19
P6
Thermostat temperature difference
0
℃
~5
℃
2
P7
Electric heater starts time
1~120 minutes
15
P8
Electric heater starts ambient
temperature setting value
-20~20
℃
0
P9
Accumulated defrost time setting
1~120 minutes
45
P10
The heating mode enter into the
defrost ambient temperature
1
~
25
℃
15
P11
Start defrost of the ambient
temperature and coil temperature
difference
1
~
25
℃
3
P12
Enter the defrost coil temperature
-20~20
℃
-3
P13
The heating exit defrost temperature
1
~
25
℃
15
P14
The maximum defrost time
1
~
25
℃
10
P15
Heating and cooling mode water
pump operation mode
0,1,2
1
0=stop running
1=timer running
2=always running
P16
Heating and cooling mode water
pump operation interval time
0
~
25minutes
5
P17
Outdoor fan corresponding to the
ambient temperature set value
0~35
℃
28
reserve
P18
The maximum operating frequency
of the inverter compressor
50~100Hz
100
reserve
P19
Electronic expansion valve
maximum opening
250~480pulse
480
reserve
P20
Electronic expansion valve minimum
opening
60~250pulse
60
reserve
P21
Compressor manual frequency
10~100Hz
50
manual only
P22
Electronic expansion valve manual
opening
60~480pulse
350
manual only
P23
Compressor frequency adjustment
mode
0,1
0
0=automatic
1=manual
P24
Electronic expansion valve
adjustment mode
0,1
0
0=automatic
1=manual
P25
Linkage switch
0,1
0
0=Invalid
1=valid
P26
reserve
P27
reserve
P28
reserve