background image

        SECTION VI VENTED 

(1) 

This appliance must be installed only in a solid-fuel burning fireplace with a working 

flue 

and constructed of non-combustible materials. 

(2)  A minimum of 25.7 sq. in. (Min. 6” chimney) or see page 24, permanent flue opening       must be 

provided by either the fireplace chimney or chimney damper to vent the flue gases. 

(3)  Obtain a Damper Flap Lock from your dealer or manufacture. Adjust the Lock on the side of the 

damper flap in position to maintain a permanent opening of 25.7 sq. in. and lock in place. 

(4) 

Solid fuels shall not be burned in a fireplace where a decorative appliance is installed.

 

(5)  Any chimney damper must be fixed in a manner which will maintain the minimum permanent vent 

opening at all times. 

NOTE: 

See chart on page 24. 

(6)  Periodic cleaning of the venting system of a solid fuel burning fireplace should be done by a quali-

fied agency. Clean once a year. 

Periodic examination and cleaning of the venting system of a solid fuel burning fireplace should be done 
once a year. 

MINIMUM FIREPLACE DIMENSIONS FOR CR8T LOG SET MANUFACTURED BY NEW 
BUCK CORPORATION FOR SOLID FUEL BURNING FIREPLACE OR MASONRY FIRE-
PLACE AND PREFAB OR MANUFACTURED FIREPLACES.

 

 

MODEL    HEIGHT OF    WIDTH OF     WIDTH AT        DEPTH OF  
                   OPENING          OPENING       REAR                FIREPLACE 
                                               AT FRONT                                                                  

CR8T          

  17”                       24”                  18”                        10”                                              

FIGURE 8 

DAMPER FLAP 
LOCK 

DAMPER 
FLAP 

 

23

Содержание CR8T

Страница 1: ...l the fire department Installation and service must be performed by a qualified installer service agency or the gas supplier Save this manual for future reference This is an unvented and vented gas fi...

Страница 2: ......

Страница 3: ...e Check 13 Heat Output 13 SECTION III Installation Heat Shield 14 Wiring Diagram 16 SECTION IV Installation After Market Mobile Home 18 SECTION V Producing Adequate Ventilation 18 Ventilation Air From...

Страница 4: ......

Страница 5: ...ision for combustion and ventilation air must conform with local codes or in the absence of local codes with the National Fuel Gas Codes AN SIZ223 1 NFPA54 3 This appliance may be installed in an Afte...

Страница 6: ...s will remain hot for some time after shutdown Allow surface to cool before touching 10 Never place any objects on these gas logs 11 These gas logs MUST NOT BE USED with glass doors in a closed positi...

Страница 7: ...off valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of 1 2 psi 3 5 kPa 25 The appliance must be isolated from the ga...

Страница 8: ...s planned Ensure that front of the logs sit inside the edge of the fireplace NOTE IF THE EXISTING FIREPLACE IE EQUIPPED WITH A SCREEN IT MUST BE IN PLACE WHEN THE APPLIANCE IS OPERATING THE SCREEN SHA...

Страница 9: ...e fireplace opening 3 Mantel Clearance Clearances from top of heater to mantel or mantel supports See Figure 1 4 Front Clearances No objects should be placed within 24 from the front of the fireplace...

Страница 10: ...ons containing the Burner Base and the Logs Inside one of the cartons you will find the Burner Base The Logs are boxed separately CR8T 1 REAR LOG 2 FRONT LOG 3 LEFT TOP LOG WARNING POSITIONING OF LOGS...

Страница 11: ...efer to PREPARING LOG KIT page 6 Figure 2 WARNING Failure to position the parts in accordance with these diagrams or failure to use only parts specifically approved with this heater may result in prop...

Страница 12: ...than 1 2 psi 3 5 kPa MODEL CR8T Gas Natural Propane LP Maximum Heat Input 27 000 27 000 Minimum Heat Input 11 000 11 000 Gas Inlet Pressure Maximum 10 5 ins W C 13 0 ins W C Minimum 5 ins W C 11 ins W...

Страница 13: ...hbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call your local fire department C Use only your hand to push in or turn the gas control knob Never use tools I...

Страница 14: ...in front of the rear log Fully open the man ual shut off valve 9 Turn control knob counterclockwise to the PILOT position Press in control knob for 15 fifteen seconds see figure 3 10 With control knob...

Страница 15: ...base for access to control knobs 2 Turn control knob clockwise to the PILOT position 2 Close access panel door CAUTION Hot while in operation Do Not Touch Keep children clothing furniture gasoline an...

Страница 16: ...etermine your personal comfort levels MANUAL LIGHTING PROCEDURE 1 If the pilot cannot be ignited with the ignitor on the control valve it can be manually lit with the use of a paper match and a lighte...

Страница 17: ...the room can be controlled by the position of the flue damper when used as Vented Gas Logs See Section VI Vented Models The gas logs may be used as non vented gas logs only where permitted by local s...

Страница 18: ...provided fasten the Heat Shield to the floor of the fireplace On each side of floor frame of the Heat Shield base there is a go through hole Position the Heat Shield as described above Mark the hole...

Страница 19: ...L 19HS Always include correct name part number and model number when ordering service Parts KEYS PART DESCRIPTION PART NUMBER 1 BLOWER PEA2 40 01 RATING 120volts 60HZ 54Amps 2 110 THERMOSTAT PE400132...

Страница 20: ...riginal wire supplied with the appliance must be replaced it must be replaced with a wire of at least a 105o C temperature rating NOTE Installation and repair should be done by a qualified service per...

Страница 21: ...UR PROTECTION AGAINST SHOCK HAZARD AND SHOULD BE PLUGGED DIRECTLY INTO A PROPERLY GROUNDED THREE PRONG RECEPTACLE WARNING DO NOT USE A BLOWER INSERT HEAT EXCHANGER INSERT OR OTHER ACCESSORIES NOT APPR...

Страница 22: ...ing of all appliances installed in that space Rooms communicating directly with the space in which the appliances are installed through openings not furnished with doors are considered a part of the u...

Страница 23: ...20 ft length x 16 ft width x 8 ft ceiling Height 2560 cu ft volume of space If additional ventilation to adjoining room is supplied with grills or openings add the volume of these rooms to the total v...

Страница 24: ...ctual BTU Hr used is more than the maximum BTU Hr the space can support You must provide additional fresh air Your options are as follows A Rework worksheet adding the space of an adjoining room If th...

Страница 25: ...ption 3 Figure 6 WARNING REWORK WORKSHEET ADDING THE SPACE OF THE ADJOINING UNCONFINED SPACE THE COMBINED SPACES MUST HAVE ENOUGH FRESH AIR TO SUPPLY ALL APPLIANCES IN BOTH SPACES NOTE Each opening sh...

Страница 26: ...Ventilation for required size of ventilation grills or ducts IMPORTANT Do not provide openings for inlet air into attic if attic has a thermostat controlled power vent Heated air entering the attic w...

Страница 27: ...ace where a decorative appliance is installed 5 Any chimney damper must be fixed in a manner which will maintain the minimum permanent vent opening at all times NOTE See chart on page 24 6 Periodic cl...

Страница 28: ...GAS PRESSURE CHECK page 8 8 See OPERATING INSTRUCTIONS pages 9 12 9 See BURNER PILOT FLAME CHECK for proper flame pattern page 13 10 See CLEANING INSTRUCTIONS page 13 25 NOTE Visually check the pilot...

Страница 29: ...HEATER BE SURE TO READ THE ABOVE SECTION ON IMPORTANT SAFEGUARDS All cleaning should be carried out when the heater is cold Only limited cleaning will be required under normal use Dusting the front o...

Страница 30: ...not 3 Reconnect igniter cable connected to igniter cable 4 Igniter cable pinched or wet 4 Free igniter cable if pinched by any metal or tubing Keep igniter cable dry 5 Broken igniter cable 5 Replace p...

Страница 31: ...S PILOT lights keep long enough control knob pressed in 30 seconds 3 Safety interlock system has 3 Wait 1 minute for safety been triggered if equipped interlock system to reset 4 Manual shutoff valve...

Страница 32: ...ed and Maintenance or replace burner 2 Burner damaged 2 Replace burner 3 Gas regulator defective 3 Replace gas regulator Slight smoke or odor during 1 Residues from manu 1 Problem will stop after a in...

Страница 33: ...is common with noise just after burner is lit or shut or contracts while cooling most heaters If noise is off excessive contact a qualified service person Heater produces unwanted odors 1 Heater burn...

Страница 34: ...WARNING 2 Locate and correct all statement at top of previous leaks see Checking page Gas Connections OPTIONAL PARTS NOT PROVIDED WITH CR8T LOG SET PART DESCRIPTION MAPSFPC CANOPY HOOD MA19HS 19HS HEA...

Страница 35: ...opreci ODS Nat Pilot 1 5A PE 2150054 Copreci ODS LP Pilot 1 6 PE RV12LF30 PILOT Regulator Nat 1 6A PE RV12LF90 PILOT Regulator LP 1 7 RF 14ALMTUB 1 4 Aluminum Tubing 1 8 PH 1166 3 8 Street Elbow 1 9 P...

Страница 36: ...1 1A 2 11 4 3 5 5A 6 6A 7 8 9 10 12 13 FIGURE 9 32...

Страница 37: ...r Support 3 Air Adjustment Shutter 4 Access Door 5 Front Log Support 6 Rear Log Holder 7 Igniter Control And Pilot Control 8 Flame Adjustment Control 9 Mertik Valve 10 Left Burner Support 11 Burner 12...

Страница 38: ...s this war ranty The heater MUST be installed by a qualified installer in accordance with all local codes and instructions furnished with the unit This warranty does not apply to parts that are not in...

Страница 39: ...xclusion or limitation of incidental or consequential damages so the previous limitation on implied warranties or exclusion or limitation on damages may not apply to you This warranty gives you specif...

Отзывы: