background image

FORM NO. L-20341-E-0208

ALIGNMENT (SEE FIGuRE 2)

1.  The Transmitter must be the upper unit with 

the Receiver mounted below when used with a 
horizontal web run.

2.  The angle of inclination to the web must be 45° + 5

o

.

3.  The Transmitter to Receiver gap must be 

 

2.36 + 0.20  in. [60 + 5 mm].

4.  The lateral displacement must be within 0.20 In. 

[5 mm].

5.  The angular displacement must be  3

o

.

FIGuRE  3

1.  Provide AC Power 100, 110, 120, 200, 220, 

240VAC, 50 or 60 Hz at Terminals 1 and 2.  
Connect the ground wire to Terminal 3 (See Figure 
3).

2.  Connect the Sensor Transmitter 16 ft.  [5 m] cable to 

Terminals 4 and 5 (See Figure 3).

NOTE: Do not extend this cable length.

3.  Terminals 7, 8, and 9 provide the Web Break Relay 

contact signal.  Wire as appropriate for Normally 
Open (N.O.) or Normally Closed (N.C.) logic (See 
Figure 3).

4.  Terminals 10, 11, and 12 provide the double sheet-

feed (two sheets stacked on top of each other) 
contact signal for sheet-fed machines or the splice 
contact signal for web-fed machines.  Make electrical 
connections as appropriate for N.O. or N.C. logic 
(See Figure 3).

5.  A relay may be connected to Terminals 13 and 14 

to prevent triggering of either the Web Break or 

Double Sheet Feed/Web Splice condition.  The relay 
must be a normally open type which closes when 
triggering is to be prevented.

 

This Lock Out Relay is normally used to prevent 
false triggering when the web or sheets stop moving 
as the machine is stopped.  As the web or sheets 
stop moving they often change position (sag, relax 
tension, etc.) which causes false triggering.

 
6.  A remote button can be used to reset the system 

after a double feed or splice signal, when the 
machine is in manual reset mode.  If this option is 
used, a customer supplied N.O. momentary contact 
remote Output Reset switch must be connected to 
Terminals 15 and 16 (See Figure 3).

7.  Connect the Sensor Receiver 16 ft. [5 m] cable to 

Terminals 17, 18, 19, and 20 (See Figure 3).

NOTE: Do not extend this cable length.

INSTALLATION

     (continued...)

ELECTRICAL CONNECTIONS

Содержание Paper Checker PC210

Страница 1: ...WEB CONTROL PRODUCTS User Manual Paper Checker PC210 FORM L 20341 E 0208...

Страница 2: ...echnical Support 800 843 7445 651 484 5900 www nexengroup com Copyright 2008 Nexen Group Inc Nexen Group Inc 560 Oak Grove Parkway Vadnais Heights Minnesota 55127 ISO 9001 Certified Read this manual c...

Страница 3: ...M NO L 20341 E 0208 Table of Contents THEORY OF OPERATION 4 INSTALLATION 4 ELECTRICAL CONNECTIONS 6 FRONT PANEL CONTROLS INDICATORS 7 SETUP CONTROLS 8 OPERATION 9 CALIBRATION 13 SPECIFICATIONS 15 WARR...

Страница 4: ...ectronic controls Locations for electronic controls must be free of shock vibrations high temperatures and moisture The sending and receiving elements of the Sensor are provided with a 16 Ft 5 m cable...

Страница 5: ...t least 80 in 2m apart In no event may the sensors be placed closer than 8 in 20 cm WEB FED MACHINES The Sensor must be installed where the web pass line is stable and does not change If possible posi...

Страница 6: ...contact signal for sheet fed machines or the splice contact signal for web fed machines Make electrical connections as appropriate for N O or N C logic See Figure 3 5 A relay may be connected to Term...

Страница 7: ...the relay at Terminals 10 11 and 12 changes state See Figure 4 The Test Switch with imbedded indicator LED allows the Sensor to be tested for sensitivity to various materials thickness web breaks etc...

Страница 8: ...for web splice double sheet feed when the PC210 is to be used in Modes 4 or 5 Mode 7 Used when the PC210 is used to detect double sheet feeding in a sheet fed machine Web Thickness Selector Switch se...

Страница 9: ...may set for any time in the range of 0 2 6 seconds If the Output Reset Selector Switch is in MAN the relay will not return to its normal state until the Reset Switch located on the front panel is push...

Страница 10: ...asurements are normal run and web splice See Table 1 for Output Configurations for Modes 1 and 4 During normal run with a single thickness of web passing through the Sensor the Normal Run Indicator LE...

Страница 11: ...to all splice detection The splice must be at least 0 8 In 20 mm long Web thickness can be from 0 0004 0 003 In 1 00 8 mm Splice thickness must always be at least 0 002 In 0 05 mm It may be necessary...

Страница 12: ...where both web break and web splice detection are required NOTE Web thickness must be set at least 0 002 In 0 05 mm to use this mode Mode 2 and 5 are the same as Modes 1 and 4 for Web Splice Sensing...

Страница 13: ...RECTIVE ACTION 45o No Web in Sensor Normal Abnormal 1 Is the Sensor installed and aligned correctly 2 Has dust accumulated inside the Sensor tube Clean the Sensor tube with an air gun or remove the Se...

Страница 14: ...et time adjust VR1 as follows 1 Turn power OFF using the Power Switch located on the front panel of the PC210 See Figure 9 2 Remove the four screws and Top Cover from the PC210 See Figure 9 3 Turn pow...

Страница 15: ...n e p O r o t c a t n o C y r D A m 0 1 C D V 5 t e s e R t u p t u O r o t c e l l o C n e p O r o t c a t n o C y r D t u p t u O K A E R B B E W d e t a R t c a t n o C y r D p m A 1 0 C D V 4 2 p...

Страница 16: ...R OTHER BREACH OF CONTRACT NEGLIGENCE OR OTHER TORT OR OTHERWISE EVEN IF NEXEN SHALL HAVE BEEN ADVISED OF THE POSSIBILITY OR LIKELIHOOD OF SUCH POTENTIAL LOSS OR DAMAGE For all of the purposes hereof...

Отзывы: