Nexen Paper Checker PC210 Скачать руководство пользователя страница 13

1

FORM NO. L-20341-E-0208

T

esT

 R

un

 

in

 W

eb

 b

Reak

 o

peRaTion

1.  Set the Mode Selector Switch to Mode 2 or 5.

2.  Set the Web Thickness Selector Switch as 

appropriate for web.

3.  Set the Power Switch to 

ON

.

4.  Check operation according to Table 5.

5.  The Test Switch can be depressed prior to testing 

to prevent the Web Break Relay from changing state 
when a test piece is placed in the sensor path with 
an open section (which looks like a web break).  
The PC210 is in test mode when the red

 

LED in 

the Test Switch glows.  When the open section 
passes through the sensor, the Normal Run Indicator 
should go out and the Web Break Indicator should 
glow.  The PC210 will return to normal State when a 
section of web reenters the Sensor.

6.  Depress Test Switch again and the imbedded LED 

will go out, indicating the PC210 is back to normal 
operation and the Web Break Relay is operational.

CONDITION

STATuS

CORRECTIvE ACTION

45

o

No Web in Sensor

Normal

Abnormal

1.  Is the Sensor installed

 

and aligned correctly?

2.  Has dust accumulated inside

 

the Sensor tube?

 

(Clean the Sensor tube with an

 

air gun or remove the Sensor

 

tube for cleaning.)

Normal

Abnormal

Set  the  Web  Thickness  Selector 

Switch LEFT 0.002 - 0.008 In. [0.05 

- 0.020 mm].

Single thickness of Web in Sensor

TABLE  5  WEB BREAk OPERATION

None

None

CALIBRATION

This potentiometer adjusts PC210 sensitivity to splices.  

It has no effect in Sheet-Fed Mode 

7

.

The Web Splice Sensitivity Control is normally set to 

Position 

3

.  In rare cases where the thickness of the 

splice is not twice the thickness of the web (as a butt 

splice made with single sided taping and very thin tape), 

it may be necessary to increase sensitivity (See Figure 6).  

The sensitivity should be increased slowly from 

3.5 

or 

even 

4

.

NOTE: An increase in sensitivity will also increase the 

possibility of false triggering.  Increase sensitivity slowly 

and only as much as necessary.

Web Splice

Sensitivity Control

FIGuRE  7

WEB SPLICE SENSITIvITY CONTROL 

(See Figure 7)

OPERATION

     

(continued...)

(continued...)

Содержание Paper Checker PC210

Страница 1: ...WEB CONTROL PRODUCTS User Manual Paper Checker PC210 FORM L 20341 E 0208...

Страница 2: ...echnical Support 800 843 7445 651 484 5900 www nexengroup com Copyright 2008 Nexen Group Inc Nexen Group Inc 560 Oak Grove Parkway Vadnais Heights Minnesota 55127 ISO 9001 Certified Read this manual c...

Страница 3: ...M NO L 20341 E 0208 Table of Contents THEORY OF OPERATION 4 INSTALLATION 4 ELECTRICAL CONNECTIONS 6 FRONT PANEL CONTROLS INDICATORS 7 SETUP CONTROLS 8 OPERATION 9 CALIBRATION 13 SPECIFICATIONS 15 WARR...

Страница 4: ...ectronic controls Locations for electronic controls must be free of shock vibrations high temperatures and moisture The sending and receiving elements of the Sensor are provided with a 16 Ft 5 m cable...

Страница 5: ...t least 80 in 2m apart In no event may the sensors be placed closer than 8 in 20 cm WEB FED MACHINES The Sensor must be installed where the web pass line is stable and does not change If possible posi...

Страница 6: ...contact signal for sheet fed machines or the splice contact signal for web fed machines Make electrical connections as appropriate for N O or N C logic See Figure 3 5 A relay may be connected to Term...

Страница 7: ...the relay at Terminals 10 11 and 12 changes state See Figure 4 The Test Switch with imbedded indicator LED allows the Sensor to be tested for sensitivity to various materials thickness web breaks etc...

Страница 8: ...for web splice double sheet feed when the PC210 is to be used in Modes 4 or 5 Mode 7 Used when the PC210 is used to detect double sheet feeding in a sheet fed machine Web Thickness Selector Switch se...

Страница 9: ...may set for any time in the range of 0 2 6 seconds If the Output Reset Selector Switch is in MAN the relay will not return to its normal state until the Reset Switch located on the front panel is push...

Страница 10: ...asurements are normal run and web splice See Table 1 for Output Configurations for Modes 1 and 4 During normal run with a single thickness of web passing through the Sensor the Normal Run Indicator LE...

Страница 11: ...to all splice detection The splice must be at least 0 8 In 20 mm long Web thickness can be from 0 0004 0 003 In 1 00 8 mm Splice thickness must always be at least 0 002 In 0 05 mm It may be necessary...

Страница 12: ...where both web break and web splice detection are required NOTE Web thickness must be set at least 0 002 In 0 05 mm to use this mode Mode 2 and 5 are the same as Modes 1 and 4 for Web Splice Sensing...

Страница 13: ...RECTIVE ACTION 45o No Web in Sensor Normal Abnormal 1 Is the Sensor installed and aligned correctly 2 Has dust accumulated inside the Sensor tube Clean the Sensor tube with an air gun or remove the Se...

Страница 14: ...et time adjust VR1 as follows 1 Turn power OFF using the Power Switch located on the front panel of the PC210 See Figure 9 2 Remove the four screws and Top Cover from the PC210 See Figure 9 3 Turn pow...

Страница 15: ...n e p O r o t c a t n o C y r D A m 0 1 C D V 5 t e s e R t u p t u O r o t c e l l o C n e p O r o t c a t n o C y r D t u p t u O K A E R B B E W d e t a R t c a t n o C y r D p m A 1 0 C D V 4 2 p...

Страница 16: ...R OTHER BREACH OF CONTRACT NEGLIGENCE OR OTHER TORT OR OTHERWISE EVEN IF NEXEN SHALL HAVE BEEN ADVISED OF THE POSSIBILITY OR LIKELIHOOD OF SUCH POTENTIAL LOSS OR DAMAGE For all of the purposes hereof...

Отзывы: