NX-507E / NX-508E AUXILIARY MODULES

 

 

9

X. 

 PROGRAMMING 

LOCATIONS 

Location 0 

Programming the Event, Zone and Time for Output 1 

(3 segments of numerical data)  Location 0 is used to select the particular function, zone number, and time for 

an output to trip. 

 

 

Segment 1  (EVENT) 

 

Selects the event that will trigger the output.  See chart below for the specific

vents that can be selected

e

 

Segment 2 (ZONE/USER) 

 

Selects the zone or user number necessary to trigger an output.  If this location is

programmed as a zero, any zone or user will activate the output. (See also loc. 68,

age 

p

11)

 

 

Segment 3  (TIME) 

 

Selects the amount of time an output will remain activated when an output

triggers. If this location is programmed as a zero, the output will follow the 

particular event.

 

 

 # 

Event 

 # 

Event 

 # 

Event

 

0   

/

 

Burglary Alarm

 

20 

Entry or Exit 

40 

Box Tamper 

1   

/

 

Fire Alarm 

21 

Armed 

41 

Siren Tamper 

2   

/

 

24 Hour Alarm 

22 

Not Armed 

42 

Any Zone Faulted 

3   

/

 

Zone Trouble 

23 

Ready  

43   

/

Any Alarm 

4   

/

 

Zone Tamper 

24 

Not Ready 

44 

Keypad Beeping 

Burglary Siren 

25 

Fire 

45   

/

Code Entry 

Fire Siren 

26 

Fire Trouble 

46  

:

Key FOB Function 1 

Any Siren 

27 

Chime 

47  

:

Key FOB Function 2 

Zone Bypass 

28   

/

Expander Trouble 

48 

Auto Arm Control 

AC Failure 

29 

Dynamic Battery Test 

49 

Auto Disarm Control 

10 

System Low Battery 

30 

Open Schedule   

50 

Auto Arm & Disarm Control 

11  

/

 

Duress 

31 

Closed Schedule   

51 

Follow schedule of NX-508E 

12  

/

 

Manual Fire 

32 

Listen In 

52 

Flash X-10 for Alarm Memory 

13  

/

 

Aux 2 Keypad 

33 

Line Seizure 

53 

Flash X-10 for Siren 

14  

/

 

Keypad Panic 

34 

Failed to Communicate 

54 

Armed Away (Exit Expired) 

15 

Keypad Tamper 

35 

Telephone Line Fault 

55 

End Listen In (Integrated Only) 

16  

/

 

Automatic Test 

36 

Program Mode 

56 

Follow X-10 Command 

17 

Alarm Memory 

37 

Download 

57 

Armed Stay 

18 

Entry  

38 

Ground Fault 

 

 

19 

Exit 

39 

Over Current 

 

 

 

See loc. 52 & 53 in NX control panel 

 

/

  If set to follow condition, these events will be 1 second.

 

:

 

Events 46 & 47 require NX-408E, NX-416E, or NX-448E wireless receivers to operate. Events 48, 49, and 50 will arm 

or disarm the NX control panel at the open (disarm) or close (arm) time for the appropriate schedule.  See 
example 3 on page 13.

 

 
 

Location 1 

Programming Special Functions and Partitions for Output 1 

(2 segments of binary data) 

 

Segment 1 Selects the following special conditions:

 

Address 

Output 

24 1-8 
25 9-16 
26 17-24 
27 25-32 
28 33-40 
29 41-48 
30 49-56 
31 57-64 

LED 1 - "On" if output should time in minutes; "Off" if output times in seconds. 

LED 2 - "On" if output should latch until a code is entered. 

LED 3 - "On" if output should reset if a code is entered while it is being timed.  

LED 4 - "On" if output should only trigger during a closed schedule. 

LED 5 - "On" if output should only trigger during an open schedule. 

LED 6 - "On" if the output should be inverted. 

LED 7 - "On" if a trigger should be logged in the event buffer. See chart. 

 

Содержание NX-507E

Страница 1: ...NetworX Series NX 507E RELAY EXPANDER NX 508E OUTPUT EXPANDER Installation and Startup...

Страница 2: ......

Страница 3: ...ERMINAL DESCRIPTION 5 IV NX 507E DRAWING 6 V NX 508E TERMINAL DESCRIPTION 7 VI NX 508E DRAWING 7 VII INSTALLING THE MODULES 8 VIII ENROLLING THE MODULES 8 IX PROGRAMMING THE MODULES 8 X PROGRAMMING LO...

Страница 4: ...inal see terminal descriptions making it ideal for use in a remote location NX 508E EIGHT OUTPUT EXPANDER Microprocessor controlled 8 output module Equipped with 8 low current trigger outputs see term...

Страница 5: ...rate from the power in the control panel AUX Any power drain from this terminal should be included in total current draw from the NetworX control panel or NX 320E Power Supply as applicable This allow...

Страница 6: ...6 NX 507E NX 508E AUXILIARY MODULES IV NX 507E DRAWING All outputs are Class 2 power limited...

Страница 7: ...om the power in the control panel AUX Any power drain from this terminal should be included in total current draw from the NetworX control panel or NX 320E as applicable This allows an isolation of th...

Страница 8: ...to program should be entered Next enter the address of the NX 508E you wish to program followed by refer to Table VII 1 on page 8 At this point the Armed LED will illuminate while it is waiting for a...

Страница 9: ...m Disarm Control 11 Duress 31 Closed Schedule 51 Follow schedule of NX 508E 12 Manual Fire 32 Listen In 52 Flash X 10 for Alarm Memory 13 Aux 2 Keypad 33 Line Seizure 53 Flash X 10 for Siren 14 Keypad...

Страница 10: ...ule 3 LED 4 On if the event should follow Schedule 4 LED 5 On if the event should follow Schedule 5 LED 6 On if the event should follow Schedule 6 LED 7 On if the event should follow Schedule 7 LED 8...

Страница 11: ...to a maximum of 8 holidays per location month Locations 57 67 Programming the Date of Holidays from February to December 8 segments of numerical data Locations 57 67 are used to program the day of eac...

Страница 12: ...g Users 161 170 egment 1 corresponds to user 161 Segment 10 corresponds to user 170 Location 85 Authorizing Users 171 180 Segment 1 corresponds to user 171 Segment 10 corresponds to user 180 Location...

Страница 13: ...e C and Unit Code 4 for 6 minutes when Zone 1 is faulted only from 5 00 p m to 9 00 a m program the following SEGMENT LOC 1 2 3 0 42 1 6 1 LED 1 2 3 4 5 6 7 8 2 1 2 3 4 5 6 7 8 3 3 2 32 9 0 33 17 0 34...

Страница 14: ...ition 7 8 Partition 8 Output 1 Schedule 2 10 1 Schedule 1 2 Schedule 2 3 Schedule 3 4 Schedule 4 5 Schedule 5 6 Schedule 6 7 Schedule 7 8 Schedule 8 3 Output 1 X 10 Address Segment 1 Module Number 0 1...

Страница 15: ...until a code is entered 3 Partition 3 3 On if output should reset if a code is entered while it is being timed 4 Partition 4 5 Partition 5 4 On if output should only trigger during a closed schedule...

Страница 16: ...2 House Code See chart on page 14 0 16 10 Output 5 Event Zone Time _ _ _ 43 5 10 Output 5 Special Functions Partition Segment 1 Segment 2 17 10 1 On if output should time in minutes Off if output tim...

Страница 17: ...1 Module Number 5 23 10 Segment 2 House Code See chart on page 14 0 24 10 Output 7 Event Zone Time _ _ _ 43 7 10 Output 7 Special Functions Partition Segment 1 Segment 2 25 10 1 On if output should ti...

Страница 18: ...should be logged in event buffer Output 8 Schedule 30 10 1 Schedule 1 5 Schedule 5 2 Schedule 2 6 Schedule 6 3 Schedule 3 7 Schedule 7 4 Schedule 4 8 Schedule 8 Output 8 X 10 Address Segment 1 Module...

Страница 19: ...3 Tuesday 7 Saturday 4 Wednesday 8 Disabled on holidays 50 11 Schedule 7 Opening Time 8 0 51 11 Schedule 7 Closing Time 20 0 Schedule 7 Days 52 11 5 Thursday 1 Sunday 2 Monday 6 Friday 3 Tuesday 7 Sat...

Страница 20: ...ut 1 Output 2 Output 3 Output 4 Output 5 Output 6 Output 7 Output 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2...

Страница 21: ...put 5 Output 6 Output 7 Output 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 CODES 7...

Страница 22: ...Output 6 Output 7 Output 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 80 12 CODES...

Страница 23: ...Output 6 Output 7 Output 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 85 12 CODES...

Страница 24: ...218 219 220 Output 1 Output 2 Output 3 Output 4 Output 5 Output 6 Output 7 Output 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2...

Страница 25: ...hole is for the screw Diagram 2 Place the first black plastic PCB guide in the top insertion point grooved edge downward The half moon protrusion will be in the large hole It does not require force In...

Страница 26: ...degrees F SHIPPING WEIGHT 1 lb COMPATIBLE NETWORX CONTROL PANELS NX 4 NX 6 NX 8 NX 8E NX 4V2 NX 6V2 NX 8V2 UNDERWRITERS LABORATORIES LISTINGS UL365 Police Station Connected Burglar Alarm Units System...

Отзывы: