groups A B C D T4 hazardous locations Class I Zone 2 AEx nA IIC T4 and Ex nA IIC T4 hazardous locations and nonhazardous locations only Follow these guidelines if you are ...

Страница 2: ...nown to be nonhazardous Table 1 Hazardous Location Retention Accessories Port Required Accessory Part Number USB Device Port NI Locking USB Cable 157788 01 USB Host Port NI Industrial USB Extender Cable 152166 xx Special Conditions for Hazardous Locations Use in Europe and Internationally The cRIO 9066 has been evaluated as Ex nA IIC T4 Gc equipment under DEMKO Certificate No 12 ATEX 1202658X and ...

Страница 3: ... authority to operate it under your local regulatory rules Caution To ensure the specified EMC performance operate this product only with shielded cables and accessories Special Conditions for Marine Applications Some products are Lloyd s Register LR Type Approved for marine shipboard applications To verify Lloyd s Register certification for a product visit ni com certification and search for the ...

Страница 4: ...f connectors Note Do not install a device if it appears damaged in any way 3 Unpack any other items and documentation from the kit Store the device in the antistatic package when the device is not in use Verifying the Kit Contents Verify that the following items are included in the cRIO 9066 kit Figure 1 cRIO 9066 Kit Contents 2 4 3 1 1 cRIO Device 2 USB A to B Cable 3 NI CompactRIO Device Drivers...

Страница 5: ...on the C Series module 3 Align the C Series module with a slot and seat it in the slot until the latches lock in place Removing C Series Modules Verify that power is not connected to the I O connector s on the C Series module before you remove a module from the cRIO 9066 If the system is in a nonhazardous location the cRIO 9066 can be powered on when you remove modules Connecting the cRIO 9066 The...

Страница 6: ...e ring lug to the grounding terminal 4 Tighten the grounding screw to 0 5 N m 4 4 lb in of torque 5 Attach the other end of the wire to the grounding electrode system of your facility using a method that is appropriate for your application Caution If you use shielded cabling to connect to a C Series module with a plastic connector you must attach the cable shield to the chassis grounding terminal ...

Страница 7: ... 0 10 in flathead Power supply 9 V to 30 V 25 W maximum NI recommends the power supply listed in the following table for the cRIO 9066 Table 3 NI Power Supplies Power Supply Part Number NI PS 15 Industrial Power Supply 24 VDC 5 A 100 VAC to 120 VAC 200 VAC to 240 VAC input 781093 01 What to Do Complete the following steps to connect a power supply to the cRIO 9066 1 Ensure that your power supply i...

Страница 8: ...teps to connect the cRIO 9066 to the host computer using the USB device port 1 Power on the host computer 2 Connect the cRIO 9066 to the host computer using the USB A to B cable Caution NI requires the use of a locking USB cable 157788 01 to meet the shock and vibration specifications Refer to the specifications on ni com manuals for shock and vibration specifications The device driver software au...

Страница 9: ...oring prompts you to do so 2 Enter a unique name for your system in the Hostname field 3 Click the Security Configuration icon 4 Click Login 5 In the Login dialog box enter the username admin and leave the password field blank 6 Click OK 7 Click Change Password 8 Enter and re enter a new password 9 Click OK 10 Click Save 11 Click OK to confirm you are changing the password Caution NI cannot recove...

Страница 10: ...ormat of 172 22 11 x 2 In MAX expand your system under Remote Systems 3 Select the Network Settings tab to configure the IP and other network settings 4 Optional Use the RJ 45 Ethernet port 1 to reconnect the cRIO 9066 to the host computer The cRIO 9066 attempts to initiate a DHCP network connection at powerup Note If the cRIO 9066 cannot obtain an IP address it connects to the network with a link...

Страница 11: ...ful and appropriate for your application skip to Step 6 4 In MAX expand your system under Remote Systems 5 Select the Network Settings tab to configure the IP and other network settings 6 Reboot the cRIO 9066 by pressing the RESET button Configure the Windows Firewall Add an exception for MAX to your network firewall or other security software by completing the following steps 1 On Windows 7 selec...

Страница 12: ...ware has been improperly installed on the cRIO 9066 An error can occur when an attempt to upgrade the software is interrupted Reinstall software on the cRIO 9066 Refer to the Measurement Automation Explorer MAX Help for information about installing software on the cRIO 9066 Blinks three times and pauses The cRIO 9066 is in user directed safe mode or the cRIO 9066 is in install mode to indicate tha...

Страница 13: ...pactriodevguide Software Support ni com info swsupport Support ni com support SOFTWARE CompactRIO Sample Projects LabVIEW Create Project HARDWARE NI cRIO 9066 Specifications ni com manuals NI cRIO 9066 User Manual ni com manuals C Series Getting Started Guides ni com manuals Configuring a Project NI RIO Help Learn LabVIEW Basics ni com gettingstarted CompactRIO Examples NI Example Finder Services ...

Страница 14: ...anch office websites which provide up to date contact information support phone numbers email addresses and current events Refer to the NI Trademarks and Logo Guidelines at ni com trademarks for information on NI trademarks Other product and company names mentioned herein are trademarks or trade names of their respective companies For patents covering NI products technology refer to the appropriat...

Отзывы: