Figure 5: Recommended Boiler Piping for Zoning with Valves
D
.
Install Drain Valve in return piping.
See Figure 5.
E.
Oil, grease, and other foreign materials
which
accumulate in new hot water boilers and a new or
reworked system should be boiled out, and then
thoroughly fl ushed. A qualifi ed water treatment
chemical specialist should be consulted for
recommendations regarding appropriate chemical
compounds and concentrations which are compatible
with local environmental regulations.
F
. After the boiler and system have been cleaned and
fl ushed,
and before refi lling the entire system add
appropriate water treatment chemicals, if necessary, to
bring the pH between 7 and 11.
G.
Fill entire heating system with water
and vent air
from system. Use the following procedure on a Series
Loop System equipped with zone valves. (See Figure
5).
1. Close isolation valve in boiler supply piping.
2. Isolate all circuits by closing zone valves or
balancing valves.
3. Attach a hose to hose bib located just below
isolation valve in boiler supply piping. (Note
- Terminate hose in fi ve gallon bucket at a suitable
fl oor drain or outdoor area).
4. Starting with one circuit, open zone valve.
5. Open hose bib.
6. Open fi ll valve (Make-up water line should be
located directly above isolation valve in boiler
supply piping).
7. Allow water to overfl ow from bucket until discharge
from hose is bubble free for 30 seconds.
8. Open zone valve to the second zone to be purged,
then close the fi rst. Repeat this step until all zones
have been purged, but always have one zone open.
At completion, open all zone valves.
9. Close hose bib, continue fi lling the system until
the pressure gauge reads 12 psi. Close fi ll valve.
(Note - If make-up water line is equipped with
pressure reducing valve, system will automatically
fi ll to 12 psi.
10. Open isolation valve in boiler supply piping.
11. Remove hose from hose bib.
Содержание microTEKDV
Страница 14: ...14 Figure 10 Vent Installation Figure 11 Vent Connector Un Assembled ...
Страница 15: ...15 Figure 13 Air Intake Installation Figure 12 Vent Connector Assembled ...
Страница 19: ...19 Figure 15 Schematic Wiring Diagram ...
Страница 30: ...30 Figure 20 microTEKDV Boiler Jacket Insulation ...
Страница 31: ...31 Figure 21 microTEKDV Bare Boiler Assembly ...
Страница 32: ...32 Figure 22 Vent Kit Repair Parts ...