1.2 Flue & chimney suitability 

This appliance is designed for use with conventional brick built or lined chimneys all flues must 
conform to the following minimum dimensions 

Minimum dimension of flue    

125 mm Diameter. 

Minimum effective height of all flue types      3 metres 

 

Before commencing installation, a flue or chimney should be inspected to ensure that all of the 
following conditions are satisfied. 

 

1. 

 Check that the chimney / flue only serves one fireplace and is clear of any obstruction, 

any                dampers or register plates must be removed or securely locked in the open position.

 

 

2. 

 Brick / stone-built chimneys or any chimney or flue which has been used for an appliance 

burning       fuel other than gas must be thoroughly swept.

 

 

3. 

 Any under floor air supply to the fireplace must be completely sealed off.

 

 

4. 

 Ensure that the inside of the chimney / flue is in good condition along its length and check 

that  there is no leakage of smoke through the structure of the chimney / flue during and after 
the smoke pellet test.

 

 

5. 

 Using a smoke pellet check there is an updraft in the chimney / flue and that the smoke can 

be  seen coming from the terminal / pot outside.

 

There must be no leakage of smoke through the structure of the chimney during or after the 
smoke pellet test and it is important to check the inside upstairs rooms adjacent to the chimney / 
flue. 

 

Check the chimney pot / terminal and general condition of the brickwork and masonry. if the 
chimney / flue is in poor condition or if there is no up-draught do not proceed with the installation, 
IIIIf there is a history of down draught conditions with the chimney / flue, a tested and certificated 
flue terminal or cowl suitable for the relevant flue type should be   considered. 

 

6. 

 A spillage test must always be carried out during commissioning of this appliance

 

 
 
 
 
 
 

 

REAR OF STOVE

 

 
 
 

 

OKE MATCH 

SM 

Содержание FLAME VIEW ST1

Страница 1: ...arm Doublegate Lane Wickford Essex SS11 8UD FLAME VIEW ST1 GAS STOVE THIS APPLIANCE IS CATEGORY I2H FOR USE WITH NATURAL GAS AT A SUPPLY PRESSURE OF 20 mbar G B INSTALLATION SERVICING BOOK THIS MANUAL...

Страница 2: ...TABILITY 3 4 2 0 INSTALLATION 5 2 1 HEARTH 5 2 2 SITING 5 2 3 FLUE CONNECTION 5 2 4 VENTILATION 5 2 5 GAS CONNECTION 6 2 6 FUEL FITTING 7 8 2 7 OPERATING INSTRUCTIONS 9 10 11 12 2 8 SPILLAGE 13 2 9 CU...

Страница 3: ...a competent person installs all gas appliances i e a gas registered installer in accordance with the current edition of the gas safety installation and use regulations or the rules in force Failure to...

Страница 4: ...he inside of the chimney flue is in good condition along its length and check that there is no leakage of smoke through the structure of the chimney flue during and after the smoke pellet test 5 Using...

Страница 5: ...be fitted for protection of young children or elderly or infirm persons The door must be opened to remove the glass allow to cool before removing this as it will become very hot and is a working surfa...

Страница 6: ...dance with national regulations in the UK purpose provided ventilation is not normally required BS5871 part 1 and in IE IS813 IE only 2 5 GAS CONNECTION The gas connection can be made by removing the...

Страница 7: ...ut the type or number of logs Completely fill the burner with the mica supplied Ensure if any spills into pilot it is removed Do not use appliance without the mica in the burner Rear log sits as shown...

Страница 8: ...shown to left Branch log sits on front log and rear log as shown on left Final log sits on front log and Small amounts of glowing flames come up show with X on picture left small Chipping s can cover...

Страница 9: ...9 2 7 OPERATING INSTRUCTIONS Below the gas controls which are situated at the bottom left of the appliance Below remote control handset...

Страница 10: ...et The handset also has batteries as shown below It is important that the batteries are replaced at least every 12 months The meaning s of the red indicator on valve and handset Red indicator Meaning...

Страница 11: ...ote This button press must be done with 1 second of the red light coming on If not done quickly enough then the above must be repeated until done correctly When done correctly you will hear an audible...

Страница 12: ...ower symbol button and release immediately when the word pilot comes on to the display at the bottom left as shown about 1 2 seconds The stove will light NOTE Releasing too soon or too long after the...

Страница 13: ...uel pieces are added and only authorised spares are used 3 0 SERVICING INSTRUCTIONS The stove is fitted with a spillage monitoring system consisting of a thermal switch this system is not adjustable a...

Страница 14: ...aling and contact with skin or eyes Use disposable gloves facemasks and eye protection After handling wash hands and other exposed parts If a vacuum is used for cleaning any ceramic fuel bed parts inc...

Отзывы: