ADM-S and ADM-D land call module
Terminalassignmentandconfiguration
4
ADMmanual
2.2.3 Terminal strip
ADM-S X3
ADM-D X3
ADM-S
function / programming
ADM-D
function / programming
Technical data
1
+ 24 V
+ 24 V
P
2
Landing call UP
Landing call UP
I/O; L; 350 mA / 24 V
3
Landing call DOWN
Landing call DOWN
I/O; L; 350 mA / 24 V
4
Landing call release
Landing call release
O; L; 350 mA / 24 V
5
+ 24 V
+ 24 V
P
6
Out-of-order, occupied display,
special drive
Occupied display, left
O; L; 350 mA / 24 V
7
Chime, floor position 5
Chime left, special drive
O; L; 350 mA / 24 V
8
Direction UP
Direction UP left
O; L; 350 mA / 24 V
9
Direction DOWN
Direction DOWN left
O; L; 350 mA / 24 V
10
GND
GND
P
11
GND
GND
P
12
Key switch 1:
fire recall, fire recall selective, fire
recall reset, landing prio, landing
prio selective, landing prio super,
remote shutdown, remote shut-
down selective, smoke alarm, soft
switch
Key switch 1:
fire recall, fire recall selective, fire
recall reset, landing prio, landing
prio selective, landing prio super,
remote shutdown, remote shut-
down selective, smoke alarm, soft
switch
I; L
13
Key switch 2:
fire recall, fire recall selective, fire
recall reset, landing prio, landing
prio selective, landing prio super,
remote shutdown, remote shut-
down selective, smoke alarm, soft
switch
Key switch 2:
fire recall, fire recall selective, fire
recall reset, landing prio, landing
prio selective, landing prio super,
remote shutdown, remote shut-
down selective, smoke alarm, soft
switch
I; L
14
Floor position 4, landing prio
display, soft output 0, soft output 1,
acoustic click
Landing prio display, acoustic click O; L; 350 mA / 24 V
15
+ 24 V
+ 24 V
P
16
Floor position bit 0
Direction DOWN right
O; L; 350 mA / 24 V
17
Floor position bit 1
Direction UP right
O; L; 350 mA / 24 V
18
Floor position bit 3
Occupied display, right
O; L; 350 mA / 24 V
19
Floor position bit 2
Chime right, special drive
O; L; 350 mA / 24 V
20
GND
GND
P
The values in the table correspond to the factory settings. Other I/O functions can be set using the software and
can thus deviate from the table. More detailed information can be found in the FST Installation and Commissio-
ning manual. The functions configured for you can be found in your system-specific wiring diagrams.
Terminals for which several functions are listed can be set with one of them at the factory. The "Direction" func-
tion can be configured in the FST menu as a direction of travel output or a travel continuation output.
The terminals labelled with key switches 1 and 2 can be set at the factory with the functions fire recall, smoke
alarm, remote shutdown and priority landing.
Other I/O functions can be set using the software.
LED
LED
Colour
State
Description
LD1
yellow
briefly flashes after switched on
ADM ready
flashing or permanently illuminated
hardware error