7
P.O. Box 1306
Newport Beach
California 92663
Phone: 714-751-0488
Fax: 714-957-1621
E-Mail: [email protected]
www.Newmarpower.com
Automation DC Power • Powering the Network
4) Settings
A) Battery Type/Charge Curve
Charge curve per battery type: via programing jumpers on top
panel of unit left side.
Using programming jumper tabs provided and a small needle
nose pliers, insert programming jumpers to select fl oat voltage and
enable absorption voltage per per battery type. Caution do
not program unit while connected to power.
B) Battery Charge Current Limit/Battery Charge Level
Allows setting maximum current fl ow to battery during recharge cycle- use when low amp-hour batteries are applied to
system to prevent overheating when recovering dead batteries. Adjustment range 20-100% of available charge current.
(Available charge current = unit output rating of 20 amps minus load demand. Note: the unit has a load priority circuit, all
produced power is made available to the load, remaining power is available for battery charging).
To set, use small slotted screw driver to rotate selector dial. Set dial between 10 to 20% of battery capacity (Amp Hours).
Figure 10: Current Limit/Battery Charge Level - Dial
Table 4: Battery Selection/Absorption Charge
Figure 9: Battery Type
Insert jumper tabs for
battery selection
MIN
MAX
L
N
(3)
(4)
BATTRY
INPUT
BATTERY
CHARGING LEVEL
i
AC
FAIL
LOW BATTERY
OR BATTERY
REPLACEMENT
DIAGNOSIS
BATTERY
START
TIME
BUFFERING
0 1 2
345
67
8 9
A
U
X
3
OUTPUT LOAD
(1)
(2)
BATTERY
SELECTION
AC
FAIL
LOW BATTERY
OR BATTERY
REPLACEMENT
5 6 7 8 9 10
JUMPER FOR
115 Vac
DIN-UPS 12-35
OUTPUT: 12Vdc 35A
INPUT: 115-230Vac
T
E
M
P
P
R
O
B
E
C
O
M
M
O
D
B
U
S
(714) 751-0488
Www.automationdcpower.com
Newport Beach, CA USA
Battery Type
Selection
Float Charge/
Jumper Insert Position
Absorption Charge Enaable/
Jumper Insert Position
Open Lead
(Default)
None
26.76 VDC
Pos. 6
28.8 VDC
Sealed Lead
Insert Jumper: Pos. 1
Pos. 1
27.0 VDC
Pos. 6
28.8 VDC
Gel Battery
Insert Jumper: Pos. 2
Pos. 2
27.6 VDC
Pos. 6
28.8 VDC
Ni-Cad
Insert Jumper: Pos. 3
Pos. 3
*See note below
Pos. 6
31.0 VDC (1.55 VPC x 20 Cells)
1 2 3 4 7
5
6
1 2 3 4 7
5
6
1 2 3 4 7
5
6
1 2 3 4 7
5
6
1 2 3 4 7
5
6
1 2 3 4 7
5
6
1 2 3 4 7
5
6
1 2 3 4 7
5
6
Absorption Charge: Unit
outputs 29.2 VDC for two
minutes, then output is
reduced to 28.8 VDC