e
Electro Industries/Gauge Tech
Doc # E134-7-15 V1.01
A-1
Appendix A
Appendix A
Glossary
Glossary
Address:
The Device Address used for Modbus Communication. Valid values are
between 1 and 247, inclusive.
Average (Current):
When applied to current values (amps) the average is a calculated value that
corresponds to the thermal average over a specified time interval. The interval
is specified by the user in the meter profile. The interval is typically 15 minutes.
So, Average Amps is the thermal average of amps over the previous 15-minute
interval. The thermal average rises to 90% of the actual value in each time
interval. For example, if a constant 100 amp load is applied, the thermal
average will indicate 90 amps after one time interval, 99 amps after two time
intervals and 99.9 amps after three time intervals.
Average (Input Pulse
When applied to Input Pulse Accumulations, the “Average” refers to the block
Accumulations):
(fixed) window average value of the input pulses.
Average (Power):
When applied to power values (watts, VARs, VA), the average is a calculated
value that corresponds to the thermal average over a specified time interval. The
interval is specified by the user in the meter profile. The interval is typically 15
minutes. So, the Average Watts is the thermal average of watts over the
previous 15-minute interval. The thermal average rises to 90% of the actual
value in each time interval. For example, if a constant 100kW load is applied,
the thermal average will indicate 90kW after one time interval, 99kW after two
time intervals and 99.9kW after three time intervals.
Bit:
A unit of computer information equivalent to the result of a choice between two
alternatives (Yes/No, On/Off, for example).
Or, the physical representation of a bit by an electrical pulse whose presence or
absence indicates data.
Binary:
Relating to a system of numbers having 2 as its base (digits 0 and 1).
Block Window Avg:
The Block (Fixed) Window Average is the average power calculated over a
(Power)
user-set time interval, typically 15 minutes. This calculated average corresponds
to the demand calculations performed by most electric utilities in monitoring
user power demand. (See Rolling Window Average.)
Build Number:
Incremented at least for every internal release and used for internal testing.
Byte:
A group of 8 binary digits processed as a unit by a computer (or device) and
used especially to represent an alphanumeric character.
Содержание I/O Module
Страница 2: ......
Страница 6: ...e Electro Industries Gauge Tech Doc E134 7 15 V1 01 iv ...
Страница 10: ...e Electro Industries Gauge Tech Doc E134 7 15 V1 01 viii ...
Страница 30: ...e Electro Industries GaugeTech Doc E134 7 15 V1 01 2 16 ...
Страница 44: ...e Electro Industries GaugeTech Doc E134 7 15 V1 01 4 8 ...
Страница 50: ...e Electro Industries GaugeTech Doc E134 7 15 V1 01 6 4 ...
Страница 52: ...e Electro Industries Gauge Tech Doc E 134 7 15 V1 01 7 2 ...
Страница 63: ...e Electro Industries GaugeTech Doc E134 7 15 V1 01 8 4 ...
Страница 65: ...e Electro Industries Gauge Tech Doc E 134 7 15 V1 01 9 2 ...
Страница 72: ...e Electro Industries GaugeTech Doc E134 7 15 V1 01 10 4 ...
Страница 74: ...e Electro Industries Gauge Tech Doc E 134 7 15 V1 01 11 2 ...
Страница 81: ...e Electro Industries Gauge Tech Doc E 134 7 15 V1 01 13 2 ...
Страница 87: ...e Electro Industries GaugeTech Doc E134 7 15 V1 01 14 4 ...
Страница 89: ...e Electro Industries Gauge Tech Doc E 134 7 15 V1 01 15 2 ...