NextE CCE07 Скачать руководство пользователя страница 51

51

T H E   S M A R T   S O L U T I O N   F O R   E N E R G Y   E F F I C I E N C Y

C o n s o l e s

R e v. :   3 0   J u n e ,   2 0 0 8 B

w w w. c l i m a t e m a s t e r. c o m

Functional Troubleshooting

Only Compressor Runs

X

X Thermostat wiring

Check G wiring at heat pump.  Jumper G and R for fan

operation.

X

X Fan motor relay

Jumper G and R for fan operation.  Check for Line voltage

across BR contacts.
Check fan power enable relay operation (if present)

X

X Fan motor

Check for line voltage at motor.  Check capacitor

X

X Thermostat wiring

Check thermostat wiring at heat pump.  Jumper Y and R for

compressor operation in test mode.

Unit Doesn't Operate in

Cooling

X Reversing Valve

Set for cooling demand and check 24VAC on RV coil and at

CXM/DXM board.

If RV is stuck, run high pressure up by reducing water flow

and while operating engage and disengage RV coil voltage

to push valve.

X Thermostat setup

Check for 'O' RV setup not 'B'

X Thermostat wiring

Check O wiring at heat pump.  Jumper O and R for RV coil

'Click'.

Performance

Troubleshooting

Htg Clg Possible Cause

Solution

Insufficient capacity/

X

X Dirty Filter

Replace or clean

Not cooling or heating

X

Reduced or no Air flow

Check for dirty air filter and clean or replace

properly

in heating

Check fan motor operation and airflow restrictions

Too high of external static.  Check static vs blower table

X Reduced or no Air flow

Check for dirty air filter and clean or replace

in cooling

Check fan motor operation and airflow restrictions

Too high of external static.  Check static vs blower table

X

X Leaky duct work

Check supply and return air temperatures at the unit and at

distant duct registers if significantly different, duct leaks

are present

X

X Low refrigerant charge

Check superheat and subcooling per chart

X

X Restricted metering device

Check superheat and subcooling per chart.  Replace.

X Defective Reversing Valve

Perform RV touch test

X

X Thermostat improperly located

Check location and for air drafts behind stat

X

X Unit undersized

Recheck loads & sizing check sensible clg load and heat

pump capacity

X

X Scaling in water heat exchanger Perform Scaling check and clean if necessary

X

X Inlet Water too Hot or Cold

Check load, loop sizing, loop backfill, ground moisture.

High Head Pressure

X

Reduced or no Air flow

Check for dirty air filter and clean or replace

in heating

Check fan motor operation and airflow restrictions
Too high of external static.  Check static vs blower table

X Reduced or no water flow

Check pump operation or valve operation/setting

in cooling

Check water flow adjust to proper flow rate

X Inlet Water too Hot

Check load, loop sizing, loop backfill, ground moisture.

X

Air Temperature out of range in

heating

Bring return air temp within design parameters

X Scaling in water heat exchanger Perform Scaling check and clean if necessary

X

X Unit Overcharged

Check superheat and subcooling.  Reweigh in charge

X

X Non-condensables insystem

Vacuum system and reweigh in charge

X

X Restricted metering device

Check superheat and subcooling per chart.  Replace.

Low Suction Pressure

X

Reduced water flow

Check pump operation or water valve operation/setting

in heating

Plugged strainer or filter.  Clean or replace.

Check water flow adjust to proper flow rate

X

Water Temperature out of range

Bring water temp within design parameters

X Reduced Air flow

Check for dirty air filter and clean or replace

in cooling

Check fan motor operation and airflow restrictions

Too high of external static.  Check static vs blower table

X Air Temperature out of range

Too much cold vent air? Bring entering air temp within

design parameters

X

X Insufficient charge

Check for refrigerant leaks

Low discharge air

temperature in heating

X

Too high of air flow

Check fan motor speed selection and airflow chart

X

Poor Performance

See 'Insufficient Capacity'

High humidity

X Too high of air flow

Check fan motor speed selection and airflow chart

X Unit oversized

Recheck loads & sizing check sensible clg load and heat

pump capacity

X Thermostat wiring

Put thermostat in cooling mode. Check for 24VAC on O

(check between C and O); check for 24VAC on W (check

between W and C). There should be voltage on O, but not

on W. If voltage is present on W, thermostat may be bad

or wired incorrectly.

Performance Troubleshooting

Only Compressor Runs

X

X Thermostat wiring

Check G wiring at heat pump.  Jumper G and R for fan

operation.

X

X Fan motor relay

Jumper G and R for fan operation.  Check for Line voltage

across BR contacts.
Check fan power enable relay operation (if present)

X

X Fan motor

Check for line voltage at motor.  Check capacitor

X

X Thermostat wiring

Check thermostat wiring at heat pump.  Jumper Y and R for

compressor operation in test mode.

Unit Doesn't Operate in

Cooling

X Reversing Valve

Set for cooling demand and check 24VAC on RV coil and at

CXM/DXM board.

If RV is stuck, run high pressure up by reducing water flow

and while operating engage and disengage RV coil voltage

to push valve.

X Thermostat setup

Check for 'O' RV setup not 'B'

X Thermostat wiring

Check O wiring at heat pump.  Jumper O and R for RV coil

'Click'.

Performance

Troubleshooting

Htg Clg Possible Cause

Solution

Insufficient capacity/

X

X Dirty Filter

Replace or clean

Not cooling or heating

X

Reduced or no Air flow

Check for dirty air filter and clean or replace

properly

in heating

Check fan motor operation and airflow restrictions

Too high of external static.  Check static vs blower table

X Reduced or no Air flow

Check for dirty air filter and clean or replace

in cooling

Check fan motor operation and airflow restrictions

Too high of external static.  Check static vs blower table

X

X Leaky duct work

Check supply and return air temperatures at the unit and at

distant duct registers if significantly different, duct leaks

are present

X

X Low refrigerant charge

Check superheat and subcooling per chart

X

X Restricted metering device

Check superheat and subcooling per chart.  Replace.

X Defective Reversing Valve

Perform RV touch test

X

X Thermostat improperly located

Check location and for air drafts behind stat

X

X Unit undersized

Recheck loads & sizing check sensible clg load and heat

pump capacity

X

X Scaling in water heat exchanger Perform Scaling check and clean if necessary

X

X Inlet Water too Hot or Cold

Check load, loop sizing, loop backfill, ground moisture.

High Head Pressure

X

Reduced or no Air flow

Check for dirty air filter and clean or replace

in heating

Check fan motor operation and airflow restrictions
Too high of external static.  Check static vs blower table

X Reduced or no water flow

Check pump operation or valve operation/setting

in cooling

Check water flow adjust to proper flow rate

X Inlet Water too Hot

Check load, loop sizing, loop backfill, ground moisture.

X

Air Temperature out of range in

heating

Bring return air temp within design parameters

X Scaling in water heat exchanger Perform Scaling check and clean if necessary

X

X Unit Overcharged

Check superheat and subcooling.  Reweigh in charge

X

X Non-condensables insystem

Vacuum system and reweigh in charge

X

X Restricted metering device

Check superheat and subcooling per chart.  Replace.

Low Suction Pressure

X

Reduced water flow

Check pump operation or water valve operation/setting

in heating

Plugged strainer or filter.  Clean or replace.

Check water flow adjust to proper flow rate

X

Water Temperature out of range

Bring water temp within design parameters

X Reduced Air flow

Check for dirty air filter and clean or replace

in cooling

Check fan motor operation and airflow restrictions

Too high of external static.  Check static vs blower table

X Air Temperature out of range

Too much cold vent air? Bring entering air temp within

design parameters

X

X Insufficient charge

Check for refrigerant leaks

Low discharge air

temperature in heating

X

Too high of air flow

Check fan motor speed selection and airflow chart

X

Poor Performance

See 'Insufficient Capacity'

High humidity

X Too high of air flow

Check fan motor speed selection and airflow chart

X Unit oversized

Recheck loads & sizing check sensible clg load and heat

pump capacity

X Thermostat wiring

Put thermostat in cooling mode. Check for 24VAC on O

(check between C and O); check for 24VAC on W (check

between W and C). There should be voltage on O, but not

on W. If voltage is present on W, thermostat may be bad

or wired incorrectly.

Содержание CCE07

Страница 1: ...Pump Applications 14 Ground Loop Heat Pump Applications 15 Ground Water Heat Pump Applications 16 Water Quality Standards 18 Electrical Wiring Line Voltage 19 21 Electrical Wiring Low Voltage 22 Therm...

Страница 2: ......

Страница 3: ...ed Water Valve A G N Autoflow 2 25 Gpm Ton B H P Autoflow 3 0 Gpm Ton C J Q Motorized Water Valve Afr 2 25 D K R Motorized Water Valve Afr 3 0 E L T Secondary Circulation Pump U V W Water Circuit Opti...

Страница 4: ...mote Mounted w DXM MPC G 208 230 60 1 B 20Amp Plug Cord D Disconnect Switch 15Amp Fuse F Disconnect Switch Non Fused H 20Amp Plug Cord Receptacle Disconnect Switch 15Amp Fuse K 20Amp Plug Cord Recepta...

Страница 5: ...in the compressor To avoid leakage of compressor oil refrigerant lines of the compressor must be sealed after it is removed CAUTION To avoid equipment damage DO NOT use these units as a source of hea...

Страница 6: ...ed for installation above false ceiling or in a ceiling plenum Other unit configurations are typically installed in a mechanical room The installation site chosen should include adequate service clear...

Страница 7: ...ttings in 1 2 1 2 1 2 1 2 1 2 Optional EPT Fittings in 1 2 1 2 1 2 1 2 1 2 Condensate Connection Size I D Vinyl Hose In mm 5 8 15 9 5 8 15 9 5 8 15 9 5 8 15 9 5 8 15 9 Air Coil Size Dimensions h x w i...

Страница 8: ...imensions h x w in mm 8 x 26 20 3 x 66 0 10 x 26 25 4 x 66 0 10 x 32 25 4 x 81 2 Filter Size Bottom Return in cm 1 10 x 30 x 1 25 4 x 76 2 x 2 5 2 10 x 16 x 1 25 4 x 40 6 x 2 5 Front Return In cm 1 7...

Страница 9: ...D Vinyl Hose In mm 5 8 15 9 Air Coil Size Dimensions h x w in mm 8 x 26 20 3 x 66 0 10 x 26 25 4 x 66 0 10 x 32 25 4 x 81 2 Filter Size Bottom Return in cm 1 10 x 30 x 1 25 4 x 76 2 x 2 5 10 x 36 x 1...

Страница 10: ...rated hose assemblies are available for use with ClimateMaster Console Units Use the following guidelines when installing supply and return hose assemblies 1 Install supply and return hoses fitted wi...

Страница 11: ...tly Horizontal runs of condensate hose should be pitched downward 1 4 inch minimum for every foot 10mm per 46cm of hose Avoid low points because dirt collects in these areas and may cause blockage If...

Страница 12: ...Hose Optional Disconnect Box mounted to cabinet not chassis Optional Motorized Water Valve Optional Autoflow Valve Water Connections 5 8 15 9 mm OD Copper 1 2 IPT or 1 2 EPT 7 5 191 3 42 87 3 56 90 Ri...

Страница 13: ...is not available tighten finger tight plus one quarter turn Tighten steel fittings as necessary Optional pressure rated hose assemblies designed specifically for use with ClimateMaster units are avai...

Страница 14: ...valve for use in variable speed pumping systems may also be included in the hose kit The piping system should be flushed to remove dirt piping chips and other foreign material prior to operation see...

Страница 15: ...water circuit insulation CAUTION CAUTION Ground Loop Heat Pump Applications Test individual horizontal loop circuits before backfilling Test vertical U bends and pond loop assemblies prior to install...

Страница 16: ...rect use A monitoring plan should be implemented in these probable scaling situations Other water quality issues such as iron fouling corrosion prevention and erosion and clogging should be referenced...

Страница 17: ...side of any field provided shut off valves and connected to the heat pump controls in series with the built in refrigerant circuit high pressure switch to disable compressor operation if water pressur...

Страница 18: ...lloy bronze or brass cast components are OK to 0 5 ppm Ammonia ion All 0 5 ppm as hydroxide chloride nitrate and sulfate compounds Maximum Maximum Allowable at maximum water temperature Chloride Level...

Страница 19: ...Code whichever is applicable Power Connection Line voltage connection is made by connecting the incoming line voltage wires to the L side of the contactor Consult Tables 4 through 5 for correct fuse...

Страница 20: ...55 8 1 0 11 6 14 3 25 G 208 230 60 1 197 254 1 5 2 24 0 0 6 5 8 7 1 15 E 265 60 1 239 292 1 4 2 25 0 0 4 4 6 5 7 15 TRC15 G 208 230 60 1 197 254 1 6 1 30 0 0 8 6 9 8 4 15 E 265 60 1 239 292 1 4 7 28...

Страница 21: ...B only required with systems employing remote mounted thermostats Figure 3 Typical Field Installed Wiring WARNING To avoid possible injury or death due to electrical shock open the power supply disco...

Страница 22: ...TRC models include digital display unit mounted controls see picture below Either manual changeover MCO or auto changeover ACO controls are available as indicated by the model number The room temperat...

Страница 23: ...he position of the back plate mounting holes and drill holes with a 3 16 5mm bit Install supplied anchors and secure plate to the wall Thermostat wire must be 18 AWG wire Wire the appropriate thermost...

Страница 24: ...MATEMASTER WATER SOURCE HEAT PUMPS Co n sole s R ev 30 J u n e 2008B 24 ClimateMaster Water Source Heating and Cooling Systems Typical Wiring Diagram Manual Change Over CCE Units Rev A with CXM Contro...

Страница 25: ...25 THE SMAR T SOLUTION FOR ENERGY EFF IC IE NC Y C ons oles Rev 3 0 June 2 0 0 8 B www climatemaster com Typical Wiring Diagram Auto Change Over CCE Units Rev A with CXM Controller...

Страница 26: ...TER WATER SOURCE HEAT PUMPS Co n sole s R ev 30 J u n e 2008B 26 ClimateMaster Water Source Heating and Cooling Systems Typical Wiring Diagram Manual Auto Change Over CCE Units Rev B TRC Units with CX...

Страница 27: ...27 THE SMAR T SOLUTION FOR ENERGY EFF IC IE NC Y C ons oles Rev 3 0 June 2 0 0 8 B www climatemaster com Typical Wiring Diagram Remote Mounted Thermosat CCE TRC Units with CXM Controller...

Страница 28: ...CL I MATEMASTER WATER SOURCE HEAT PUMPS Co n sole s R ev 30 J u n e 2008B 28 ClimateMaster Water Source Heating and Cooling Systems Typical Wiring Diagram CCE TRC Units with CXM MPC Controller...

Страница 29: ...29 THE SMAR T SOLUTION FOR ENERGY EFF IC IE NC Y C ons oles Rev 3 0 June 2 0 0 8 B www climatemaster com Typical Wiring Diagram Manual Change Over CCE Units Rev A with DXM Controller...

Страница 30: ...MATEMASTER WATER SOURCE HEAT PUMPS Co n sole s R ev 30 J u n e 2008B 30 ClimateMaster Water Source Heating and Cooling Systems Typical Wiring Diagram Auto Change Over CCE Units Rev A with DXM Control...

Страница 31: ...31 THE SMAR T SOLUTION FOR ENERGY EFF IC IE NC Y C ons oles Rev 3 0 June 2 0 0 8 B www climatemaster com Typical Wiring Diagram Manual Auto Change Over CCE Units Rev B TRC Units with DXM Controller...

Страница 32: ...TEMASTER WATER SOURCE HEAT PUMPS Co n sole s R ev 30 J u n e 2008B 32 ClimateMaster Water Source Heating and Cooling Systems Typical Wiring Diagram Remote Mounted Thermostat CCE TRC Units with DXM Con...

Страница 33: ...33 THE SMAR T SOLUTION FOR ENERGY EFF IC IE NC Y C ons oles Rev 3 0 June 2 0 0 8 B www climatemaster com Typical Wiring Diagram CCE TRC Units with DXM MPC Controller...

Страница 34: ...TEMASTER WATER SOURCE HEAT PUMPS Co n sole s R ev 30 J u n e 2008B 34 ClimateMaster Water Source Heating and Cooling Systems Typical Wiring Diagram Manual Auto Change Over TRC Units 50Hz with CXM Cont...

Страница 35: ...35 THE SMAR T SOLUTION FOR ENERGY EFF IC IE NC Y C ons oles Rev 3 0 June 2 0 0 8 B www climatemaster com Typical Wiring Diagram Remote Mounted Thermostat TRC Units 50Hz with CXM Controller...

Страница 36: ...CL I MATEMASTER WATER SOURCE HEAT PUMPS Co n sole s R ev 30 J u n e 2008B 36 ClimateMaster Water Source Heating and Cooling Systems Typical Wiring Diagram TRC Units 50Hz with CXM DXM Controller...

Страница 37: ...37 THE SMAR T SOLUTION FOR ENERGY EFF IC IE NC Y C ons oles Rev 3 0 June 2 0 0 8 B www climatemaster com Typical Wiring Diagram Manual Auto Change Over TRC Units 50Hz with DXM Controller...

Страница 38: ...EMASTER WATER SOURCE HEAT PUMPS Co n sole s R ev 30 J u n e 2008B 38 ClimateMaster Water Source Heating and Cooling Systems Typical Wiring Diagram Remote Mounted Thermostat TRC Units 50Hz with DXM Con...

Страница 39: ...39 THE SMAR T SOLUTION FOR ENERGY EFF IC IE NC Y C ons oles Rev 3 0 June 2 0 0 8 B www climatemaster com Typical Wiring Diagram TRC Units 50Hz with DXM MPC Controller...

Страница 40: ...ote In the following field configuration options DIP switches should only be changed when power is removed from the CXM control DIP switch 1 Unit Performance Sentinel Disable provides field selection...

Страница 41: ...on Low pressure normally open Jumper 1 JW1 LP norm open provides field selection for low pressure input to be normally closed or normally open Not Clipped LP normally closed Clipped LP normally open D...

Страница 42: ...between the coaxial heat exchanger and the expansion device TXV or cap tube Therefore the 50 F 10 C setting is not 50 F 10 C water but approximately 60 F 16 C EWT On 50 F 10 C Off 40 F 16 C DIP Packa...

Страница 43: ...ockout code 2 Example 2 quick flashes 10 sec pause 2 quick flashes 10 sec pause etc Low pressure switch The low pressure switch must be open and remain open for 30 continuous seconds during on cycle t...

Страница 44: ...ernal common signal to terminal ESD to shut down the unit The green status light will flash code 3 when the unit is in ESD mode ESD mode code 3 green status LED CXM DXM Controls Diagnostic Features Th...

Страница 45: ...n a regular basis 2 Voltage utilization range complies with ARI Standard 110 Determination of operating limits is dependent primarily upon three factors 1 return air temperature 2 water temperature an...

Страница 46: ...m phosphate in a proportion of approximately one pound per 150 gallons 1 2 kg per 750 l of water or other equivalent approved cleaning agent Reset the boiler to raise the loop temperature to 100 F 38...

Страница 47: ...ystem water temperature Check water temperature for proper range and also verify heating and cooling set points for proper operation System pH Check and adjust water pH if necessary to maintain a leve...

Страница 48: ...FF position A hissing noise indicates proper functioning of the reversing valve 6 Allow five 5 minutes between tests for pressure to equalize before beginning heating test a Adjust the thermostat to t...

Страница 49: ...ng conditions and be replaced when necessary Units should never be operated without a filter Washable high efficiency electrostatic filters when dirty can exhibit a very high pressure drop for the fan...

Страница 50: ...r replace Air Coil low temperature limit in cooling Check fan motor operation and airflow restrictions Too high of external static Check static vs blower table X Air Temperature out of range Too much...

Страница 51: ...ck for 24VAC on W check between W and C There should be voltage on O but not on W If voltage is present on W thermostat may be bad or wired incorrectly Performance Troubleshooting Only Compressor Runs...

Страница 52: ...ANALYSIS COAX COMPRESSOR DISCHARGE SUCTION HWG HEATING CYCLE ANALYSIS PSI SAT PSI SAT F F AIR COIL F F FP2 HEATING LIQUID LINE F EXPANSION VALVE AIR COIL F F PSI SAT PSI SAT F F F F WATER IN WATER OU...

Страница 53: ...the improper application of CM s products CM is not responsible for 1 The costs of any fluids refrigerant or other system components or associated labor to repair or replace the same which is incurre...

Страница 54: ...rrect system design or the improper application of CM s products CM is not responsible for 1 The costs of any fluids refrigerant or other system components or associated labor to repair or replace the...

Страница 55: ...55 THE SMAR T SOLUTION FOR ENERGY EFF IC IE NC Y C ons oles Rev 3 0 June 2 0 0 8 B www climatemaster com Notes...

Страница 56: ...ct at the time for order may be changed without notice and may not be as described herein Please contact ClimateMaster s Customer Service Department at 1 405 745 6000 for speci c information on the cu...

Отзывы: