NX-507E / NX-508E AUXILIARY MODULES 

 

Segment 2 Selects the following partitions:

 

LED 1 - "On" if the event should activate when it occurs in Partition 1. 

LED 2 - "On" if the event should activate when it occurs in Partition 2. 

LED 3 - "On" if the event should activate when it occurs in Partition 3. 

LED 4 - "On" if the event should activate when it occurs in Partition 4. 

LED 5 - "On" if the event should activate when it occurs in Partition 5. 

LED 6 - "On" if the event should activate when it occurs in Partition 6. 

LED 7 - "On" if the event should activate when it occurs in Partition 7. 

LED 8 - "On" if the event should activate when it occurs in Partition 8. 

 

Location 2 

Enabling the Schedules for Output 1 

(1 segment of binary data)  Location 2 is used to enable any or all of the eight (8) schedules.  LED 1 corresponds 

to Schedule 1 (see locations 32-34, page 10) and LED 8 corresponds to Schedule 8 (see locations 53-55, page 11). 

This location can be used in conjunction with the Special Function location to create an output that will only 

activate during certain times and/or certain days. 

 

LED 1 - "On" if the event should follow Schedule 1. 

LED 2 - "On" if the event should follow Schedule 2. 

LED 3 - "On" if the event should follow Schedule 3. 

LED 4 - "On" if the event should follow Schedule 4. 

LED 5 - "On" if the event should follow Schedule 5. 

LED 6 - "On" if the event should follow Schedule 6. 

LED 7 - "On" if the event should follow Schedule 7. 

LED 8 - "On" If the event should follow Schedule 8. 

 

Location 3 

Programming the X-10 Address for Output 1 

(2 segments of numerical data) 

 

Segment 1

 

Program a number from 0-15 to represent the corresponding X-10 

Module Number

 from the 

following table. 

 

 

Module 

 

 

 

 

 

 

 

 

 

 

10 

 

11 

 

12 

 

13 

 

14 

 

15 

 

16 

 

Seg 1 

 

 

 

 

 

 

 

 

 

 

 

10 

 

11 

 

12 

 

13 

 

14 

 

15 

 

Segment 2

 

Program a number from 0-15 to represent the corresponding X-10 

House code

 from the 

following table.  

 

X-10 ADDRESS CODES 

0=A 4=E  8=I 12=M 
1=B 5=F 9=J 13=N 
2=C 6=G 10=K 14=O 

3=D 7=H 11=L 15=P 

 

Locations 4 - 31  Programming For Outputs 2- 8  

 

Locations 4 - 31 are used to program the events, zones and times, as well as the special functions, partitions, 

schedules and X-10 addresses for Outputs 2 - 8.  Each output has four locations that are programmed with 

the same steps as Output 1 described previously.  Refer to Output 1 for specific instructions (locations 0 - 3, 

pages 9-10).   Also refer to the worksheets beginning on page 14. 

 

Location 32 

Programming the Opening Time for Schedule 1 

(2 segments of numerical data) 

 

Segment 1

 

Program the hour of the opening time in 24-hour format.  (1:00 PM = 13) 

Segment 2

 

Program the minutes after the hour of the opening time for Schedule 1. 

Содержание NX-507E

Страница 1: ...NetworX Series NX 507E RELAY EXPANDER NX 508E OUTPUT EXPANDER Installation and Startup...

Страница 2: ......

Страница 3: ...ERMINAL DESCRIPTION 5 IV NX 507E DRAWING 6 V NX 508E TERMINAL DESCRIPTION 7 VI NX 508E DRAWING 7 VII INSTALLING THE MODULES 8 VIII ENROLLING THE MODULES 8 IX PROGRAMMING THE MODULES 8 X PROGRAMMING LO...

Страница 4: ...inal see terminal descriptions making it ideal for use in a remote location NX 508E EIGHT OUTPUT EXPANDER Microprocessor controlled 8 output module Equipped with 8 low current trigger outputs see term...

Страница 5: ...rate from the power in the control panel AUX Any power drain from this terminal should be included in total current draw from the NetworX control panel or NX 320E Power Supply as applicable This allow...

Страница 6: ...6 NX 507E NX 508E AUXILIARY MODULES IV NX 507E DRAWING All outputs are Class 2 power limited...

Страница 7: ...om the power in the control panel AUX Any power drain from this terminal should be included in total current draw from the NetworX control panel or NX 320E as applicable This allows an isolation of th...

Страница 8: ...to program should be entered Next enter the address of the NX 508E you wish to program followed by refer to Table VII 1 on page 8 At this point the Armed LED will illuminate while it is waiting for a...

Страница 9: ...m Disarm Control 11 Duress 31 Closed Schedule 51 Follow schedule of NX 508E 12 Manual Fire 32 Listen In 52 Flash X 10 for Alarm Memory 13 Aux 2 Keypad 33 Line Seizure 53 Flash X 10 for Siren 14 Keypad...

Страница 10: ...ule 3 LED 4 On if the event should follow Schedule 4 LED 5 On if the event should follow Schedule 5 LED 6 On if the event should follow Schedule 6 LED 7 On if the event should follow Schedule 7 LED 8...

Страница 11: ...to a maximum of 8 holidays per location month Locations 57 67 Programming the Date of Holidays from February to December 8 segments of numerical data Locations 57 67 are used to program the day of eac...

Страница 12: ...g Users 161 170 egment 1 corresponds to user 161 Segment 10 corresponds to user 170 Location 85 Authorizing Users 171 180 Segment 1 corresponds to user 171 Segment 10 corresponds to user 180 Location...

Страница 13: ...e C and Unit Code 4 for 6 minutes when Zone 1 is faulted only from 5 00 p m to 9 00 a m program the following SEGMENT LOC 1 2 3 0 42 1 6 1 LED 1 2 3 4 5 6 7 8 2 1 2 3 4 5 6 7 8 3 3 2 32 9 0 33 17 0 34...

Страница 14: ...ition 7 8 Partition 8 Output 1 Schedule 2 10 1 Schedule 1 2 Schedule 2 3 Schedule 3 4 Schedule 4 5 Schedule 5 6 Schedule 6 7 Schedule 7 8 Schedule 8 3 Output 1 X 10 Address Segment 1 Module Number 0 1...

Страница 15: ...until a code is entered 3 Partition 3 3 On if output should reset if a code is entered while it is being timed 4 Partition 4 5 Partition 5 4 On if output should only trigger during a closed schedule...

Страница 16: ...2 House Code See chart on page 14 0 16 10 Output 5 Event Zone Time _ _ _ 43 5 10 Output 5 Special Functions Partition Segment 1 Segment 2 17 10 1 On if output should time in minutes Off if output tim...

Страница 17: ...1 Module Number 5 23 10 Segment 2 House Code See chart on page 14 0 24 10 Output 7 Event Zone Time _ _ _ 43 7 10 Output 7 Special Functions Partition Segment 1 Segment 2 25 10 1 On if output should ti...

Страница 18: ...should be logged in event buffer Output 8 Schedule 30 10 1 Schedule 1 5 Schedule 5 2 Schedule 2 6 Schedule 6 3 Schedule 3 7 Schedule 7 4 Schedule 4 8 Schedule 8 Output 8 X 10 Address Segment 1 Module...

Страница 19: ...3 Tuesday 7 Saturday 4 Wednesday 8 Disabled on holidays 50 11 Schedule 7 Opening Time 8 0 51 11 Schedule 7 Closing Time 20 0 Schedule 7 Days 52 11 5 Thursday 1 Sunday 2 Monday 6 Friday 3 Tuesday 7 Sat...

Страница 20: ...ut 1 Output 2 Output 3 Output 4 Output 5 Output 6 Output 7 Output 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2...

Страница 21: ...put 5 Output 6 Output 7 Output 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 CODES 7...

Страница 22: ...Output 6 Output 7 Output 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 80 12 CODES...

Страница 23: ...Output 6 Output 7 Output 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 85 12 CODES...

Страница 24: ...218 219 220 Output 1 Output 2 Output 3 Output 4 Output 5 Output 6 Output 7 Output 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2...

Страница 25: ...hole is for the screw Diagram 2 Place the first black plastic PCB guide in the top insertion point grooved edge downward The half moon protrusion will be in the large hole It does not require force In...

Страница 26: ...degrees F SHIPPING WEIGHT 1 lb COMPATIBLE NETWORX CONTROL PANELS NX 4 NX 6 NX 8 NX 8E NX 4V2 NX 6V2 NX 8V2 UNDERWRITERS LABORATORIES LISTINGS UL365 Police Station Connected Burglar Alarm Units System...

Отзывы: