Configuration
Single-ended
Polarity
Unipolar
Step Response
0.7 sec for 99.9%
Decimal Selection
None, 0.1, 0.01 or 0.001
Setpoint Adjustment
-1999 to 9999 counts
Span Adjustment
0.001 to 9999 counts
Offset Adjustment
-1999 to +9999
NETWORK AND COMMUNICATIONS
(Optional -C24, -C4EI, -EI not
available with excitation)
Ethernet:
Standards Compliance IEEE
802.3 10Base-T
Supported Protocols:
TCP/IP, ARP,
HTTPGET
RS-232/RS-422/RS-485/MODBUS:
Selectable from menu; both ASCII and
modbus protocol selectable from menu.
Programmable 300 to 19.2 K baud;
complete programmable setup
capability; program to transmit current
display, alarm status, min/max, actual
measured input value and status.
RS-485
Addressable from 0 to 199
Connection
Screw terminals
ALARM 1 & 2
Programmable to Display Color Change
250 Vac or 30 Vdc @ 3 A
(Resistive Load); configurable for on/off,
PID and Ramp and Soak
PART 4
Accuracy
0.03% reading
Resolution
10 / 1 µV
Temperature Stability
50 ppm/°C
NMRR
60 dB
CMRR
120 dB
A/D Conversion
Dual slope
Reading Rate
3 samples per second
Digital Filter
Programmable
Display
Single 4-digit, 9-segment LED;
• 10.2 mm (0.4" for i/32),
• 21 mm (0.83" for i/8);
red, green and amber programmable
colors for process variable and set
points
Warm up to Rated Accuracy
30 min.
INPUT
Input Types
Analog Voltage, Analog Current
Voltage Input
0 to 100 mV, 0 to 1 V (+100 mV),
0 to 10 Vdc
Input Impedance:
10 MΩ for 100 mV
1 MΩ for 1 V or 10 Vdc
Current Input
0 to 20 mA (5 ohm load)
Linearization Points
Up to 10 Linearization Points