Assuming that the Active Threshold is set to 10m/s2, the value to be set is 10/9.8/0.0625=16.32,and the last value obtained is
an integer and is configured as 16.
Configure device parameters ActiveThreshold=16, InActiveTime=5
Downlink: 03C8001005000000000000 0010(H
ex)
= 16(D
ec)
Device returns:
83C8000000000000000000 (configuration is successful)
83C8010000000000000000 (configuration failed)
Read device parameters
Downlink: 04C8000000000000000000
Device returns:
84C8001005000000000000 (device current parameter)
6.4 Example for MinTime/MaxTime logic
Example#1
based on MinTime = 1 Hour, MaxTime= 1 Hour, Reportable Change i.e. BatteryVoltageChange=0.1V
MaxTime MaxTime
Sleeping(MinTime)
Sleeping(MinTime)
Note: MaxTime=MinTime. Data will only be report according to MaxTime (MinTime) duration regardless BatteryVoltageChange
value.
Example#2
based on MinTime = 15 Minutes, MaxTime= 1 Hour, Reportable Change i.e. BatteryVoltageChange= 0.1V.
MaxTime
Sleeping(MinTime) sleeping sleeping sleeping
0H
15
th
M 30
th
M 45
th
M
1H
Wakes up and
collects data
3.6V
Does not report
Wakes up and
collects data
3.6V
Does not report
Wakes up and
collects data
3.6V
Does not report
Wakes up and
collects data
REPORTS 3.6V
Wakes up and
collects data
REPORT 3.6V
Wake up and collects data
REPORTS 3.6V
Wakes up and collects data
REPORTS 3.6V
Wakes up and collects data
REPORTS 3.6V