Protection Settings
Long Time Delay (LTD) protection
27
TemBreak
PRO
P_BE-UM-001-EN V1.3.0
Adjusting t
r
(Time Delay)
The t
r
time delay defines the trip time of the long-time delay protection for a current of 6 x I
r
. and adjustable via the t
r
dial.
t
r
Adjustment Range (seconds)
0.5
1.5
2.5
5
7.5
9
10
12
14
16
Notice
: For the following MCCBs the setting of I
r
and t
r
can limit the setting of I
sd
for STD protection.
P160_BE I
n
= 160A, P250_BE I
n
= 250A
If: I
r
> 0.9 x I
n
and t
r
= 16s
I
sd
is limited to 9 x I
r
. even if the dial is set to 10x
Notice
: The trip time tolerance for LTD protection is -20% + 20ms to 0% + 30ms.
Example:
For t
r
= 5 s and I = 6 x I
r
, the trip time for long time delay protection will be between 4.02 s and 5.03 s.
Содержание TemBreak PRO P
Страница 50: ...50 TemBreak PRO P_BE UM 001 EN V1 3 0 Annex A Dimensions P160 Dimensions...
Страница 51: ...Annex A Dimensions 51 TemBreak PRO P_BE UM 001 EN V1 3 0 P250 Dimensions...
Страница 52: ...Annex A Dimensions 52 TemBreak PRO P_BE UM 001 EN V1 3 0 P400 Dimensions...
Страница 53: ...Annex A Dimensions 53 TemBreak PRO P_BE UM 001 EN V1 3 0 P630 Dimensions...
Страница 55: ...55 TemBreak PRO P_BE UM 001 EN V1 3 0 Annex C I2t Let Through Curves P160_BE...
Страница 56: ...Annex C I2t Let Through Curves 56 TemBreak PRO P_BE UM 001 EN V1 3 0 P250_BE...
Страница 57: ...Annex C I2t Let Through Curves 57 TemBreak PRO P_BE UM 001 EN V1 3 0 P400_BE...
Страница 58: ...Annex C I2t Let Through Curves 58 TemBreak PRO P_BE UM 001 EN V1 3 0 P630_BE...
Страница 59: ...59 TemBreak PRO P_BE UM 001 EN V1 3 0 Annex D Peak Let Through Curves P160_BE...
Страница 60: ...Annex D Peak Let Through Curves 60 TemBreak PRO P_BE UM 001 EN V1 3 0 P250_BE...
Страница 61: ...Annex D Peak Let Through Curves 61 TemBreak PRO P_BE UM 001 EN V1 3 0 P400_BE...
Страница 62: ...Annex D Peak Let Through Curves 62 TemBreak PRO P_BE UM 001 EN V1 3 0 P630_BE...
Страница 65: ...65 TemBreak PRO P_BE UM 001 EN V1 3 0 This page is intentionally left blank...