Description
Device
CmdID
DeviceType
NetvoxPayLoadData
Off
R809A
0x90
0x0E
Reserved
(9Bytes,Fixed 0x00)
On
0x91
Reserved
(9Bytes,Fixed 0x00)
Toggle
0x92
Reserved
(9Bytes,Fixed 0x00)
ClearEnergy
0x93
Reserved
(9Bytes,Fixed 0x00)
ReadCurrentStatus
0x94
Reserved
(9Bytes,Fixed 0x00)
Config
ReportReq
0x01
MinTime
(2bytes Unit:s)
MaxTime
(2bytes Unit:s)
CurrentChange
(2byte
Unit:1mA)
PowerChange
(
2byte
Unit:1W
)
Reserved
(1Byte,Fixed
0x00)
Config
ReportRsp
0x81
Status
(0x00_success)
Reserved
(8Bytes,Fixed 0x00)
ReadConfig
ReportReq
0x02
Reserved
(9Bytes,Fixed 0x00)
ReadConfig
ReportRsp
0x82
MinTime
(2bytes Unit:s)
MaxTime
(2bytes Unit:s)
CurrentChange
(2byte
Unit:1mA)
PowerChange
(
2byte
Unit:1W
)
Reserved
(1Byte,Fixed
0x00)
(1)
Turn off the R809A switch button
Downlink: 900E000000000000000000
(2)
Turn on the R809A switch button
Downlink: 910E000000000000000000
(3)
Toggle turn on/off switch button
Downlink: 920E000000000000000000
(4)
Clear the historical electrical energy data
Downlink:930E000000000000000000
(5)
Setting Min Interval = 2 seconds,
Max Interval
= 300 seconds,
Current Change = 100mA,Power Change = 20W
Downlink:
010E0002012C0064001400
Response: 810E000000000000000000 (successful)
(6)
Read the current report interval
Downlink:
020E000000000000000000
Response:
820E0002012C0064001400
Example for MinTime/MaxTime logic:
Example#1
based on MinTime = 1 Hour, MaxTime= 1 Hour,
PowerChange=2W
MaxTime MaxTime
(MinTime)
(MinTime)
0H 1H 2H
Note:
MaxTime=MinTime. Data will only be report according to MaxTime (MinTime) duration regardless PowerChange value.
Collects data
REPORTS 35W
Collects data
REPORTS 39W
Collects data
REPORTS 50W