5
5.
Data Report
After power on, the device will immediately send a version packet report. Then, it will send another
report with the data of the value of the liquid level
after it is powered on for 20s.
The device sends data according to the default configuration before any other configuring.
Default setting:
MaxTime: Max Interval = 3min = 180s
MinTime: The MinTime configuration is not available.
*But the software has restriction, MinTime must be configured a number greater than 0.
Note:
Report interval is based on the factory default.
R718PA11 reports the value of the liquid level.
The device reported data parsing please refer to
Netvox LoraWAN Application Command document and Netvox Lora Command Resolver
http://loraresolver.netvoxcloud.com:8888/page/index
Report Configuration
(1) Configure R718PA11 device parameter MaxTime = 1min
Downlink: 0157000A003C0000000000
Device Return:
Description
Device
Cmd
ID
Devic
e
Type
NetvoxPayLoadData
ConfigReport
Req
R718PA11
0x01
0x57
MinTime
(2bytes Unit: s)
MaxTime
(2bytes Unit: s)
Reserved
(5Bytes,Fixed 0x00)
ConfigReport
Rsp
0x81
Status
(0x00_success)
Reserved
(8Bytes, Fixed 0x00)
ReadConfig
ReportReq
0x02
Reserved
(9Bytes, Fixed 0x00)
ReadConfig
ReportRsp
0x82
MinTime
(2bytes Unit: s)
MaxTime
(2bytes Unit: s)
Reserved
(5Bytes,Fixed 0x00)