5. Data Report
The device will immediately send a version packet report along with two uplink packets including temperature, battery voltage,
acceleration and velocity of the X, Y, and Z axes.
The device sends data in the default configuration before any configuration is done.
Default setting:
MaxTime: Max Interval = 60 min = 3600s
MinTime: Max Interval = 60 min = 3600s
BatteryChange = 0x01 (0.1v)
AccelerationChange = 0x0003 (m/s
2
)
ActiveThreshold = 0x0003
InActiveThreshold = 0x0002
RestoreReportSet = 0x00 (DO NOT report when sensor restore)
Three-axis acceleration and velocity:
If the three-axis acceleration of the device exceeds ActiveThreshold, a report will be sent immediately. After the
three-axis acceleration and speed are reported, the three-axis acceleration of the device needs to be lower than
InActiveThreshold, the duration is greater than 5s (cannot be modified), and the vibration stops completely, the next
detection will start. If the vibration continues during this process after the report is sent, the timing will restart.
The device sends two packets of data. One is the acceleration of the three axes, and the other is the speed of the three axes
and temperature. The interval between the two packets is 15s.
Note:
(1)
The device report interval will be programmed based on the default firmware which may vary.
(2)
The interval between two reports must be the minimum time.
Please refer Netvox
LoRaWAN Application Command document
and
Netvox Lora Command Resolver