Commissioning
47
TemBreak
PRO
P_BE-UM-001-EN V1.3.0
LSIG 4P
–
NP and GF Protection Adjustments (I
N,
I
g
)
On the LSIG 4P variant P_BE MCCB, both NP and GF protection modes are configured by the N (%) adjustment rotary dials, which is performed as follows.
Refer to
Ground/Earth Fault Protection (GF)
sections for further detail on NP and GF protection.
Action
Note / Illustration
1
Turn the MCCB to the OFF Position
Open the transparent flap to access N(%) adjustment dial
2
Using a PH1, PH2 or PZ2 size screwdriver, rotate the N(%)
adjustment dial to the desired N Coefficient value.
NOTE: There are two sides to the N(%) dial to enable or
disable GF protection: Right side to enable, and left side to
disable.
Содержание TemBreak PRO P
Страница 50: ...50 TemBreak PRO P_BE UM 001 EN V1 3 0 Annex A Dimensions P160 Dimensions...
Страница 51: ...Annex A Dimensions 51 TemBreak PRO P_BE UM 001 EN V1 3 0 P250 Dimensions...
Страница 52: ...Annex A Dimensions 52 TemBreak PRO P_BE UM 001 EN V1 3 0 P400 Dimensions...
Страница 53: ...Annex A Dimensions 53 TemBreak PRO P_BE UM 001 EN V1 3 0 P630 Dimensions...
Страница 55: ...55 TemBreak PRO P_BE UM 001 EN V1 3 0 Annex C I2t Let Through Curves P160_BE...
Страница 56: ...Annex C I2t Let Through Curves 56 TemBreak PRO P_BE UM 001 EN V1 3 0 P250_BE...
Страница 57: ...Annex C I2t Let Through Curves 57 TemBreak PRO P_BE UM 001 EN V1 3 0 P400_BE...
Страница 58: ...Annex C I2t Let Through Curves 58 TemBreak PRO P_BE UM 001 EN V1 3 0 P630_BE...
Страница 59: ...59 TemBreak PRO P_BE UM 001 EN V1 3 0 Annex D Peak Let Through Curves P160_BE...
Страница 60: ...Annex D Peak Let Through Curves 60 TemBreak PRO P_BE UM 001 EN V1 3 0 P250_BE...
Страница 61: ...Annex D Peak Let Through Curves 61 TemBreak PRO P_BE UM 001 EN V1 3 0 P400_BE...
Страница 62: ...Annex D Peak Let Through Curves 62 TemBreak PRO P_BE UM 001 EN V1 3 0 P630_BE...
Страница 65: ...65 TemBreak PRO P_BE UM 001 EN V1 3 0 This page is intentionally left blank...