5. Data Report
Data report configuration and sending period are as following:
Min Interval
(Unit:second)
Max Interval
(Unit:second)
Reportable
Change
Current Change≥
Reportable Change
Current Change
<
Reportable Change
Any number between
1~65535
Any number between
1~65535
Can not be 0.
Report
per Min Interval
Report
per Max Interval
The device will immediately send a version packet report along with an uplink packet including illuminance and battery
voltage.
The device sends data in the default configuration before any configuration is done.
Default setting:
MaxTime : Max Interval = 15 min = 900s
MinTime : Min Interval = 15 min = 900s
BatteryChange: 0x01 (0.1V)
IlluminanceChange:0x0032 (50 Lux)
Illuminance detection range:
0x00 3~65000 Lux (default)
0x01 3~130000 Lux
0x02 3-220000 Lux
Note:
The device report interval will be programmed based on the default firmware which may vary.
The interval between two reports must be the minimum time.
Please refer Netvox
LoRaWAN Application Command document