SECTION VI VENTED
(1)
This appliance must be installed only in a solid-fuel burning fireplace with a working
flue
and constructed of non-combustible materials.
(2) A minimum of 25.7 sq. in. (Min. 6” chimney) or see page 24, permanent flue opening must be
provided by either the fireplace chimney or chimney damper to vent the flue gases.
(3) Obtain a Damper Flap Lock from your dealer or manufacture. Adjust the Lock on the side of the
damper flap in position to maintain a permanent opening of 25.7 sq. in. and lock in place.
(4)
Solid fuels shall not be burned in a fireplace where a decorative appliance is installed.
(5) Any chimney damper must be fixed in a manner which will maintain the minimum permanent vent
opening at all times.
NOTE:
See chart on page 24.
(6) Periodic cleaning of the venting system of a solid fuel burning fireplace should be done by a quali-
fied agency. Clean once a year.
Periodic examination and cleaning of the venting system of a solid fuel burning fireplace should be done
once a year.
MINIMUM FIREPLACE DIMENSIONS FOR CR8T LOG SET MANUFACTURED BY NEW
BUCK CORPORATION FOR SOLID FUEL BURNING FIREPLACE OR MASONRY FIRE-
PLACE AND PREFAB OR MANUFACTURED FIREPLACES.
MODEL HEIGHT OF WIDTH OF WIDTH AT DEPTH OF
OPENING OPENING REAR FIREPLACE
AT FRONT
CR8T
17” 24” 18” 10”
FIGURE 8
DAMPER FLAP
LOCK
DAMPER
FLAP
23
Содержание CR8T
Страница 2: ......
Страница 4: ......
Страница 36: ...1 1A 2 11 4 3 5 5A 6 6A 7 8 9 10 12 13 FIGURE 9 32...