5. Data Report
Data report configuration and sending period are as following:
Min Interval
(Unit:second)
Max Interval
(Unit:second)
Reportable Change
Current Change
≥
Reportable Change
Current Change
<
Reportable Change
Any number between
1~65535
Any number between
1~65535
Can not be 0.
Report
per Min Interval
Report
per Max Interval
The device will immediately send a version packet report along with two uplink packets including ON/OFF status, energy, over
current alarm, dash current alarm, voltage, current and power.
The device sends data in the default configuration before any configuration is done.
Default setting:
MaxTime: Max Interval = 900s (15 min)
MinTime: Min Interval = 2 s
Current Change: 0x0064 (100mA)
Power Change: 0x14 (20W)
Note:
1.
The device reports the ON/OFF status, energy, over current alarm, dash current alarm first, and after 10 seconds reports
the voltage, current and power.
2.
When happened the over-current alarm, it will disconnect the load and the network indicator will quickly flash about 25
times.
Please refer
Netvox LoRaWAN Application Command document
and
Netvox Lora Command Resolver