INSTRUCTION FOR REPAIRING APPLIANCES CONTAINING R 290

AUTHORISED PERSONS ONLY!

    Oxygen free nitrogen (OFN) shall then be purged through the system both before and during the 
    brazing process.

15. Removal and evacuation
    

When breaking into the refrigerant circuit to make repairs – or for any other purpose – conventional 

    procedures shall be used. However, it is important that the best practise is followed since 
    flammability is a consideration. The following procedure shall be adhered to:
          - remove refrigerant;
          - purge the circuit with inert gas;
          - evacuate;
          - purge again with inert gas;
          - open the circuit by cutting or brazing.
    The refrigerant charge shall be recovered into the correct recovery cylinders. The system shall be 
    “flushed” with OFN to render the unit safe. This process may need to be repeated several times. 
    Compressed air or oxygen shall not be used for this task. Flushing shall be achieved by breaking 
    the vacuum in the system with OFN and continuing to fill until the working pressure is achieved, 
    then venting to atmosphere, and finally pulling down to a vacuum. This process shall be repeated 
    until no refrigerant is within the system. When the final OFN charge is used, the system shall be 
    vented down to atmospheric pressure to enable work to take place. This operation is absolutely vital 
    if brazing operations on the pipe-work are to take place. Ensure that the outlet for the vacuum pump 
    is not close to any ignition sources and there is ventilation available. 

16. Charging procedures
    

In addition to conventional charging procedures, the following requirements shall be followed:

          - Ensure that contamination of different refrigerants does not occur when using charging 
            equipment. Hoses or lines shall be as short as possible to minimise the amount of refrigerant 
            contained in them.
          - Cylinders shall be kept upright.
          - Ensure that the refrigeration system is earthed prior to charging the system with refrigerant.
          - Label the system when charging is complete (if not already).
          - Extreme care shall be taken to not overfill the refrigerant system.
    Prior to recharging the system it shall be pressure tested with OFN. The system shall be leak tested 
    on completion of charging but prior to commissioning. A follow up leak test shall be carried out prior 
    to leaving the site.

17. Decommissioning 
    

Before carrying out this procedure, it is essential that the technician is completely familiar with the 

    equipment and all its details. It is recommended good practice that all refrigerants are recovered 
    safely. Prior to the task being carried out, an oil and refrigerant sample shall be taken in case 
    analysis is required prior to re-use of reclaimed refrigerant. It is essential that electrical power is 
    available before the task is commenced.
        a) Become familiar with the equipment and its operation.
        b) Isolate system electrically.
        c) Before attempting the procedure ensure that:
          - Mechanical handling equipment is available, if required, for handling refrigerant cylinders;
          - All personal protective equipment is available and being used correctly;
          - The recovery process is supervised at all time by a competent person.
          - Recovery equipment and cylinder confirm to the appropriate standards.
        d) Pump down refrigerant system, if possible.
        e) If a vacuum is not possible, make a manifold so that the refrigerant can be removed from 
            various parts of the system.

12

Содержание ausclimate WDH-070EBP

Страница 1: ...NG 2 3 CAUTIONS 4 5 DESCRIPTION OF COMPONENTS FUNCTION EXPLANATION 6 OPERATING INSTRUCTIONS 7 CONTINUOUS DRAINAGE OPTIONS 8 MAINTENANCE EMERGENCY 9 R290 AUTHORISED REPAIRER INSTRUCTIONS 10 13 SPECIFIC...

Страница 2: ...nimum of once every two weeks Do not place the appliance near any heating appliance The appliance should be transported upright Any internal water should be emptied before transporting Do not turn the...

Страница 3: ...erating electrical heater A surface area greater than 9 m is necessary for the installation use and storage of the appliance Do not pierce or burn the appliance Do not perforate any of the components...

Страница 4: ...wer plug If the power cord on this unit is damaged it must be replaced by the manufacturer it s service agent or qualified persons in order to avoid a hazard CAUTIONS CAUTIONS Do not place anything on...

Страница 5: ...parts or start a fire Do not place the machine on uneven ground This may cause shaking noise and leakage of water It is dangerous to put anything into the machine Keep the machine away from any type o...

Страница 6: ...after displaying the timer the display will change back to current room temperature On Off POWER FAN SPEED High Low TIMER To operate press TIMER select hours the unit will turn off after set hours Wh...

Страница 7: ...ket Full light may illuminate if so pull out the water tank check the float lever is able to move freely then return the water tank to the correct position When the water tank is full the indication l...

Страница 8: ...may choose this method to allow the water to bypass the water tank and flow directly from the dehumidifier via a drain hose or pump out drain hose The following steps are useful when there are good c...

Страница 9: ...mpurities from the air which may hinder the dehumidifying function these should be regularly cleaned The filter is located behind the front grill and can be accessed after removal cleaner or wash it w...

Страница 10: ...f fire or explosion All possible ignition sources including cigarette smoking should be kept sufficiently far away from the site of installation repairing removing and disposal during which flammable...

Страница 11: ...ipment in use Intrinsically safe components are the only types that can be worked on while live in the presence of a flammable atmosphere The test apparatus shall be at the correct rating Replace comp...

Страница 12: ...s shall be followed Ensure that contamination of different refrigerants does not occur when using charging equipment Hoses or lines shall be as short as possible to minimise the amount of refrigerant...

Страница 13: ...good working order with a set of instructions concerning the equipment that is at hand and shall be suitable for the recovery of flammable refrigerants In addition a set of calibrated weighing scales...

Страница 14: ...posed of with household waste Please recycle where facilities exist Check your local authority of retailer for recycling advice SPECIFICATIONS 14 TUV approval Certificate No TUV 025166 EA WDH 070EBP 7...

Отзывы: