NextE CCE07 Скачать руководство пользователя страница 15

15

T H E   S M A R T   S O L U T I O N   F O R   E N E R G Y   E F F I C I E N C Y

C o n s o l e s

R e v. :   3 0   J u n e ,   2 0 0 8 B

w w w. c l i m a t e m a s t e r. c o m

Pre-Installation

Prior to installation, locate and mark all existing 
underground utilities, piping, etc. Install loops for new 
construction before sidewalks, patios, driveways, and 
other construction has begun. During construction, 
accurately mark all ground loop piping on the plot plan 
as an aid in avoiding potential future damage to the 
installation.

Piping Installation

All earth loop piping materials should be limited to 
polyethylene fusion only for in-ground sections of the 

loop. Galvanized or steel fittings should not be used at 

any time due to their tendency to corrode. All plastic to 

metal threaded fittings should be avoided due to their 
potential to leak in earth coupled applications. A flanged 
fitting should be substituted. P/T plugs should be used 
so that flow can be measured using the pressure drop of 

the unit heat exchanger. 

Earth loop temperatures can range between 25 and 
110°F [-4 to 43°C].  Flow rates between 2.25 and 3 gpm 
per ton [2.41 to 3.23 l/m per kW] of cooling capacity is 
recommended in these applications. 

CAUTION!

  The following instructions represent industry 

accepted installation practices for closed loop earth 
coupled heat pump systems. Instructions are provided 
to assist the contractor in installing trouble free ground 
loops. These instructions are recommendations only. 
State/provincial and local codes MUST be followed and 
installation MUST conform to ALL applicable codes. It is the 
responsibility of the installing contractor to determine and 
comply with ALL applicable codes and regulations.

CAUTION!

  Ground loop applications require extended range 

equipment and optional refrigerant/water circuit insulation.

� 

CAUTION! 

� 

CAUTION! 

Ground-Loop Heat Pump Applications

Test individual horizontal loop circuits before backfilling. 

Test vertical U-bends and pond loop assemblies prior to 
installation. Pressures of at least 100 psi [689 kPa] should 
be used when testing.  Do not exceed the pipe pressure 
rating.  Test entire system when all loops are assembled. 

Flushing the Earth Loop

Upon completion of system installation and testing, flush 

the system to remove all foreign objects and purge to 
remove all air. 

Antifreeze

In areas where minimum entering loop temperatures 
drop below 40°F [5°C] or where piping will be routed 

through areas subject to freezing, antifreeze is required. 

Alcohols and glycols are commonly used as antifreeze; 
however your local sales manager should be consulted 
for the antifreeze best suited to your area. Freeze 
protection should be maintained to 15°F [9°C] below 
the lowest expected entering loop temperature. For 
example, if 30°F [-1°C] is the minimum expected entering 
loop temperature, the leaving loop temperature would be 
25 to 22°F [-4 to -6°C] and freeze protection should be at 
15°F [-10°C].  Calculation is as follows:
30°F - 15°F = 15°F [-1°C - 9°C = -10°C]. 

All alcohols should be premixed and pumped from 
a reservoir outside of the building when possible or 
introduced under the water level to prevent fumes. 

Calculate the total volume of fluid in the piping system. 

Then use the percentage by volume shown in table 
2 for the amount of antifreeze needed. Antifreeze 
concentration should be checked from a well mixed 

sample using a hydrometer to measure specific gravity.

Low Water Temperature Cutout Setting

CXM or DXM Control

When antifreeze is selected, the FP1 jumper (JW3) should 
be clipped to select the low temperature (antifreeze 13°F 
[-10.6°C]) set point and avoid nuisance faults (see “Low 
Water Temperature Cutout Selection” in this manual).  NOTE:  

Low water temperature operation requires extended range 
equipment.

Содержание CCE07

Страница 1: ...Pump Applications 14 Ground Loop Heat Pump Applications 15 Ground Water Heat Pump Applications 16 Water Quality Standards 18 Electrical Wiring Line Voltage 19 21 Electrical Wiring Low Voltage 22 Therm...

Страница 2: ......

Страница 3: ...ed Water Valve A G N Autoflow 2 25 Gpm Ton B H P Autoflow 3 0 Gpm Ton C J Q Motorized Water Valve Afr 2 25 D K R Motorized Water Valve Afr 3 0 E L T Secondary Circulation Pump U V W Water Circuit Opti...

Страница 4: ...mote Mounted w DXM MPC G 208 230 60 1 B 20Amp Plug Cord D Disconnect Switch 15Amp Fuse F Disconnect Switch Non Fused H 20Amp Plug Cord Receptacle Disconnect Switch 15Amp Fuse K 20Amp Plug Cord Recepta...

Страница 5: ...in the compressor To avoid leakage of compressor oil refrigerant lines of the compressor must be sealed after it is removed CAUTION To avoid equipment damage DO NOT use these units as a source of hea...

Страница 6: ...ed for installation above false ceiling or in a ceiling plenum Other unit configurations are typically installed in a mechanical room The installation site chosen should include adequate service clear...

Страница 7: ...ttings in 1 2 1 2 1 2 1 2 1 2 Optional EPT Fittings in 1 2 1 2 1 2 1 2 1 2 Condensate Connection Size I D Vinyl Hose In mm 5 8 15 9 5 8 15 9 5 8 15 9 5 8 15 9 5 8 15 9 Air Coil Size Dimensions h x w i...

Страница 8: ...imensions h x w in mm 8 x 26 20 3 x 66 0 10 x 26 25 4 x 66 0 10 x 32 25 4 x 81 2 Filter Size Bottom Return in cm 1 10 x 30 x 1 25 4 x 76 2 x 2 5 2 10 x 16 x 1 25 4 x 40 6 x 2 5 Front Return In cm 1 7...

Страница 9: ...D Vinyl Hose In mm 5 8 15 9 Air Coil Size Dimensions h x w in mm 8 x 26 20 3 x 66 0 10 x 26 25 4 x 66 0 10 x 32 25 4 x 81 2 Filter Size Bottom Return in cm 1 10 x 30 x 1 25 4 x 76 2 x 2 5 10 x 36 x 1...

Страница 10: ...rated hose assemblies are available for use with ClimateMaster Console Units Use the following guidelines when installing supply and return hose assemblies 1 Install supply and return hoses fitted wi...

Страница 11: ...tly Horizontal runs of condensate hose should be pitched downward 1 4 inch minimum for every foot 10mm per 46cm of hose Avoid low points because dirt collects in these areas and may cause blockage If...

Страница 12: ...Hose Optional Disconnect Box mounted to cabinet not chassis Optional Motorized Water Valve Optional Autoflow Valve Water Connections 5 8 15 9 mm OD Copper 1 2 IPT or 1 2 EPT 7 5 191 3 42 87 3 56 90 Ri...

Страница 13: ...is not available tighten finger tight plus one quarter turn Tighten steel fittings as necessary Optional pressure rated hose assemblies designed specifically for use with ClimateMaster units are avai...

Страница 14: ...valve for use in variable speed pumping systems may also be included in the hose kit The piping system should be flushed to remove dirt piping chips and other foreign material prior to operation see...

Страница 15: ...water circuit insulation CAUTION CAUTION Ground Loop Heat Pump Applications Test individual horizontal loop circuits before backfilling Test vertical U bends and pond loop assemblies prior to install...

Страница 16: ...rect use A monitoring plan should be implemented in these probable scaling situations Other water quality issues such as iron fouling corrosion prevention and erosion and clogging should be referenced...

Страница 17: ...side of any field provided shut off valves and connected to the heat pump controls in series with the built in refrigerant circuit high pressure switch to disable compressor operation if water pressur...

Страница 18: ...lloy bronze or brass cast components are OK to 0 5 ppm Ammonia ion All 0 5 ppm as hydroxide chloride nitrate and sulfate compounds Maximum Maximum Allowable at maximum water temperature Chloride Level...

Страница 19: ...Code whichever is applicable Power Connection Line voltage connection is made by connecting the incoming line voltage wires to the L side of the contactor Consult Tables 4 through 5 for correct fuse...

Страница 20: ...55 8 1 0 11 6 14 3 25 G 208 230 60 1 197 254 1 5 2 24 0 0 6 5 8 7 1 15 E 265 60 1 239 292 1 4 2 25 0 0 4 4 6 5 7 15 TRC15 G 208 230 60 1 197 254 1 6 1 30 0 0 8 6 9 8 4 15 E 265 60 1 239 292 1 4 7 28...

Страница 21: ...B only required with systems employing remote mounted thermostats Figure 3 Typical Field Installed Wiring WARNING To avoid possible injury or death due to electrical shock open the power supply disco...

Страница 22: ...TRC models include digital display unit mounted controls see picture below Either manual changeover MCO or auto changeover ACO controls are available as indicated by the model number The room temperat...

Страница 23: ...he position of the back plate mounting holes and drill holes with a 3 16 5mm bit Install supplied anchors and secure plate to the wall Thermostat wire must be 18 AWG wire Wire the appropriate thermost...

Страница 24: ...MATEMASTER WATER SOURCE HEAT PUMPS Co n sole s R ev 30 J u n e 2008B 24 ClimateMaster Water Source Heating and Cooling Systems Typical Wiring Diagram Manual Change Over CCE Units Rev A with CXM Contro...

Страница 25: ...25 THE SMAR T SOLUTION FOR ENERGY EFF IC IE NC Y C ons oles Rev 3 0 June 2 0 0 8 B www climatemaster com Typical Wiring Diagram Auto Change Over CCE Units Rev A with CXM Controller...

Страница 26: ...TER WATER SOURCE HEAT PUMPS Co n sole s R ev 30 J u n e 2008B 26 ClimateMaster Water Source Heating and Cooling Systems Typical Wiring Diagram Manual Auto Change Over CCE Units Rev B TRC Units with CX...

Страница 27: ...27 THE SMAR T SOLUTION FOR ENERGY EFF IC IE NC Y C ons oles Rev 3 0 June 2 0 0 8 B www climatemaster com Typical Wiring Diagram Remote Mounted Thermosat CCE TRC Units with CXM Controller...

Страница 28: ...CL I MATEMASTER WATER SOURCE HEAT PUMPS Co n sole s R ev 30 J u n e 2008B 28 ClimateMaster Water Source Heating and Cooling Systems Typical Wiring Diagram CCE TRC Units with CXM MPC Controller...

Страница 29: ...29 THE SMAR T SOLUTION FOR ENERGY EFF IC IE NC Y C ons oles Rev 3 0 June 2 0 0 8 B www climatemaster com Typical Wiring Diagram Manual Change Over CCE Units Rev A with DXM Controller...

Страница 30: ...MATEMASTER WATER SOURCE HEAT PUMPS Co n sole s R ev 30 J u n e 2008B 30 ClimateMaster Water Source Heating and Cooling Systems Typical Wiring Diagram Auto Change Over CCE Units Rev A with DXM Control...

Страница 31: ...31 THE SMAR T SOLUTION FOR ENERGY EFF IC IE NC Y C ons oles Rev 3 0 June 2 0 0 8 B www climatemaster com Typical Wiring Diagram Manual Auto Change Over CCE Units Rev B TRC Units with DXM Controller...

Страница 32: ...TEMASTER WATER SOURCE HEAT PUMPS Co n sole s R ev 30 J u n e 2008B 32 ClimateMaster Water Source Heating and Cooling Systems Typical Wiring Diagram Remote Mounted Thermostat CCE TRC Units with DXM Con...

Страница 33: ...33 THE SMAR T SOLUTION FOR ENERGY EFF IC IE NC Y C ons oles Rev 3 0 June 2 0 0 8 B www climatemaster com Typical Wiring Diagram CCE TRC Units with DXM MPC Controller...

Страница 34: ...TEMASTER WATER SOURCE HEAT PUMPS Co n sole s R ev 30 J u n e 2008B 34 ClimateMaster Water Source Heating and Cooling Systems Typical Wiring Diagram Manual Auto Change Over TRC Units 50Hz with CXM Cont...

Страница 35: ...35 THE SMAR T SOLUTION FOR ENERGY EFF IC IE NC Y C ons oles Rev 3 0 June 2 0 0 8 B www climatemaster com Typical Wiring Diagram Remote Mounted Thermostat TRC Units 50Hz with CXM Controller...

Страница 36: ...CL I MATEMASTER WATER SOURCE HEAT PUMPS Co n sole s R ev 30 J u n e 2008B 36 ClimateMaster Water Source Heating and Cooling Systems Typical Wiring Diagram TRC Units 50Hz with CXM DXM Controller...

Страница 37: ...37 THE SMAR T SOLUTION FOR ENERGY EFF IC IE NC Y C ons oles Rev 3 0 June 2 0 0 8 B www climatemaster com Typical Wiring Diagram Manual Auto Change Over TRC Units 50Hz with DXM Controller...

Страница 38: ...EMASTER WATER SOURCE HEAT PUMPS Co n sole s R ev 30 J u n e 2008B 38 ClimateMaster Water Source Heating and Cooling Systems Typical Wiring Diagram Remote Mounted Thermostat TRC Units 50Hz with DXM Con...

Страница 39: ...39 THE SMAR T SOLUTION FOR ENERGY EFF IC IE NC Y C ons oles Rev 3 0 June 2 0 0 8 B www climatemaster com Typical Wiring Diagram TRC Units 50Hz with DXM MPC Controller...

Страница 40: ...ote In the following field configuration options DIP switches should only be changed when power is removed from the CXM control DIP switch 1 Unit Performance Sentinel Disable provides field selection...

Страница 41: ...on Low pressure normally open Jumper 1 JW1 LP norm open provides field selection for low pressure input to be normally closed or normally open Not Clipped LP normally closed Clipped LP normally open D...

Страница 42: ...between the coaxial heat exchanger and the expansion device TXV or cap tube Therefore the 50 F 10 C setting is not 50 F 10 C water but approximately 60 F 16 C EWT On 50 F 10 C Off 40 F 16 C DIP Packa...

Страница 43: ...ockout code 2 Example 2 quick flashes 10 sec pause 2 quick flashes 10 sec pause etc Low pressure switch The low pressure switch must be open and remain open for 30 continuous seconds during on cycle t...

Страница 44: ...ernal common signal to terminal ESD to shut down the unit The green status light will flash code 3 when the unit is in ESD mode ESD mode code 3 green status LED CXM DXM Controls Diagnostic Features Th...

Страница 45: ...n a regular basis 2 Voltage utilization range complies with ARI Standard 110 Determination of operating limits is dependent primarily upon three factors 1 return air temperature 2 water temperature an...

Страница 46: ...m phosphate in a proportion of approximately one pound per 150 gallons 1 2 kg per 750 l of water or other equivalent approved cleaning agent Reset the boiler to raise the loop temperature to 100 F 38...

Страница 47: ...ystem water temperature Check water temperature for proper range and also verify heating and cooling set points for proper operation System pH Check and adjust water pH if necessary to maintain a leve...

Страница 48: ...FF position A hissing noise indicates proper functioning of the reversing valve 6 Allow five 5 minutes between tests for pressure to equalize before beginning heating test a Adjust the thermostat to t...

Страница 49: ...ng conditions and be replaced when necessary Units should never be operated without a filter Washable high efficiency electrostatic filters when dirty can exhibit a very high pressure drop for the fan...

Страница 50: ...r replace Air Coil low temperature limit in cooling Check fan motor operation and airflow restrictions Too high of external static Check static vs blower table X Air Temperature out of range Too much...

Страница 51: ...ck for 24VAC on W check between W and C There should be voltage on O but not on W If voltage is present on W thermostat may be bad or wired incorrectly Performance Troubleshooting Only Compressor Runs...

Страница 52: ...ANALYSIS COAX COMPRESSOR DISCHARGE SUCTION HWG HEATING CYCLE ANALYSIS PSI SAT PSI SAT F F AIR COIL F F FP2 HEATING LIQUID LINE F EXPANSION VALVE AIR COIL F F PSI SAT PSI SAT F F F F WATER IN WATER OU...

Страница 53: ...the improper application of CM s products CM is not responsible for 1 The costs of any fluids refrigerant or other system components or associated labor to repair or replace the same which is incurre...

Страница 54: ...rrect system design or the improper application of CM s products CM is not responsible for 1 The costs of any fluids refrigerant or other system components or associated labor to repair or replace the...

Страница 55: ...55 THE SMAR T SOLUTION FOR ENERGY EFF IC IE NC Y C ons oles Rev 3 0 June 2 0 0 8 B www climatemaster com Notes...

Страница 56: ...ct at the time for order may be changed without notice and may not be as described herein Please contact ClimateMaster s Customer Service Department at 1 405 745 6000 for speci c information on the cu...

Отзывы: