20

POSSIBLE CAUSE

1. Extremely discharged
batteries requiring long re-
charge time

2. Charger limiting its output
due to overload or over-
temperature conditions

3. Fan not operating prop-
erly, causing charger to over-
heat, reducing or ceasing
power output

1. d.c. load connected to
batteries drawing current (not
a problem condition)

2. Bad cell in one of the
batteries to which the charger
is connected

1. Blown input or output fuse
or other internal defect

SOLUTION

1. Turn off all d.c. loads and
allow charger 24-48 hours to
recharge batteries

2. Reduce d.c. load and/or
determine cause of over-
temperature condition (see
section III-B, Location)

3. Check to ensure there is
no blockage at fan intake on
bottom of charger. Replace
fan if necesssary (see section
IV-G, Cooling Fan)

1. Turn off main battery
switch to d.c. electrical panel
or turn of all d.c. loads if you
wish to confirm charger will
output minimal amperage to
fully charged batteries

2. Check for shorted cell in
wet lead-acid batteries using
a hydrometer. Refer to manu-
facturer for testing mainte-
nance-free batteries

1. Return to servicing dealer
for failure analysis or contact
NEWMAR for Return Authori-
zation Number

VII

TROUBLESHOOTING

PROBLEM

A. Batteries not coming up to
full charge

B. Charger continues to
charge at 3 amps or more—
does not taper back

C. No charger output, even
when all connections have
been checked, a.c. is applied
to the charger, and a d.c.
load is applied to the batter-
ies

Note

: The PT-70a and PT-24-40 chargers incorporate self-contained a.c. to d.c. conver-

sion modules which utilize numerous automatic protection circuits. The a.c. input and
d.c. output fuses which protect internal wiring are housed inside the charger with these
modules. Under most circumstances these fuses will fail only if the charger has an
internal fault. Hence, they are not intended to be user-replaceable and any condition
which has caused a blown fuse will likely require repair of other internal circuitry by a
qualified technician. If an apparent charger fault cannot be corrected using any of the
recommendations in this section, the charger should be returned to the factory or place
of purchase for inspection and repair or replacement.

Содержание Phase Three PT-24-40

Страница 1: ...B Location 5 C Mounting 6 D d c Output Wiring 6 E Multiple Unit Parallel Wiring 8 F a c Input Wiring 8 IV OPERATION 10 A Three Stage Charge Regimen 10 B Time Out Circuit 11 C Gel Cell Lead Acid Select...

Страница 2: ...based on battery type Multiple output banks charge independently based on demand Universal input of 90 264V a c 50 60 Hz input with no setting of selector switch required can be used anywhere in the...

Страница 3: ...ended or sold by NEWMAR may result in a risk of fire electric shock or injury to persons 6 To reduce the risk of damage to the electric plug and cord if plugged into an a c outlet pull by plug rather...

Страница 4: ...low a spark or flame in the vicinity of the battery or engine 6 Be extra cautious to reduce the risk of dropping a metal tool onto the battery It might spark or short circuit the battery or other elec...

Страница 5: ...isfaction card has been included in the packaging Upon completion of the installation please fill out this card and return it to the factory You will be contacted promptly if you have any problems wit...

Страница 6: ...hat required for the d c current carrying conductors and not less than 16 AWG Make a mark on the wall or bulkhead where each of the keyhole slots will be located Then drive a screw about halfway in at...

Страница 7: ...fuse The fuse is not user replaceable If this fuse blows the unit must be returned to NEWMAR or a qualified electronic technician for repair Typical d c wiring configurations are illustrated in FIGUR...

Страница 8: ...rger may be wired in parallel The unit is diode protected so it will not be damaged by feedback from the second unit and current limiting will prevent overloading in the case of a failure of one of th...

Страница 9: ...rd of equal or larger AWG rating with stranded not solid conductors Remove the a c input terminal cover by removing one front panel and two bottom panel screws Loosen the strain relief to slide the co...

Страница 10: ...tinues until battery voltage reaches the charge voltage level where batteries are at about 75 80 of capacity A cur rent limit circuit prevents charger overload during this maximum output stage Note Du...

Страница 11: ...he charger or when the reinitialize button on the optional remote panel is activated and runs for a pre set interval before forcing the charger to go into the float lower voltage mode The functioning...

Страница 12: ...efore timing out or counter clockwise to decrease the amount of time The approximate ranges are illustrated below FIGURE 5 Adjusting the Time out Circuit Note Once the time out circuit has put the cha...

Страница 13: ...remote location Red and green L E D s indicate whether the charger is in the bulk absorption or float phase of the charge cycle In addition the panel features a re initialize button which when presse...

Страница 14: ...gel cell batteries The remote sensor is provided with 30 of cable One end of the cable is plugged into the temperature compensation jack which is located on the right side of the charger See FIG URE...

Страница 15: ...rger when batteries are at 72 F or when the sensor is not installed and at cold 50 F or hot 90 F battery temperatures with the sensor installed F Equalize Timer Option Some manufacturers of flooded le...

Страница 16: ...s instructions when deciding the appropriate time period setting for this voltage to achieve proper equalization while ensuring batteries are not damaged by increased battery temperature This install...

Страница 17: ...with the molded arrow at the top of the fan facing away from the plate 7 Reconnect the in line wire assembly and slide the fan back into the charger taking care to fit the assembly between the guides...

Страница 18: ...Refer to Specifications section for continuous duty ratings at 115V and 230V While the charger cannot be damaged by over loads that exceed this continuous rating excessive load demands may draw batte...

Страница 19: ...mum in Bulk Phase 65 amps maximum in Absorption Float Phases PT 24 40 40 amps maximum in Bulk Phase 36 amps maximum in Absorption Float Phases Output Current 115V a c Input PT 70a 65 amps maximum in B...

Страница 20: ...harger will output minimal amperage to fully charged batteries 2 Check for shorted cell in wet lead acid batteries using a hydrometer Refer to manu facturer for testing mainte nance free batteries 1 R...

Страница 21: ...ed across charger output termi nals F Charger will not stay in bulk absorption phase when re initialize button on remote panel is pressed G Maximum output of charger is 35 amps model PT 70a or 20 amps...

Страница 22: ...he battery to discharge by itself Therefore at least twice a year it is a good idea to disconnect the battery cables and scrub the battery with a baking soda solution Rinse with fresh water and dry wi...

Страница 23: ...ccept or hold a charge one of the following conditions may exist 1 A BAD BATTERY You may have a battery with an open or shorted cell a battery without any life left Check by charging the battery until...