current is proportional to the temperature difference between the ambient temperature and 
the desired temperature within the laser package.  
 
If the ambient temperature is lower than the package temperature, the power dissipated will 
support the heating process of the device by increasing the ambient temperature. On the 
other hand, if the ambient temperature is much higher than the desired package temperature 
(about +22°C) it may cause the laser to malfunction. The current, which is proportional to the 
temperature difference, implies power dissipation and an increase of the ambient 
temperature. 
This increased ambient temperature will again increase the current through the Peltier 
element in order to lower the internal package temperature. The increased current will make 
more power dissipate thereby increasing the ambient temperature, and so on.  
 
To avoid this, proper ventilation of the DWDM-system is needed. A 40-channel system needs 
12RU-26ru of rack space. Additional rack space needed for ventilation is 1RU above and 
below each set of 4 flashlink frames (8RU). Receiver cards generate less heat than 
transmitter cards, and bidirectional cards decrease the number of cards in a 40-channel 
system. Please consult with Network Electronics before building a 40-channel system. 
 
Example with 6 flashlink frames, frame space utilisation depending on card types: 
 
1RU 

Fan, hot air exhaust 

6RU 

3x flashlink DWDM frames 

1RU 

Cold air intake 

2RU 

flashlink DWDM filter frame 

1RU 

Fan, hot air exhaust 

6RU 

3x flashlink DWDM frames 

1RU 

Cold air intake 

 
The operational temperature for the DWDM-system is 0°-40°C. 
 

 
  

network-electronics.com 

11 

Содержание Flashlink DWDM-40C

Страница 1: ...network electronics com 40 ch 100GHz Dense Wavelength Division Multiplexing System Rev 0 Flashlink User Manual DWDM 40C...

Страница 2: ...9 Fax 47 33 48 99 98 Email support network electronics com www network electronics com Support Phone 47 90 60 99 99 Revision history Current revision of this document is the uppermost in the table bel...

Страница 3: ...Connections 7 3 1 Connecting to the DWDM 40C 7 3 2 System design 7 4 Operation 8 4 1 Handling of optical fibers 8 4 2 Laser safety precautions 8 4 3 Connector cleaning 9 4 4 Power dissipation in the...

Страница 4: ...ltiplexed signals The modules are bidirectional so they work as both multiplexer and demultiplexer at the same time A DWDM 40C consists of one DWDM 40C A and one DWDM 40C B which when used together pr...

Страница 5: ...ched pair including connectors 6dB max Channel Spacing 100GHz Passband ITU 12 5GHz Adjacent Channel Isolation 25dB min 28dB typ Non Adjacent Channel Isolation 40dB min Directivity 45dB min Thermal Wav...

Страница 6: ...9 48 194 80 1538 98 47 194 70 1539 77 46 194 60 1540 56 45 194 50 1541 35 Blue wavelengths 44 194 40 1542 14 43 194 30 1542 94 42 194 20 1543 73 41 194 10 1544 53 40 194 00 1545 32 39 193 90 1546 12 3...

Страница 7: ...ure 3 1 The backplane for the 40 channel DWDM system optical filter endpoint A 3 2 System design The maximum insertion loss for any channel in end point A is 4 0dB but the same channel in the compleme...

Страница 8: ...adius This means that any bending of the fiber corresponding to a bend radius less than the given value will make the light leak out of the fiber A typical value is 20 mm to 40 mm Telcordia standard f...

Страница 9: ...ied as Class 1 laser product according to EN 60 825 1 94 A11 96 and CFR Ch1 1997 Part 1040 10 If the front panel is removed the FR 2RU 10 2 is classified as Class 1 laser product according to EN 60 82...

Страница 10: ...aser wavelength will drift with changing temperature if the laser is not controlled This means that the internal temperature of the laser must be kept at a constant level for all operation temperature...

Страница 11: ...lower the internal package temperature The increased current will make more power dissipate thereby increasing the ambient temperature and so on To avoid this proper ventilation of the DWDM system is...

Страница 12: ...umidity range 90 non condensing 2 The equipment will operate without damage under the following environmental conditions Temperature range 5 C to 50 C Relative humidity range 95 non condensing 3 Elect...

Страница 13: ...d conditions for the product s covered by this manual follow the General Sales Conditions by Network Electronics ASA These conditions are available on the company web site of Network Electronics ASA w...

Отзывы: