IP POWER 9212 USER MANUAL
Source mode ( Voltage input) :
IN1-IN4 contacts are active signal sensor. If the voltage difference between the two contacts in one set
within 0V~3V, 9212 shows ON. It the voltage difference within 4V~24V, 9212 shows OFF. So user can
detect the change of equipment. Such as smoke detector, light detector and gas detector.
NOTE
:
1. The data in this figure is the average measure
value. To ensure the correct detection, we suggest
user set the voltage lower than 3V when it shows
OFF and higher than 4V when it shows ON
2. The maximum measure voltage is 24V.
.
Slink mode (Resistance Input ) :
IN5-IN8 contacts are short circuit sensor. If the resistance between the two contacts in one set within
0
Ω
~200
Ω
, 9212 shows ON. If the resistance within 500
Ω
~
∞
,
9212 shows OFF. So user can detect the
movement of equipment through the magnetic reed switch or other kind of reactive sensors.
NOTE
:
1. The data in this figure is the average measure
value. To ensure the correct detection, we suggest
user set the voltage lower than 200
Ω
when it shows
ON and higher than 500
Ω
when it shows OFF.
2. When measure the resistance of web contacts, the
maximum voltage is 5V and the maximum currency
is no more than 10mA
。
PS:
magnetic reed switch: using the magnetic field of the magnet to produce a signal when there is a
movement happened in switch. Low cost and easy to use is the chief characteristic of magnetic reed switch.
Most of them are used in security equipment, living product and automatic mechanism.
9202 Pro Hardware connection (recommend)
IP Power 9202 Pro offers 4 sets of NC(Normal Close ) – Out 1
-
Out 4
4 sets of NO (Normal Open ) –Out 5
-
Out 8.
Maximum Rated Voltage: 240V/AC, 60V/DC
Maximum Rated Currency: 12A AC/DC
Maximum Switch time: Max 10ms
Environment Temperature: -30°C~ + 55°C
NOTICE: Only the professionals should operate the following operations in this section and the
common user DO NOT try it!
For example—Light ball
1 Use the electrical wire of the equipment
:
VER. X.X,
- 9 -