30
110772-01 - 5/20
CL
Installation & Service Manual
A. CLEAN THE FLUEWAYS (See Figure 11-1).
1. Prior to cleaning boiler, lay a protective cloth
or plastic over combustion chamber blanket
to collect debris falling from flueways. Several
models
DO NOT
utilize a combustion chamber
blanket, see Section XIV, Repair Parts, Item 1
Bare Boiler Assembly for details.
2. For access to combustion chamber remove
two (2) 5/16" - 18 cap screws, one on the right
(1¼" long) and one on the left (3¼" long). If
boiler is equipped with flexible fuel line(s),
swing door open.
3. For cleaning from the top:
a. Remove as much vent pipe as necessary
to allow removal of the jacket top panel and
canopy.
b. Remove the jacket top panel.
c. Remove the canopy, being careful not to
damage the gasket.
4. Using a 1¼” diameter wire or fibre bristle brush
(30” handle) clean the flueways. Brush from the
top and/or side using horizontal and diagonal
strokes for best results.
DO NOT
allow brush to
strike the target wall or liner in the chamber.
B. CLEAN TOP OF BOILER SECTIONS
Brush and vacuum the tops of the boiler sections.
C. CLEAN THE COMBUSTION CHAMBER.
Using wire or fibre bristle brush, clean crown of
boiler and inside of water legs.
WARNING
DO NOT allow brush to strike target wall or
blanket in the combustion chamber.
D. AFTER CLEANING,
remove protective cloth or
plastic with debris and vacuum as necessary, but
be careful not to damage blanket. Inspect target
wall, combustion chamber blanket, burner swing
door insulation, and rope gasket for signs of
damage. If damaged, replace as needed.
E. REASSEMBLE BOILER.
CAUTION
DO NOT start the burner unless canopy, vent
pipe, burner swing door and all flue cover
plates are secured in place.
1. Install the canopy taking care to align the
gasket without blocking the flueways. If gasket
is damaged, replace as needed.
2. Reinstall jacket top panel with #8 x ½" long
sheet metal screws.
3. Reinstall vent pipe on canopy and secure to
collar with sheet metal screws.
4. Close burner swing door. Secure door to front
section with 5/16" flange nut and washer (right
side) and 5/16" x 3½" lg. bolt (left side).
NOTICE
When securing burner swing door make sure
door is drawn-in equally on both sides.
Tighten swing door hardware to provide
adequate seal to rope gasket around perimeter
of door.
Use an alternating tightening method from right
side flange nut to left side cap screw to pull
door tight equally.
11
Boiler Cleaning
WARNING
All boiler cleaning must be completed with burner service switch turned off. Boilers equipped with burner
swing door have a potential hazard which can cause severe property damage, personal injury or loss of
life if ignored. Before opening swing door, turn off service switch to boiler to prevent accidental firing of
burner outside the combustion chamber. Be sure to tighten swing door fastener completely when service is
completed.
!
!
!