BATTERY STATUS:
Battery Status:
‘XX.XX’
Battery voltage
Normal readings ‘12.40-13.20’ (Charger Off)
‘Disc’
Battery disconnected
Displays when Battery is disconnected or Battery voltage
is below 1.50 volts
‘Rep_’
Replace Battery
(The ‘_ ‘ indicates the reason for failure “numeric value”)
See (Battery Troubleshooting)
If Notification is Installed:
Notification will occur on a Battery Disconnected or Low
Battery or Battery Replacement Alert after approximately
five (5) Minutes. After an AC Power Outage when running
on Battery, Notification will occur after approximately
thirty (30) Minutes.
Clear Battery Alerts:
Only Battery Replacement Alerts can be cleared. To Clear
a Battery Replacement Alert, use Function
'C'
Testing:
Battery is tested on 12 Hour Self-Tests or Manual Tests.
Exceptions: Charge System is Active, Battery Disconnect,
Battery Replacement Alert is Active.
Menu Options for Battery Operations:
Function 'K' Battery Operations:
Menu Item to set or reset Battery Amp Hours:
(Set Total Amp Hours of Batteries Connected. Press and
hold Function Button at this menu, number will increment
by 5. Release at desired amount. Defaults to 105 AH)
Menu Item to turn on Battery Charger:
(Turn on Charger when system is first installed or when
replacing Batteries. Press and hold Function Button at this
menu, cursor will toggle between 'Y' and 'N'. Release at
desired position)
Menu Item to reset Battery Life Timer:
(Batteries have a lifespan and should be replaced when the
NexPump reports this time frame has expired. This should
also be reset when replacing batteries. Defaults for battery
type selected. WET = '1300 Days, 3.5 Years', AGM =
'1600 Days, 4.5 Years'')
Menu Item for Battery Type:
(Select Battery Type to type installed. Press and hold
Function Button at this menu, cursor will toggle between
'W' and 'A'. Release at desired position)
Function 'I' Battery Operations:
Info Item to check Battery Amp Hours and Type:
BA=Battery Amp\Hours, Batt=Battery Type
Running On Battery Power:
Location '(C) AC Power Status' above indicats an AC
Power Loss 'O'. If the alarm is silenced this location will
be blinking to indicate the alarm is silenced. Location '(F)
Battery Life' will indicate the Battery Life in Hours
Remaining when AC Power fails. ‘999’ Hours is the
maximum number displayed. The Battery Life Monitor
calculates the remaining life about 4 times an hour. When
running on battery power you should closely monitor the
Battery Life when the Hours Indicated are ten (10) or
below. Fluctuating pump(s) times, battery condition and
battery state before going to battery power will affect the
calculated time throughout the power loss, in addition this
number may not be accurate if the Battery Amps Hours are
not set correctly before the Power Outage began. The
alarm will also sound from the loss of electric power,
which may silenced by performing a Function 'S'. Once
AC power is restored the display will again display a
normal status. A charge cycle may also be enabled at the
time AC Power is restored.
10
(E) Battery or Notification Status