6
Example of data configuration
FPort
:
0x07
Bytes
1
1
Var (Fix =9 Bytes)
CmdID
DeviceType
NetvoxPayLoadData
CmdID
– 1 byte
DeviceType
– 1 byte – Device Type of Device
NetvoxPayLoadData
– var bytes (Max=9bytes)
Description
Device
Cmd
ID
Device
Type
NetvoxPayLoadData
ConfigReport
Req
R718WBA
0x01
0x6B
MinTime
(2bytes Unit: s)
MaxTime
(2bytes Unit: s)
BatteryChange
(1byte Unit:0.1v)
Temperature
Change (2byte
Unit:0.01℃)
HumidityChange
(
2byte
Unit:0.01%
)
ConfigReport
Rsp
0x81
Status
(0x00_success)
Reserved
(8Bytes, Fixed 0x00)
ReadConfigR
eportReq
0x02
Reserved
(9Bytes, Fixed 0x00)
ReadConfigR
eportRsp
0x82
MinTime
(2bytes Unit: s)
MaxTime
(2bytes Unit: s)
BatteryChange
(1byte Unit:0.1v)
Temperature
Change (2byte
Unit:0.01℃)
HumidityChange
(
2byte
Unit:0.01%
)
(1)
Configure device parameters MinTime = 1min, MaxTime = 1min, BatteryChange = 0.1v
,
TemperatureChange = 1°C,
HumidityChange =1%
Downlink: 016B003C003C0100640064
The device returns:
816B000000000000000000 (configuration success)
816B010000000000000000 (configuration failure)
(2) Read device parameters
Downlink: 026B000000000000000000
The device returns:
826B003C003C0100640064 (device current parameter)