Page 7
¾
AC Input Terminal
Terminal for bypass VAC input voltage.
A 115 VAC, 20 amp circuit is recommended for full power operation.
¾
AC Input Breaker
Breaker for AC input
¾
DC Input Terminal
Terminal for VDC input voltage
¾
Dry Contact Terminal
Dry contact terminal is connected to two Form C relays. One is for “DC abnormal” and the other one is for
“FAULT”.
When input DC voltage or fault occurs, the internal contact relay will open/close.
The terminal can support 5A / 250VAC
3-5 Bypass Switching and Grounding
DC/AC
AC Bypass
INV-L
INV-N
AC I/P
DC I/P
+
-
AC L
AC N
GND
GND
O/P
Inverter Relay
Bypass Relay
Chassis
Chassis
Operation =
Off – Line Mode
:
AC input supplied from local service panel,
AC I/P neutral to earth connection provided externally.
(Usually service panel)
Operation =
On– Line Mode
:
DC input supplied from battery/DC power system
Inverter originated AC, therefore neutral to earth connection provided internally to chassis.
Grounding:
Chassis to Earth Ground connection should be made per customer installation specifications or prevailing safety
jurisdiction authority.
The inverter external safety ground plane is not switched by operation in any mode. Typically - the chassis is
mounted in a rack or a conductor to ground plane is installed.
4. INSTALLATION
4-1 Delivery
Upon receipt of goods, check the condition of the package. Should the package or unit be damaged, refuse
receipt and/or contact your shipper immediately to initiate your claim.
4-2 Installation Procedures
¾
Mount unit using the brackets and screws supplied in the hardware kit.
Содержание 125-1000RM